For the installer Instructions for installation and servicing ecoTEC Wall hung room sealed fan assisted condensing boiler ecoTEC plus 612 ecoTEC plus 615 ecoTEC plus 618 ecoTEC plus 624 ecoTEC plus 630 ecoTEC plus 637 ecoTEC plus 824 ecoTEC plus 831 ecoTEC plus 837 ecoTEC pro 28 ecoTEC pro 24 GB, IE
Contents 1 1.1 1.1.1 1.1.2 1.1.3 1.2 1.3 1.4 1.5 1.6 1.7 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Notes on the documentation . . . . . . . . . . . . . . . . 4 Applicable documents . . . . . . . . . . . . . . . . . . . . . . 4 Retention of documents . . . . . . . . . . . . . . . . . . . . 4 Safety instructions and symbols. . . . . . . . . . . . . 4 Validity of the manual. . . . . . . . . . . . . . . . . . . . . . 4 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents 6 6.1 6.1.1 6.1.2 6.1.3 6.1.4 6.2 6.3 Functional checks (commissioning part II). . Functional checks . . . . . . . . . . . . . . . . . . . . . . . . . Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Water heating (combination boilers only). . . . . Final flush of the heating system (“hot”) . . . . . Handing over to the user . . . . . . . . . . . . . . . . . . . Factory guarantee . . . . . . . .
1 Introduction 1 Introduction 1.1 Notes on the documentation The following information is intended to help you throughout the entire documentation. Further documents apply in combination with this installation and maintenance manual. We assume no liability for any damage caused by non-observance of these manuals. 1.1.1 Applicable documents • Always observe all installation instructions for structural parts and components of the system when installing the ecoTEC plus 937.
Introduction 1 The ecoTEC system boiler consists of models with outputs of 12, 15, 18, 24, 30 and 37 kW. All ecoTEC system boilers are available in Natural Gas. The ecoTEC plus 618 and 630 are also available in LPG. 1.4 General Notes The boilers have been designed for use with a sealed central heating system, and come fully tested and assembled with a built in circulating pump, expansion vessel and diverter valve (ecoTEC combination boilers).
2 Boiler specifications 2 Boiler specifications 2.1 Technical data Technical data CH heat output range 80 °C flow/60 °C return 60 °C flow/40 °C return 50 °C flow/30 °C return 40 °C flow/30 °C return Maximum DHW output 824 ecoTEC plus 831 837 ecoTEC pro 24 28 6.7 – 19.0 6.9 – 19.6 7.1 – 20.2 7.2 – 20.6 8.7 – 24.0 9.0 – 24.7 9.2 – 25.5 9.4 – 26.0 12.0 – 28.0 12.3 – 28.9 12.7 – 29.7 12.9 – 30.3 6.7 – 19.0 6.9 – 19.6 7.1 – 20.2 7.2 – 20.6 9.0 – 24.0 9.3 – 24.7 9.6 – 25.5 9.8 – 26.
Boiler specifications 2 ecoTEC plus Technical data CH heat output range 80 °C flow/60 °C return 60 °C flow/40 °C return 50 °C flow/30 °C return 40 °C flow/30 °C return Category 612 615 4.9 – 12.0 5.1 – 12.3 5.2 – 12.7 5.3 – 12.9 4.9 – 15.0 5.1 – 15.5 5.2 – 15.9 5.3 – 16.
2 Boiler specifications 2.2 Dimensions 9 65 8 190 440 175 241 7 6 642 720 883 125 10 11 12 20 5 4 3 2 1 35 100 45 300 75 130 180 ecoTEC plus 630: 334 ecoTEC plus 637, ecoTEC plus 837: 368 35 100 5 4 3 2 1 Fig. 2.
Boiler specifications 2 2.3 Installation 14 14 1 1 13 13 2 2 3 3 4 4 5 12 12 6 11 5 11 10 7 7 8 9 9 Fig. 2.2 Function elements of combination boilers Fig. 2.
