Installation Manual

Instructions for installation and servicing ecoTEC plus 0020020828_0738
• Remove valve cap from expansion vessel charge point.
Check that the internal charge pressure of the expan-
sion vessel is to the correct design pressure. If the
pressure is lower than this the vessel should be re
pressurised using an air pump.
Refit the valve cap.
Re pressurise boiler and heating system.
8.1.11 Re commissioning the boiler
Carry out electrical safety checks.
Turn on the electrical supply.
Open the boiler CH service valves.
Carry out function checks of boiler operation as previ-
ously detailed.
Check gas rate as previously detailed.
Check for water leaks.
Refit case, ensuring that a good seal is obtained.
8.1.12 Test operation
Always perform the following checks after completing
any maintenance task:
Commission the appliance according to the relevant
operating manual.
Check the appliance for gas and water leaks.
Check the air/flue gas system for leaks, check its
fastening
Check for ignition and an even flame on the burner.
Check that the heating system is working.
Fill out the Benchmark gas boiler commissioning
checklist at the rear of this guide.
9 Combustion analysis
h
Note!
The boiler is fitted with a flue gas analysis
point. A suitable flue gas analyser can be con-
nected to this point to establish the combus-
tion performance of the boiler.
9.1 Check
CO
2
content
Refer to table 9.1 and if necessary set (air-ratio adjustment).
h
Note!
Combustion analysis must be carried out at an-
nual service if a flue gas analyser is available, if
no analyser is available then visual checks
should be carried out as per service schedule.
Checking/adjustment of this value is also re-
quired in the following instances: replacement
of gas valve, conversion to or from natural gas/
LPG or if incorrect combustion is suspected!
flue gas analysis point
Fig. 9.1 Analysis point
Remove the front and inner cover.
• To correct combustion follow the procedure as listed
below.
• Ensure that the gas supply pressure is correct (see
table 5.1)
• The gas inlet working pressure can be checked at the
pressure test point on the gas valve (fig 5.3.).
• Turn gas supply on.
• Ensure there is an external heat demand.
• Enter the test programs by holding the “+” key, see fig
6.2. and turning power on.
• Press “+” until “P.1” is displayed for max rate.
• Press “ i ” to operate appliance in this mode.
• Allow appliance to stabilise.
• Measure the CO2 at the combustion analysis point
point, see fig 9.1.
• Check CO2 value (for case off) as stated in table 9.1 for
the boiler installed.
8 Inspection and maintenance
9 Combustion analysis