Technical data

45
Does green power `on`
indicator ( ) glow or flash?
Does green power `on`
indicator ( ) flash?
Go to sheet C.
Ensure boiler main on/off
control is set to position ` `.
Is 230 V present across
terminals L and N?
Reset overheat cut-off device
by pressing on the middle of
the transparent rubber cover.
Does the green indicator
flash now?
Check electrical supply and appliance fuses
Sheet A
Check and if necessary
replace 2 A fuses situated
below boiler terminal strip
(spare fuse supplied with
appliance).
If fuse is defective, suspect
wiring fault on external
controls (see note 1).
Does green power `on`
indicator glow now?
Go to sheet B.
Go to sheet C.
Check continuity of overheat
thermostat, replace if
necessary.
Does the green indicator
flash now?
Check transformer (A, fig. 67)
230 V AC primary (black/
red) and approx. 17 V
secondary (blue/brown)
Does the indicator flash now?
Replace electronic boards.
Repair external
wiring fault.
Yes
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Note 1
For test purposes, disconnect
external controls from terminals
3 - 4 and replace with a bridge
between these terminals. If
appliance then operates, the
fault is with the external controls.
No