3 General requirements 3 General requirements 3.1 Preliminary remarks for room sealed appliances This appliance should only be installed in conjunction with either a Vaillant flue system or an alternative approved system (details of flue approval categories can be found in the technical section of the installation manual). Install the flue system as detailed in the separate flue installation instructions supplied with this boiler. 3.
General requirements 3 1 8 1 8 2 7 2 7 3 6 4 5 3 6 4 5 Fig. 3.1 Contents included with delivery of ecoTEC plus system boilers Fig. 3.2 Contents included with delivery of ecoTEC plus combination boilers DO NOT remove the boiler from the polystyrene base at this stage. DO NOT remove the boiler from the polystyrene base at this stage.
3 General requirements 1 7 2 Note If the boiler is to be installed in an airing cupboard it is not required to separate the boiler with a non-combustible partition. However installation and servicing clearances must be maintained, and the appliance kept clear of any clothing.
General requirements 3 their contractor. An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891. In IE the current edition of IS 813. Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15 mm). The complete installation must be checked for leaks and purged as described in BS 6891.
3 General requirements A G B F G BCD F H, I J M A A E F F L K LK A G In order to ensure that the condensate plume does not affect adjacent surfaces the terminal should be extended as shown in Fig. 3.9. 2) Dimension F: This clearance may be reduced to 25 mm without affecting the performance of the boiler. However, in order to ensure that the condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferred. For IE, recommendations are given in the current edition of IS 813.
General requirements 3 3.10 Guide to system requirements 3.10.1 Water circulation system Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems). Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possible freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces.
3 General requirements Total heating output Total hardness at 20 l/kW for the smallest boiler heating surface2) Total hardness at > 20 l/kW < 50 l/kW for the smallest boiler heating surface2) Total hardness at > 50 l/kW for the smallest boiler heating surface2) kW mol/m3 mol/m3 mol/m3 < 50 No requirement or < 3 2 0,02 > 50 to ≤ 200 2 1,5 0,02 > 200 to ≤ 600 > 600 1,5 0,02 0,02 0,02 0,02 0,02 1) 1) with systems equipped with wall-hung boiler and systems with electric heating elements 2)
General requirements 3 1.0 1.5 Pressure relief valve setting (bar) 3.0 Total water content of system litres 25 50 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 For system volumes other than those given above, multiply the system volume by the factor across 2.7 5.4 10.9 13.6 16.3 19.1 21.8 24.5 27.2 30.0 32.7 35.7 38.1 40.9 43.6 46.3 49.0 51.8 54.5 3.9 7.8 15.6 19.5 23.4 27.3 31.2 35.1 39.0 42.9 46.8 50.7 54.6 58.5 62.4 66.3 70.2 74.1 78.0 0.109 0.156 Table 3.
4 Boiler installation sequence 4 Boiler installation sequence 4.1 Transporting the appliance Caution! With regards to the Manual Handling Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift. General recommendations when handling Clear the route before attempting the lift. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Do not twist – reposition feet instead.
Boiler installation sequence 4 Positioning of Appliance for Final Installation – in roof space restricting installation. This appliance is deemed to be a one person lift when removed from the carton. Obtain firm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to drop into place onto bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler.
4 Boiler installation sequence 4.2.2 Unpack the boiler To unpack the boiler, cut both plastic carton straps, open box and lift out the polystyrene top packing. Lift the cardboard box upwards. Note Care should be taken not to scratch the white surface of the boiler casing. • Fix the paper template to the wall ensure that the template is vertical. The template shows: – The position of the fixing holes for the boiler mounting bracket. – The position of the connections. – The position of the flue exit hole.
Boiler installation sequence 4 4.5 Installing the flue system • Install the flue system (refer to the seperate air/flue duct installation instructions). 4.6 Fitting the boiler • Lift the boiler (3) up to the wall so that it is slightly above the hanging bracket (1). Note Lift the boiler from either side at the bottom edge • Lower the boiler slowly onto the hanging bracket so that the cross member at the rear of the boiler fully engages onto the hanging bracket. 4.
