Technical data
Adapting the boiler to the heating installation
Installation and maintenance instructions ecoTEC pro 0020129672_03 43
11
T
Feed
(target)
[°C]
Set maximum burner anti-cycling time [min]
1 5 10 15 20 25 30 35 40 45 50 55 60
20 2.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0
25 2.0 4.5 9.2 14.0 18.5 23.0 27.5 32.0 36.5 41.0 45.0 50.0 54.5
30 2.0 4.0 8.5 12.5 16.5 20.5 25.0 29.0 33.0 37.0 41.0 45.0 49.5
35 2.0 4.0 7.5 11.0 15.0 18.5 22.0 25.5 29.5 33.0 36.5 40.5 44.0
40 2.0 3.5 6.5 10.0 13.0 16.5 19.5 22.5 26.0 29.0 32.0 35.5 38.5
45 2.0 3.0 6.0 8.5 11.5 14.0 17.0 19.5 22.5 25.0 27.5 30.5 33.0
50 2.0 3.0 5.0 7.5 9.5 12.0 14.0 16.5 18.5 21.0 23.5 25.5 28.0
55 2.0 2.5 4.5 6.0 8.0 10.0 11.5 13.5 15.0 17.0 19.0 20.5 22.5
60 2.0 2.0 3.5 5.0 6.0 7.5 9.0 10.5 11.5 13.0 14.5 15.5 17.0
65 2.0 1.5 2.5 3.5 4.5 5.5 6.5 7.0 8.0 9.0 10.0 11.0 11.5
70 2.0 1.5 2.0 2.5 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5
75 2.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
11.2 Effective burner anti-cycling times
11.1.6 Setting the maintenance interval
You can define maintenance intervals for the ecoTEC pro.
After the set burner operating hours have elapsed, in addi-
tion to the current flow temperature, the maintenance sym-
bol
(open-end spanner) appears in the display and this
shows that the boiler must be serviced. The display on the
eBUS controller (accessory) shows the information "Mainte-
nance" "MAIN".
Heat demand
Number of
persons
Burner operating hours until the
next inspection/service
(depending on the system type)
5.0 kW
1 - 2
2 - 3
1,050 h
1,150 h
10.0 kW
1 - 2
2 - 3
1,500 h
1,600 h
15.0 kW
2 - 3
3 - 4
1,800 h
1,900 h
20.0 kW
3 - 4
4 - 5
2,600 h
2,700 h
25.0 kW
3 - 4
4 - 6
2,800 h
2,900 h
> 27.0 kW
3 - 4
4 - 6
3,000 h
3,000 h
11.3 Guideline values for operating hours
> Set the operating hours until the next service using diag-
nosis code "d.084".
Guideline values for the setting can be found in
¬ table 11.3. The values stated correspond to an average
boiler operating time of one year.
You can set the operating hours in increments of ten from
0 to 3,000 h.
If you do not enter a figure under diagnosis code "D.084"
but instead enter the symbol "–", then the "Maintenance
display" function is not active.
i
On completion of the set operating hours, you
must set the maintenance interval again in diag-
nosis mode.
11.1.7 Setting the by-pass valve
The boilers have a by-pass valve.
The pressure is adjustable in the range between 17.0 MPa
(170 mbar) and 35.0 MPa (350 mbar). Approx. 25.0 MPa
(250 mbar) is pre-set (mid-position). The pressure changes
by approx. 1.0 MPa (10 mbar) each time the adjusting screw
is rotated. By turning right, the pressure increases and turn-
ing left decreases it.
1
11.1 Setting the by-pass valve