For the heating engineer Installation and maintenance instructions ecoTEC plus 937 VUI GB; IE
Contents Contents 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Notes on the documentation ................................4 Documents also having validity ..............................4 Storing documents .....................................................4 Symbols used...............................................................4 Validity of the manual ...............................................4 Identification plates ...................................................4 CE label ............................
Contents 6.5 6.6 6.7 6.8 6.9 6.9.1 6.9.2 6.9.3 6.10 6.11 6.12 Flushing the system for the first time ("cold")..41 Filling the condensate drain trap ..........................41 Setting the pump output .........................................41 Adjusting the bypass ................................................41 Checking the gas setting ....................................... 42 Checking for tightness of the flue gas installation and flue gas recirculation................
1 Notes on the documentation 1 Notes on the documentation 1.4 The following information is intended to help you throughout the entire documentation. Further documents apply in combination with this installation and maintenance manual. We accept no liability for any damage caused by failure to observe these instructions. 1.1 This installation manual applies exclusively to the unit with the following part number: – 0010003809 The part number of the unit can be obtained from the identification plate.
Notes on the documentation 1 Unit description, data and dimensions 2 1.7 2 Benchmark 2.1 i 1.8 Vaillant Ltd. supports the Benchmark Initiative. You will find the Benchmark Logbook on the last page of this instruction manual. It is very important that this document be filled out properly when installing, commissioning and handing-over to the owner of the installation. Gas Council Number Appliance Gas council Number ecoTEC plus 937 47-044-39 Table 1.
2 Unit description, data and dimensions 2.
Unit description, data and dimensions 2 2.3 Dimensions 440 8 323 9 175 241 7 6 20 35 100 243 10 11 35 100 5 Fig. 2.
2 Unit description, data and dimensions 175 241 440 8 642 720 883 6 7 130 180 198 20 5 4 3 2 1 35 35 100 100 5 4 3 2 1 Fig. 2.
Unit description, data and dimensions 2 2.4 Structure and functional elements 1 The ecoTEC plus 937 consists of – a modified combination boiler and – a 15 litre shift load storage tank. Mains cold water heated by the combi unit is fed to the heat insulated storage tank by means of a modulating storage tank charging pump. The combi unit supplies the shift load storage tank with electrical energy for the storage tank charging pump. 2 3 13 1 12 4 2 3 4 5 5 11 Fig. 2.
2 Unit description, data and dimensions 2.5 Functional description 1 15 20 2 14 3 19 4 13 5 18 12 6 7 8 a 9 b c 21 10 16 17 11 Fig. 2.
Unit description, data and dimensions 2 Safety 3 The ecoTEC plus 937 is a fully-automatic wall-mounted unit with condensing technology for central heating and hot water preparation and with a shift load storage tank for the storage of hot water. Mains cold water heated by the combi boiler is fed to the heat insulated storage tank by means of a modulating storage tank charging pump.
3 Safety The unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and/or knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety. Children must be watched to ensure that they do not play with the unit. The appliance is designed to generate heat for closed hot water central heating systems and for instantaneous hot water supply.
Safety 3 Preliminary remarks for room sealed appliances This appliance should only be installed in conjunction with either a Vaillant flue system or an alternative approved system (details of flue approval categories can be found in the technical section of the installation manual). > Install the flue system as detailed in the separate flue installation instructions supplied with this boiler. 3.4 General requirements 3.4.
4 General requirements 4 General requirements 4.1 Pos.
General requirements 4 It is possible to mount onto a wall made of flammable material if the regulations of the Local Authority and the legal building regulations are fulfilled. In this case however, the unit would have to be mounted in a specially made enclosure. (You can also use an existing cabinet or existing enclosure as long as it can be modified accordingly to suit the new application.
4 General requirements 4.5 542 The following information applies to both flue pipe systems. a) The terminal position must be located in such a position that any flammable gases can be freely dissipated. b) A plume of water vapour will sometimes be visible from the flue terminal. Positions where this could be a nuisance should be avoided.
General requirements 4 Location of the junction mm A Directly under or above an opening or the horizontal to an opening, a hollow ventilation tile, an opening window etc. 300 B Under gutters, soil pipes or drainpipes 75 C Unter eaves 200 D Under balconies 200 E From vertical drainpipes and down-pipes 25 F From external and internal corners 300 G Above the ground, a roof or a balcony 300 H Opposite another surface 600 I Opposite another termination 1200 J Next to an opening (e.
