Technical data
Adapting the boiler to the heating installation
Installation and maintenance instructions ecoTEC plus 0020116700_06  49
11
Code Parameters Adjustable values
Factory 
 setting
Your own 
setting
D.000 Heating partial load Adjustable heating partial load in kW
Auto: Boiler automatically adjusts max. partial load to cur-
rent system demand
Auto
D.001 Overrun time of internal pump for 
heating mode
1 - 60 min 5 min
D.002 Max. burner anti-cycling time heating 
at 20 °C flow temperature
2 - 60 min 20 min
D.003 Outlet temp. actual value In °C Not 
 adjustable
D.004 Measured value of hot water sensor In °C Not 
 adjustable
D.005 Flow temperature target value 
(or return target value)
In °C, max. of the value set in d.71, limited by an eBUS con-
troller if connected)
Not 
 adjustable
D.006 Hot water temperature target value 
(VUW boilers only)
35 to 65 °C Not 
 adjustable
D.007 Warm start temperature target value 
(only with VUW boilers)
Cylinder temperature target value 
(only with VU boilers)
40 to 65 °C 
15 °C frost protection, then 40 to 70 °C;
(max. temperature can be adjusted under D.020)
Not 
 adjustable
D.008 Room thermostat at terminal RT Room thermostat open (no heat requirement)
Room thermostat closed (heat requirement) 
Not 
 adjustable
D.009 Target value from external eBus con-
troller
In °C Not 
 adjustable
D.010 Status of internal pump On, Off Not 
 adjustable
D.011 Status of external heating pump On, Off Not 
 adjustable
D.012 Status of cylinder charge pump On, Off Not 
 adjustable
D.013 Status of hot water circulation pump  On, Off Not 
 adjustable
D.014 Target pump speed 
(high-efficiency pump)
Not relevant Not 
 adjustable
D.015 Actual pump speed 
(high-efficiency pump)
Not relevant Not 
 adjustable
D.016 Room thermostat 24 V DC open/
closed
Heating mode Off/On Not 
 adjustable
D.017 Heating flow/return regulation 
changeover
Control type: flow, return  Flow
D.018  Pump operating mode setting Comfort (continuously operating pump)
Eco (intermittently operating pump)
Eco
D.019 Operating mode of 2-stage pump Setting for operating mode of 2-stage pump:
0 = Burner operation = stage 2, Flow/overrun = stage 1; 
1 = Heating + Overrun = stage 1, Hot water = stage 2,
2 = Like 1, but rotational speed during heating mode 
depending on heating partial load,
3 =always stage 2
4 =  Rotational speed during heating mode depending on 
heating partial load, otherwise always stage 1
2
D.020 Max. setting for cylinder target value Setting range: 50 °C - 70 °C (actoSTOR 65 °C) 65 °C
D.022 Hot water requirement via C1/C2, 
impeller or APC
On, Off Not 
 adjustable
D.023 Summer/winter operating mode 
(heating on/off)
Heating on, heating off (summer mode) Not 
 adjustable
D.025 Hot water generation enabled by 
eBUS controller
On, Off Not 
 adjustable
11.1   Diagnosis codes