Installation Manual

Instructions for installation and servicing ecoTEC plus 0020020828_0730
6 Natural gas to LPG conversion
6 Natural gas to LPG conversion
The ecoTEC plus is able to be field adjusted for use on
LPG – propane G31 gas. To enable conversion the use of
a flue gas analyser is necessary.
a
Caution!
After converting from natural gas to LPG, com-
mission and check boiler function as described
in commissioning section of the servicing and
installation instructions.
a
Caution!
This conversion must only be carried out by a
competent person approved at the time by the
Health and Safety executive and in accordance
with the gas safety (installation and use) regu-
lations 1998.
Before starting any work:
Isolate the electrical supply to the boiler.
Turn off the gas supply at the gas service cock fitted
to the appliance.
Turn the gas valve “A” throttle screw (Ref fig.6.1) fully
clockwise.
Turn the “A” throttle screw back anti-clockwise the
required number of turns as stated in Table 9.1 for the
boiler installed.
Ensure the gas analyser is set to the correct fuel
setting propane.
To obtain conversion follow the procedure as listed below.
Ensure that the gas supply pressure is in the range 34 - 37
mbar. The gas inlet working pressure can be checked at the
pressure test point on the gas valve (fig 5.3.).
Turn gas supply on.
Ensure there is an external heat demand.
Enter the test programs by holding the “+” key, see
fig 6.2. and turning power on.
Press “+” until “P.1” is displayed for max rate.
Press “ i ” to operate appliance in this mode.
Allow appliance to stabilise.
• Measure the CO
2
at the flue gas analysis point, see
fig 9.1.
• Check CO
2
value (for case off) as stated in table 6.1
for the boiler installed.
Model
LPG
G31 % CO
2
after 5mins at full load Throttle Maximum
Case off Case on Adjustment CO/CO
2
ratio
ecoTEC plus 415 10.1 + 0.5 - 0.5 10.3 + 0.5 - 0.5 5 turns
<0.0026
ecoTEC plus 418 10.1 + 0.0 - 1.0 10.3 + 0.0 - 1.0 5 turns
<0.0026
ecoTEC plus 428 10.5 + 0.3 - 0.8 10.7 + 0.3 - 0.8 5 turns
<0.0026
ecoTEC plus 438 9.8 + 0.2 - 0.8 10.0 + 0.2 - 0.8 8 turns
<0.0026
Table 6.1 LPG settings
• If required, using a screwdriver, adjust the “A” throttle
to obtain correct value. (rotating anti-clockwise to
increase). Appliance will remain in this mode for 15 mi-
nutes or exit by pressing “ i ” and “+” simultaneously.
• Repeat the process above and select “P.2” for min rate.
Press “ i ” to operate appliance in this mode.
Allow appliance to stabilise.
• Check CO
2
value (for case off) as stated in table 6.1
for the boiler installed.
• If required, using a 2mm allen key, adjust the “B” offset
to obtain correct value. (rotating clockwise to increase)
After checking the combustion, exit by pressing “ i ”
and “+” simultaneously
Refit the chassis panel and the inner case. (Note the
CO
2
will increase slightly).
Fit the LPG conversion label to the type plate.
Lift the control box into place and fit the front casing.
Commission the boiler as described in the Installation
and Servicing Instructions supplied with the boiler.
"A" throttle – "Pmax" rotate
to increase
"B" offset adjustment
"Pmin" rotate
to increase
Fig. 6.1 Gas control valve
Fig. 6.2 ecoTEC plus controls