4 General requirements 4.8 System requirements 4.8.1 Water circulation system 4.8.2 Filling and preparation of the heating system Detailed recommendations concerning the water circulation system can be taken from BS 6798 and BS 5449, Part 1 (for "Small Bore” and "Micro Bore” central heating systems).
General requirements 4 – Jenaqua 110 – Sentinel X 100 – Sentinel X 200 Heating water qualities Additives for frost protection intended to remain permanently in the system – Fernox Antifreeze Alphi 11 – Sentinel X 500 > Inform the operator of the necessary measures in case you have used any of these additives. > Inform the operator of the required procedures for frost protection. > Observe the applicable national regulations and technical standards for the treatment of filling and top-up water.
4 General requirements 4.8.5 Heating circuit expansion vessel 4.9 Details for the pumps The boiler of the ecoTEC series are equipped with a 10 litre expansion vessel which is suitable for a sealed heating system with a maximum water volume of 100 litres. If the nominal capacity of the boiler expansion vessel is not adequate for the heating system (e.g. when modernising old open systems) an additional expansion vessel can be fitted outside the boiler.
Sequence of operations during installation 5 5 5.1 Sequence of operations during installation Transporting the appliance Important: With regards to the Manual Handling Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift. General recommendations when handling > Clear the route before attempting the lift. > Ensure safe lifting techniques are used – keep back straight – bend using legs. > Keep load as close to body as possible.
5 Sequence of operations during installation > > > > > packing and remove carton by sliding up over the boiler. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Always use assistance if required. Dispose of packaging in a responsible manner. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance outside packaging.
Sequence of operations during installation 5 165/246 Required minimum gaps/assembly clearances min 5.2 min 5 min 5 min 500 the flue pipe is installed in accordance with the installation instructions for the flue pipe provided – all the required pipework including the pressure relief valve and the condensate drain can be fitted. Further information concerning the installation location of the combi boiler can be found in the Section 3.4 "Installation Location". min 180 5.3 Fig. 5.
5 Sequence of operations during installation 5.4 > drill 2 holes Ø 10 mm in the wall for the hanging bracket. Using the installation template 40 b 80/125 (Art.-Nr. 303210) 276 ( ) 140 173 195 ( 80/125 60/100 ) 223 256 (Art.-Nr. 303910) 60/100 25 A Caution! Material damage as a result of inadequate installation. The combi-heater may come loose from the wall and fall if the wall or fixing material is unsuitable.
Sequence of operations during installation 5 5.7 Fitting the appliance hanging bracket 5.8 Mounting the combination boiler 1 1 2 2 3 Fig. 5.3 Shift load storage tank with hanging bracket > Fix the hanging bracket (1) to the wall using the plugs and screws (2) provided with the appliance. > Lift the shift load storage tank out of the packaging (see Section 5.1). > Lift the shift load storage tank (3) onto the wall so that it is located slightly above the hanging bracket (1).
5 Sequence of operations during installation 5.9 Removing the front case 5.11 2 Gas connection a Danger! Risk of death caused by improper gas installation. An improper gas installation may impair the operational safety of the appliance and result in material damage or personal injury. > The gas installation should only be fitted by a competent person approved at the time by the Health and Safety Executive and in accordance with the gas safety (installation and use) regulations 1998.
Sequence of operations during installation 5 5.12 1 Connecting the hot and cold water a Danger! Risk of scalding and damage due to leaking water. Possible leaks in water pipes. > Make sure there is no tension in the supply lines when they are installed. b Caution! Risk of damage to gas shut-off valves caused by heat transfer. If the final connections are soldered, the heat transferred during the process may damage the gas shut-off valves. > Use extra care when soldering.
5 Sequence of operations during installation > Push the union nut (4) with the inserted olive (3) onto the copper tail (5) included with the combi boiler. The diameter of this pipe is 15 mm. > Insert the copper tail into the cold water isolating valve up to the stop. Tighten the union nuts in this position. > Insert the fibre seal (7) and screw the copper tail (6) which is included with the storage tank module, to the hot water connection on the unit. The diameter of this pipe is 15 mm.
