Technical data
Inspection and maintenance
Installation and maintenance instructions ecoTEC plus 0020116700_06  59
12
Settings
Unit Natural gas (H) Propane
CO
2
 after 5 minutes full
load mode with 
boiler front casing fitted
Vol.–%
7.8 - 10.2 9.7 - 10.7
CO
2
 after 5 minutes full
load mode with boiler 
front casing removed
Vol.–%
7.6 - 10.0 9.5 - 10.5
Set for Wobbe index Ws  kWh/m
3
15 22.5
CO value with full load ppm < 250 < 250
CO/CO
2
< 0.0031 < 0.0026
12.1 Factory gas setting
a
 Danger!
Risk to life due to poisoning!
CO is an extremely toxic gas. Risk to life 
due to excessive CO concentrations.
 > If you are not able to adjust the boiler 
correctly and the flue gas values remain 
higher than allowed in ¬table12.1, call 
the Vaillant Service Solutions (0870 
6060 777).
 > Do not start up the boiler!
12.1.5  Performing the gas family check
a
 Danger!
Risk to life due to poisoning!
CO is an extremely toxic gas. Risk to life 
due to excessive CO concentrations. Fault 
codes F.92 or F.93 may occur as result of 
the gas family check.
 > Correct the failure unconditionally before 
starting up the boiler for continuous 
operation.
Menu ¬ Installer level ¬ Test programs ¬Gas family 
check
The gas family check checks the boiler setting with regard 
to combustion quality.
 > Perform the gas family check:
 – as part of regular boiler maintenance
 – after replacing components or working on the gas 
route.
i
 No CO/CO
2
 or CO
2
 measurement is possible dur-
ing the gas family check.
Result Meaning Response
F.92 Coding 
resistor fault
The coding 
resistor on the 
PCB does not 
match the 
entered gas 
family
 > Check the coding resistor, 
repeat the gas family check 
and enter the correct gas fam-
ily.
"successful" Combustion 
quality is good. 
Appliance con-
figuration 
matches the 
specified gas 
family.
None
"Warning" Combustion 
quality insuffi-
cient. CO
2
 value 
and CO/CO
2
ratio are incor-
rect.
 > Start test program P.01 and 
adjust the CO
2
 value with the 
adjusting screw in the venturi 
¬section 12.1.4.
 > If the correct CO
2
 value cannot 
be set:
Check the gas restrictor for 
correctness (yellow: H-gas, 
grey: liquid gas) and damage.
 > Repeat gas family check. 
F.93 Gas 
group fault
Combustion 
quality outside 
the permitted 
range
 > Damaged or incorrect gas 
restrictor (yellow: H-gas, grey: 
liquid gas), wrong gas group, 
internal pressure measuring 
point in venturi blocked (do not 
use lubricants on O-ring in ven-
turi.), recirculation, faulty seal.
 > Resetting the boiler.
 > Set correct CO
2
 value using 
test program P.01 (adjusting 
screw in venturi) 
¬section12.1.4.
 > Repeat the gas family check.
12.2 Results and measures after gas family check