4 Boiler installation sequence 4.10 Cold water mains inlet and hot water outlet (ecoTEC combination boilers only) 1 7 2 3 4 6 6 5 1 7 2 3 Fig. 4.5 Fitting the gas connection (example ecoTEC plus combination boiler) • Fit the union nut (2) and the compression olive (3) to the gas connection pipe (1) of the boiler. • Fit the union nut (6) and the compression olive (5) to the pre-formed tail provided with ecoTEC plus appliances (7).
Boiler installation sequence 4 Note Flush all foreign matter from the mains supply before connecting to the boiler. • Insert the seal (1) and connect the service valve (2) to the appliance cold water connection. • Fit the union nut (4) and the compression olive (3) to the pre-formed tail provided with ecoTEC plus appliances (5). The diameter of the pipe is 15 mm. • Fully insert the pre-formed tail into the service valve. Tighten the union nuts.
4 Boiler installation sequence 4.12 Heating connection ecoTEC pro combination boiler Caution! When making final connection to the boiler, if using soldered fittings, extra care should be taken to avoid damage to isolation valves through heat transfer. 4.12.1 bar Heating flow and return connection Note Before connecting the heating circuit to the boiler, all pipework and radiators must be thoroughly flushed to remove any installation debris. 2 4 1 3 5 ecoTEC plus combination boiler 13 Fig. 4.
Boiler installation sequence 4 Caution! To ensure fumes do not escape through the syphon of the boiler the trap must be filled with water before the boiler is turned on. Therefore the discharge pipework should be installed so as not to interfere with the removal and refitting of the condensate trap, we recommend the outlet pressure release valve pipe supplied is not shortened. You must leave a bottom clearance of at least 180 mm below the condensate trap for removal and refitting. 4.14.
4 Boiler installation sequence 4.14.2 Connection to the main supply - + 7 89 L N 3 45 - + 7 89 L N 3 45 Fig. 4.14 Wiring system • Connect the flex to the L, N and earth plug to the terminal block. Green/yellow (earth) wire – boiler terminal Earth sign Blue (neutral) wire – boiler terminal N Brown (live) wire – boiler terminal L Fig. 4.13 Opening the electronics box • Remove the front case and lower the control panel.
Boiler installation sequence 4 4.14.3 Electric board layout eBUS accessory connection Burner cable harness Accessory module connection Diagnosis via eBUS, vrnetDIALOG outer probe ext.
4 Boiler installation sequence NTC return NTC flow Ignition electrode X 20/5 red X 20/7 black X 20/8 blue X 20/7 black X 20/13 black Thermal fuse X 20/12 black Gas valve assembly Fan unit Plug in coupling X 20/16 blue (earth) X 20/4 grey (PWM) X 20/3 black (Hall signal) X 20/18 red (24 VDC) X 20/17 red (24 VDC) X 20/9 blue (earth) X 2/16 black A X 2/7 pink B X 2/15 brown C Water pressure sensor X 2/8 blue D Diverter valve X 2/9 black X 2/11 red X 2/12 green Pump Aqua sensor X 2/4 orange X 2/3
Boiler installation sequence 4 NTC return NTC flow Ignition electrode X 20/5 red X 20/7 black X 20/8 blue X 20/7 black X 20/13 black Thermal fuse X 20/12 black Fan unit Gas valve assembly Plug in coupling X 20/16 blue (earth) X 20/4 grey (PWM) X 20/3 black (Hall signal) X 20/18 red (24 VDC) X 20/17 red (24 VDC) X 20/9 blue (earth) X 2/10 black Hot water contact C1/C2 X 2/14 brown Pump Water pressure sensor X 2/9 black X 2/11 red X 2/12 green X 2/4 orange tank NTC connection X 2/10 black X2
4 Boiler installation sequence 4.15 Controls 4.15.1 Vaillant controls and accessories Controller Item no.
Boiler installation sequence 4 4.16 Thermostatic radiator valves The boiler has a built in automatic by-pass valve making it ideal for use in systems with thermostatic radiator valves (no separate system by-pass is required). For optimum fuel economy where TRV’s are used they must be used in conjunction with a boiler control interlock. A programmable room thermostat or separate timer and room thermostat will ensure complete boiler shut down when the heating demand is satisfied.