Sequence of operations during installation 5 5.14 Connecting the heating supply and return lines a Danger! Risk of scalding and damage due to leaking water. Possible leaks in water pipes. > Make sure there is no tension in the supply lines when they are installed. b Caution! Risk of damage to service valves caused by heat transfer. If the final connections are soldered, the heat transferred during the process may damage the service valves. > Use extra care when soldering.
5 Sequence of operations during installation 5.15 Installing the condensate drain line a a Danger! Risk of poisoning due to an improperly installed condensate drain line. Blockages in the condensate drain line may cause exhaust gas to escape. > Install the condensate drain line in such a way that blockages are prevented. > Leave an access space of at least 180 mm underneath the trap. Danger! Risk of poisoning from escaping exhaust gas.
Sequence of operations during installation 5 i 5.17 min. 180 We recommend that the discharge pipe for the pressure relief valve is not shortened. Connecting the drain hose to the pressure relief valve of the stratified storage tank Fig. 5.12 Installation space condensate siphon There must be a minimum clearance of 180mm below the siphon for access. 1 5.16 Connecting the drain pipe to the pressure relief valve 2 Fig. 5.
5 Sequence of operations during installation 5.19 Electrical connection ance with BS 6500, Tables 6, 8 or 16 (3 x 0.75 to 3 x 1.5 mm2). 5.19.1 General requirements e Danger! Risk of fatal electric shock from live connections. Voltage is continuously present in the L and N terminals of the turquoise coloured plug, even when the main switch is turned off.
Sequence of operations during installation 5 > Pull the electronics box forward and lower. > Unclip the back cover of the electronics box and lift the cover upwards to reveal the connections. 5.19.3 Establishing the power supply b Caution! Risk of damage to the appliance. The electronics may be damaged via a mains supply at terminals 7, 8, 9 and "BUS". > Only connect the mains supply cable to the terminals marked for the purpose. 1 2 - + 7 89 3 L N 3 45 Fig. 4.
5 Sequence of operations during installation 5.19.
Sequence of operations during installation 5 Flow temperature sensor (NTC) Return temperature sensor (NTC) Ignition electrode X 20/5 red X 20/7 black X 20/8 blue X 20/7 black X 20/13 black Thermal fuse X 20/12 black Gas valve Fan Plug connection X 20/16 blue (Earth) X 20/4 grey (PWM) X 20/3 black (Hall-Signal) X 20/18 red (24 VDC) X 20/17 red (24 VDC) X 20/9 blue (Erde) X 2/16 black A X 2/7 pink B X 2/15 brown C Water pressure sensor X 2/8 blue D X 2/9 black Diverter valve X 2/11 red Pump X 2
5 Sequence of operations during installation Shift load storage tank electronics X 1/3 Violet Storage tank charging sensor (NTC) X 1/1 Black X 1/4 orange Storage tank sensor (NTC) X 1/1 Black X 1/6 Blue Inlet sensor SWT (NTC) X 1/1 Black Aqua-Sensor X 1/7 Green X 1/1 Black Pump X 1/8 red Plug connection X 1/2 Brown X 1/2 brown X 1/1 Black X 1/1 Black X40 X 1/10 Black 7 8 9 24V L N 3 230V 4 5 X12 — + BUS X31 X 1/11 Red X41 X 1/9 Grey Boiler electronics box Fig. 5.
Sequence of operations during installation 5 5.20 Control units 5.20.1 Vaillant control units and accessories Controller Item no.
5 Sequence of operations during installation tral heating. (Hot water preparation is not affected by this function. Hot water can be drawn off at any time.) 5.20.4 Optional plug-in timers by Vaillant Further details for the connection can be found in the relevant instructions of the accessories. The cover on the electronics box should be replaced after all the electrical connections have been made. The cover is secured with two clips. 5.
Commissioning, Part I 6 6 6.1 Commissioning, Part I Preparatory checks of the electrical system > Check the electrical installation for short circuits, proper earthing and earth resistance and for correct polarity. 6.2 Gas supply a Danger! Risk of explosion caused by escaping gas. When the gas line is bled, gas may leak and possibly ignite. > Provide adequate ventilation whilst doing the work. > Extinguish all naked flames. > Do not smoke while bleeding the gas line.
6 Commissioning, Part I 6.4.2 Filling device for ecoTEC plus 937 The ecoTEC plus 937 is fitted with a filling loop. > Push the double check (1) of the filling loop into the cold water stop valve (2) and secure the double check valve (1) with the spring clip (4). > First open the stop valve to perform the filling (3). > Open the cold water stop valve (2) so that the water flows into the heating system. Fill the heating system as described in Section 6.4.3.
Commissioning, Part I 6 6.5 Flushing the system for the first time ("cold") i The entire heating system must be flushed through completely at least twice: once cold and once hot, in accordance with the following instructions. > Check if all radiator thermostat valves and both stop valves on the combi boiler are open. > Connect a hose to the drain valve which is located at the lowest position in the heating system.
6 Commissioning, Part I 6.9 Checking the gas setting a 6.9.1 Caution! Malfunctions or reduction in working life of the boiler! If the boiler version does not correspond to the local gas family, there will be malfunctions or you have to change components of the boiler ahead of schedule, e. g. do not use a LPG boiler on natural gas. > Before starting up the boiler compare the details of the type of gas specified on the identification plate with the type of gas supplied at the installation site.
Commissioning, Part I 6 6.9.2 Checking the gas flow rate 1 The boiler is fitted with a multifunctional automatic gas valve which ensures that the precise air/gas ratio is provided under all operating conditions. The gas flow rate has been set during production and does not require adjustment. With the front casing fitted check the gas flow rate of the boiler as follows: > Start the boiler by activating the test program P.1 as described in section 9.2.
6 Commissioning, Part I check if there is any blockage in the pipework or if the pipework is undersized. > If the supply pressure is out of tolerance contact your Emergency Service Provider.
Commissioning, Part I 6 Commissioning Part II: Functional checks 7 The setting mode is also de-activated if a button is not pushed within a period of 4 minutes. Appliance Heating output in kW ecoTEC plus 937 12 - 28 7 Commissioning Part II: Functional checks 7.1 Functional checks 7.1.1 Method of procedure Table 6.3 Setting the part load ranges of the heating system 6.
7 Commissioning Part II: Functional checks – Knob setting "c“ – Knob setting "a“ 35 °C 65 °C 1 a Fig. 7.2 Display in heating mode 7.1.3 Hot water operation > Switch on the appliance. > Open the hot water tap fully. > Press "i" to activate the status indicator. If the hot water operation is operating properly, the display shows "S.14". b 1 c a c 1 Fig. 7.
Commissioning Part II: Functional checks 7 The symbol " “ is displayed. > Turn the hot water temperature control knob to the temperature you require. > Press "i" to activate the status indicator. During the storage tank charging the display shows "S.24“. > > > Fig. 7.5 Display during storage tank charging > i When operating the appliance in the winter, the tank charging function is limited in order to prevent the heating installation from cooling down.
7 Commissioning Part II: Functional checks 8 Inspection and maintenance > Leave the operating and installation instructions with the operator of the appliance. > Go through the operating manual with the user and answer any questions. > Draw special attention to the safety instructions, which the user must follow. > Instruct the user about the methods used for combustion air supply and flue conducting. In particular, point out that these measures must not be altered.
Inspection and maintenance 8 We recommend the conclusion of an inspection and maintenance contract with an approved company or installer. The inspection serves to determine the actual condition of the respective boiler and compare it with the specified condition. This is done by measuring, checking and observing. Maintenance is required in order to eliminate any deviations of the actual condition from the specified condition.
8 Inspection and maintenance Always perform the following steps prior to inspection or maintenance work: > Switch off the main switch. > Disconnect the boiler from the power mains by – disconnecting the mains plug or – de-energising the boiler via an isolating device with a contact opening of at least 3 mm (e. g. fuses or power switches). > Further check for electrical isolation of the appliance by use of a test meter. > Close the gas isolation valve.
Inspection and maintenance 8 8.1.4 Adjusting the CO2 concentration (or the air ratio) a Danger! Increased risk of poisoning due to incorrect settings! Incorrect setting may increase the risk of poisoning. > If one of the flue gas values is greater than the acceptable values in Table 8.1 then check - the integrity of the complete flue gas installation - the integrity of the combustion circuit seals - the gas inlet working pressure - the gas flow rate.
8 Inspection and maintenance 8.1.5 Inspection and maintenance work steps Column 2 Maintenance Column 1 must be carried Inspection must out at regular be carried out intervals – but each year no longer than 5 years No. Activity 1 Check the air flue gas installation for leaks and for proper fixation and ensure it is not blocked or damaged and is fitted correctly, complying with the relevant installation instructions.