5 Commissioning Part I 5 Commissioning Part I 5.1 Preliminary electrical checks Check the electrical installation by carrying out short circuit, earth continuity and resistance to earth tests and a check for correct polarity. 5.2 Gas supply The complete gas installation including the gas meter must be inspected, checked for leaks and purged in accordance with BS 6891. In IE the current edition of IS 813. The gas supply to the boiler can be purged by slackening the gas service valve beneath the boiler.
Commissioning Part I 5 The ecoTEC plus combination boiler will be delivered with a filling loop. • Insert the double check valve (1) of the filling pipe at the cold water shutoff valve and secure the double check valve with the spring clip (2). • To fill, first open the stop valve (3). • Open the stop valve (4), so that water flows into the heating system. Fill the heating system as described in Section 5.4.4.
5 Commissioning Part I 5.6 Filling the condensate siphon 1 Fig. 5.5 Adjusting the by-pass valve (in combination boilers) 1 1 Fig. 5.4 Filling the condensate siphon Danger! Note that if the boiler is run with an empty condensate trap there is a danger that fumes might escape into the room and cause poisoning. For this reason, it is important to ensure that the trap is topped up each time the unit is cleaned.
Commissioning Part I 5 If the boiler version corresponds to the local gas family: • Proceed as described below. 1 If the boiler version does not correspond to the local gas family: • Perform the gas conversion in accordance with the gas conversion kit 0020010641. • Adjust the gas setting as described below (see sections 5.9.1 to 5.9.3). The combustion of this boiler has been checked, adjusted and preset at the factory for operation on the type of gas defined on the identification plate.
5 Commissioning Part I Gas flow rate Nominal net heat input in kW as per BS EN 483 nominal + 5% - 10% nominal + 5% - 10% ecoTEC plus 612 12.2 1.29 1.36 1.16 0.95 1.00 0.85 ecoTEC plus 615 15.3 1.62 1.70 1.46 1.19 1.25 1.07 1.29 Boiler Natural gas in m3/h Propane in kg/h ecoTEC plus 618 18.4 1.95 2.04 1.75 1.43 1.50 ecoTEC plus 624 24.5 2.59 2.72 2.33 1.90 2.00 1.71 ecoTEC plus 630 30.6 3.24 3.40 2.91 2.38 2.50 2.14 ecoTEC plus 637 37.8 4.00 4.20 3.
Commissioning Part I 5 • Connect a digital pressure gauge or U-tube manometer (2). • Open the gas isolation valve of the boiler. • Start the boiler by activating the test program P.1 as described in section 8.2. • In addition, ensure that maximum heat can be dissipated into the heating system by turning up the room thermostat. • Alternatively, for ecoTEC combination boilers fully open the hot water taps to ensure full flow rate through the boiler.
5 Commissioning Part I 5.10 Refitting the case 2 1 Appliance ecoTEC plus 612 ecoTEC plus 615 ecoTEC plus 618 ecoTEC plus 624 ecoTEC plus 630 ecoTEC plus 637 ecoTEC plus 824 ecoTEC plus 831 ecoTEC plus 837 ecoTEC pro 24 ecoTEC pro 28 Heating output in kW 5 – 12 5 – 15 7 – 18 9 – 24 10 – 30 12 – 37 7 – 19 9 – 24 12 – 28 7 – 19 9 – 24 Table 5.3 Heating system part load adjustment ranges 5.12 Gas changeover Fig. 5.
Functional checks (commissioning part II) 6 6 6.1 Functional checks (commissioning part II) plus pro Functional checks 6.1.1 Procedure After installing and checking the gas supply pressure, perform a function check before commissioning the appliance and handing over to the user. • Commission the appliance according to the relevant operating manual. • Check the gas supply pipe, exhaust system, heating system and the hot water lines (combination boilers only) for leaks.
6 Functional checks (commissioning part II) • Release water from the system until the system design pressure of 1.0 bar is attained. (The actual reading on the digital pressure gauge should ideally be 0.5 bar plus an additional pressure corresponding to the highest point of the system above the base of the boiler – 10 m head equals an additional 1 bar reading on the pressure gauge. The minimum pressure should not be less than 1 bar in any installation.
Inspection and maintenance 7 7 Inspection and maintenance 7.1 Inspection and maintenance intervals Danger! Risk of injury and risk of damage to property due to neglected inspection and maintenance! Neglected inspection and maintenance works or not observing the stated inspection and maintenance intervals can interfere with the operational safety of the boiler and can result in damage to property and to persons.
7 Inspection and maintenance - Correctness of electrical, water and gas connections. - Correctness of the water pressure. - The condition of the whole system, in particular the condition of radiator valves, evidence of leakage from the heating system and dripping taps. • Correct any faults before proceeding. • Check the boiler for gas and water leaks. • If necessary, refill and re-bleed the heating installation. • Replace the front casing to the boiler.
Inspection and maintenance 7 Note The boiler is fitted with a flue gas analysis point (4). A suitable flue gas analyser can be connected to this point to establish the combustion performance of the boiler. • Remove the front casing. • Start the testing program P.1. • Wait at least 5 minutes until the boiler reaches its operating temperature. • Measure the CO2 concentration at the flue gas analysis point (4). Compare the measured value with the corresponding value in Table 7.1.
7 Inspection and maintenance 7.1.5 Inspection and maintenance work steps Column 2 Maintenance Column 1 must be carried Inspection must out at regular be carried out intervals – but each year no longer than 5 years No. Activity Check the air flue gas installation for leaks and for proper fixation and ensure it is not blocked or damaged and is fitted correctly, complying with the relevant installation instructions. 2 Carry out a general inspection of the boiler for dirt and dust and clean as necessary.
Inspection and maintenance 7 7.2 Servicing the burner module 7.2.1 Removing the burner module The burner module consists of the burner, fan, gas valve und the gas supply (mixer tube). These four components make up the complete assembly, the burner module. • Disconnect the gas supply (3) on the gas valve. Ensure the corrugated gas pipe does not twist by holding the flattened section of the pipe, with an open ended spanner, whilst loosening the union nut.
7 Inspection and maintenance 7.2.3 Checking the burner 7.2.2 Cleaning the integral condensation heat exchanger Caution! Protect the electronics box against sprayed water. 1 1 Fig. 7.5 Checking burner 2 The burner (1) is maintenance-free and needs no cleaning. • Check the burner surface for damage, replace the burner if necessary. • After checking/replacing the burner, re-assemble the burner module in the boiler as described in Section 7.2.4. 7.2.4 Refitting the burner module 3 1 4 Fig. 7.
Inspection and maintenance 7 • Reconnect the gas supply (3) to the gas valve, ensuring that a new sealing washer is used and correctly located. Use the spanner flat at the flexible gas line to hold the gas fittings. 4 10 9 5 11 6 Fig. 7.9 Testing the gas supply for soundness 8 7 • Turn on the gas supply and test for soundness. Check especially the screwed connections (3) and (11). • Refit the air inlet pipe, ensuring that the blue seal in the air intake pipe is correctly located. Fig. 7.
7 Inspection and maintenance • Clean the siphon part section by rinsing it out with water. • Fill the lower part with water until about 10 mm below the upper edge. • Fasten the lower part again on the condensate siphon. 7.4 Checking the expansion vessel 7.6 Test operation Always perform the following checks after completing any maintenance task: • Commission the appliance according to the relevant operating manual. • Check the appliance for gas and water leaks.
Troubleshooting 8 8 Troubleshooting 8.1.2 Diagnostic codes 8.1 Logical fault finding procedure These checks must be carried out before attempting to use the fault finding guide. 1. Carry out electrical safety checks (see section ‘Preliminary Electrical Checks’). 2. Check that the external electricity supply to the boiler is on, and a supply of 230 V~ is present between boiler terminals ‘L’ and ‘N’. 3.