Inspection and maintenance 8 8.2 Maintaining the compact thermal module 8.2.1 Removing the compact thermal module a Danger! Risk of burns caused due to hot components. The compact thermal module, all water-carrying parts and the heating water may become hot and cause burns or scalding. > Only work on these components if these parts have cooled down. > Unscrew the screw (2) and remove the air inlet pipe (1). > Separate the gas supply line (3) from the gas valve.
8 Inspection and maintenance 8.2.2 Cleaning the integral condensation heat exchanger If necessary, the heat-exchanger can be cleaned using ordinary vinegar. b 8.2.3 Caution! Risk of damage to the electronics. Water may damage the electronics and cause power failures. > Protect the open switch box from spray water. Checking the burner 1 > Dismantle the compact thermo module as described under 8.2.1. 1 Fig. 8.5 Checking the burner The burner (1) is maintenance-free and needs no cleaning.
Inspection and maintenance 8 flats of the spanner on the flexible gas pipe to hold the gas fittings in position. 4 10 9 5 11 Fig. 8.9 Checking the gas supply for leaks 6 8 7 > Turn on the gas supply and check for leaks. Pay particular attention to fittings (3) and (11). > Re-connect the air inlet pipe (1) and make sure that the blue seal is correctly located in the air inlet pipe. Fig. 8.7 Fitting the thermo-compact module 8.
8 Inspection and maintenance > Fill the lower section with water until about 10 mm below the upper edge. > Re-fit the lower section to the condensate siphon. 8.4 Cleaning strainer in cold water supply There is a strainer in the cold water supply to the combi boiler which must be cleaned during maintenance. > Isolate the unit from the electric mains in the appartment as described in 9.2. > Close the cold water stop valve on the inlet combination (see Fig. 8.11) and drain the unit from the hot water side.
Inspection and maintenance 8 8.6 Checking filling pressure of the expansion vessel of the shift load storage tank i This check need not be performed every year – a check every three years is sufficient. > Close the stop valves of the hot water system. > Release the pressure from the appliance. > Release the screw on the top cover of the shift load storage tank and remove the cover. 2 8.
9 Troubleshooting 9 Troubleshooting 9.1.1 9.1 Logical fault finding procedure The status codes which you can see in the display provide information concerning the current operating status of the unit. Proceed as follows to display the status codes: Carry out the following checks before the actual troubleshooting: > Carry out the tests to check electrical safety (see Section "Preparatory Checks on the Electrical System").
Troubleshooting 9 Display Meaning Heating mode: S.0 No heat demand S.1 Fan running S.2 Pump running S.3 Ignition S.4 Burner ignited S.5 Fan and pump running S.6 Fan over run S.7 Pump overrun time S.8 Anti-cycling mode 9.1.2 In the diagnostic mode, you can change certain parameters or display more information. The diagnostic information is divided into two diagnostic levels. Access to the second diagnostic level can only be permitted after entering a password.
9 Troubleshooting Display Meaning Displayed value/settable value d.0 Heating partial load Adjustable heating partial load in kW (factory setting: max. output) d.1 Water pump over run time for heating mode 2 - 60 minutes (factory setting: 5 minutes) d.2 Max. anti cycle time heating at 20°C flow temperature 2 - 60 minutes (factory setting: 20 minutes) d.3 Measured value of the domestic hot water temperature in °C d.4 Measured value for the warmstart sensor in °C d.
Troubleshooting 9 Second diagnostic level > As described above in the first diagnostic level, scroll through to the diagnosis number d.97. > Change the displayed value to 17 (Password) and push the button "i". You are now in the second diagnostic level where all information from the first diagnostic level (see Table 9.2) and the second diagnostic level (see Table 9.3) is displayed. Scroll and change values and exit diagnosis mode as described in the first diagnosis level.
9 Troubleshooting Display Meaning Displayed value/settable value d.72 Pump overrun time after warm start or shift load storage tank charging Setting range in seconds: 0, 10, 20 to 600 Factory setting: 80 d.73 Offset for warm start target temperature Setting range: -15 K to +5 K (Factory setting: 0K) d.74 Legionella protection shift load storage tank Setting range: 0 = deactivated 1 = activated (Factory setting) d.