8 Troubleshooting In the diagnostic mode, you can change certain parameters or display more information. The diagnostic information is divided into two diagnostic levels. The second diagnostic level can be reached only after entering a password. Caution! Access to the second diagnostic level must be used exclusively by a qualified technician. First Diagnostic level • Press the “i” and “+” keys simultaneously. The display shows “d.0”.
Troubleshooting 8 Display Meaning Display value/adjustable value d.36 Hot water flow sensor in l/min d.40 Flow temperature Actual value in °C d.41 Return temperature Actual value in °C d.44 Digitised ionisation potential Display range of 0 to 102, > 80 no flame, < 40 even flame d.47 Outside temperature (with weather compensating Vaillant controller only) Actual value in °C d.67 Remaining burner anti cycling time in min d.76 Appliance variant (device specific number) 00 to 99 d.
8 Troubleshooting Display Meaning Display value/adjustable value d.50 Offset for minimum speed in rpm/10, adjustment range: 0 to 300 d.51 Offset for maximum speed in rpm/10, adjustment range: -99 to 0 d.58 From the third quarter of 2006: Activation of solar reheating d.60 Number of safety temperature limiter cut offs Setting range: 0 to 3 0 = solar reheating disabled (factory setting) 3 = activation of min. hot water target value = 60 °C for solar reheating Quantity d.
Troubleshooting 8 Code Meaning F.10 Flow NTC short circuit Cause NTC broken, NTC cable broken, Defective connection at NTC, Defective connection at electronics NTC broken, NTC cable broken, Defective connection at NTC, Defective connection at electronics NTC defective, short circuit in cable harness, cable/casing shortcut F. 0 Flow–NTC open circuit F.11 Return NTC short circuit NTC defective, short circuit in cable harness, cable/casing shortcut F.13 Tank NTC short circuit F.
8 Troubleshooting 9 Parts replacement 8.2 Test programs Special functions can be triggered on the appliances by activating various test programs. These programs are given in detail in the Table 8.5. • The test programs P.0 to P.6 will be started when “Power ON” is turned on and the “+” key is pressed for 5 s. The display shows “P.0”. • Press the “+” key to start counting the test number upwards. • Press the “i” to operate the appliance now and to start the test program.
Parts replacement 9 9.2 Replacing burner Danger! Before replacing the component, comply with the safety instructions in Section 9.1. • Dismantle the burner module as described in Section 7.2.1. 1 2 1 4 3 Fig. 9.1 Replacing burner • Loosen the 4 screws (1) on burner, and remove the burner. • Mount the new burner with a new seal. Ensuring that the notch in the burner aligns with the burner viewing window. • Install the burner module as described in Section 7.2.4.
9 Parts replacement 9.4 Replacing expansion vessel 9.5 Danger! Before replacing the component, comply with the safety instructions in Section 9.1. • Disconnect the appliance from the mains as described in Section 9.1, and close the service valve in the gas supply pipe. • Close the flow and return service valves and drain the water from the boiler. Replacing primary heat exchanger Danger! Before replacing the component, comply with the safety instructions in Section 9.1.
Parts replacement 9 9.6 Replacing electronics and display Danger! Before replacing the component, comply with the safety instructions in Section 9.1. • Comply with the assembly and installation manuals provided with the spare parts. 1 2 3 Fig. 9.6 Primary heat exchanger holder • Disconnect the plug-in connection (2) of the thermal fuse in the primary heat exchanger. • Remove the three screws (3) on the primary heat exchanger holder.
10 Recycling and disposal 11 Vaillant service 10 Recycling and disposal Both the Vaillant ecoTEC and the associated transport packaging consist primarily of recyclable raw materials. The Vaillant ecoTEC and all accessories and packaging must not be disposed of in the normal household rubbish. Make sure that the old unit and any existing accessories and the transport packaging is handed over to a proper disposal organisation.
Appendix Appendix EG declaration of conformity
Installation, Commissioning and Service Record
Please affix the label from the rear cover of the control box over this area.
SERVICE INTERVAL RECORD 0020008345-06 It is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record Below . Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the boiler manufacturer’s instructions. Always use the manufacturer ‘s specified spare part when replacing all controls.
839592_12 GBIE 062010 — Subject to alterations