Troubleshooting 9 Code Meaning Cause F.0 Flow NTC open circuit F.01 Return NTC open circuit F.02 Shift load storage tank charging (NTC) open circuit, only in combination with F.91 NTC faulty, NTC cable faulty, faulty plug connection on NTC, faulty plug connection on the electronics NTC faulty, NTC cable faulty, faulty plug connection on NTC, faulty plug connection on the electronics NTC faulty, NTC cable faulty, faulty plug connection on NTC, faulty plug connection on the electronics F.
9 Troubleshooting Code Meaning Cause F.74 Signal water pressure sensor in the wrong range (too high) Harness to water pressure sensor has a short-circuit at 5 V / 24 V or internal fault in water pressure sensor F.
Troubleshooting 9 Replacing components 10 9.2 Test programmes Display Meaning P.0 Bleeding test program. The heating circuit and the hot water circuit are bled via the automatic air vent (the cap of the automatic air vent must be released two turns). P.1 Test programme where the appliance is operated in full load after successful ignition. P.2 Test program where the appliance is operated with minimum gas volume (ignition gas volume) after successful ignition P.3 not available P.
10 Replacing components 10.2 Replacing the burner a 10.3 Danger! Risk of personal injury and/or material damage as a result of non-compliance with the safety instructions. > Before replacing the component, comply with the safety instructions in Chapter 10.1. > Dismantle the compact thermo module as described under 8.2.1. Replacing the fan or the gas valve a > > > > Danger! Risk of personal injury and/or material damage as a result of non-compliance with the safety instructions.
Replacing components 10 > Release both fixing screws (5) on the gas valve and remove the fan from the gas valve. > Replace the faulty component. b Caution! Possible material damage caused by improper installation. The gas valve and the fan may be damaged as a result of incorrect installation. > Fit the gas valve and the fan in the same position as before. 1 2 > Screw the fan onto the gas valve. Use new seals. > Re-install the complete "gas valve/fan" unit in reverse sequence.
10 Replacing components 10.5 Replacing the primary heat exchanger a Danger! Risk of personal injury and/or material damage as a result of non-compliance with the safety instructions. > Before replacing the component, comply with the safety instructions in Chapter 10.1. > Disconnect the appliance from the mains as described in Chapter 10.1, and close the gas isolator valve in the gas supply pipe. > Close the stop valves in the flow and return pipes and drain the water out of the combi boiler.
Replacing components 10 b b Caution! Possible material damage caused by loosening or retightening the screws. The primary heat exchanger may become damaged. > You must not loosen or tighten the four screws (fig. 8.4, 1). Caution! Possible material damage caused by lubricating the seals. Mineral oil-based lubricants may damage the seals. The seals should therefore not be lubricated. > Only use water or commercially available soft soap, if necessary, to assist with installation.
10 Replacing components > After completion of the work check the system for gas leaks and carry out a function test (see Section 8.8). 1 10.8 6 Replacing the aqua sensor a 5 4 Danger! Risk of personal injury and/or material damage as a result of non-compliance with the safety instructions. > Before replacing the component, comply with the safety instructions in Chapter 10.1. > Isolate the unit from the mains as described in Section 10.1. > Close the gas isolator valve in the gas supply pipe.
Replacing components 10 > Fit the pipe elbow onto the new Aqua-Sensor and use new gaskets. > Mount the new Aqua-Sensor in reverse order and replace the seals. > Connect the line plug of the Aqua-Sensors with the wiring harness. > Re-fit the discharge pipe (1) and use new gaskets. > Filling and vent the combi boiler and the shift load storage tank. > After completion of the work check the system for water leaks and carry out a function test (see Section 8.8). 10.
11 Recycling and disposal 12 Vaillant service 11 Recycling and disposal 12 Vaillant service Both the gas fired boiler and its transport packaging consist mainly of recyclable raw materials. To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
EC declaration of conformity EC declaration of conformity Installation and maintenance instructions ecoTEC plus 937 0020031552_06 73
Installation and maintenance instructions ecoTEC plus 937 0020031552_06
Installation, Commissioning and Service Record Installation and maintenance instructions ecoTEC plus 937 0020031552_06 75
Installation and maintenance instructions ecoTEC plus 937 0020031552_06
Installation and maintenance instructions ecoTEC plus 937 0020031552_06 77
0020031552_06 GBIE 102010 — Subject to alterations