Technical data
Commissioning
Installation and maintenance instructions ecoTEC plus 0020116700_06  41
10
Display Meaning
P.00 
1)
Purging test program
The heating circuit and the hot water circuit are purged 
using the automatic air vent (the cap of the automatic 
air vent must be released).
1 x right selection button: Start heating circuit purging
2 x right selection button ("  ->  "): Start purging 
hot water circuit
3 x right selection button ("  ->  "): Restart heating 
circuit purging
1 x left selection button ("Cancel"): Exit purging pro-
gram
The internal pump is cyclically actuated. 
Note: The purge program runs 7.5min per circuit.
P.01 Maximum load test program:
The boiler is operated at maximum heat input after suc-
cessful ignition.
P.02 Minimum load test program:
The boiler is operated at minimum heat input after suc-
cessful ignition.
P.06 Filling mode test program:
The diverter valve (VUV) is moved to the mid-position. 
The burner and pump are switched off (to fill or drain 
the boiler).
10.1 Overview of the test programs
1)
  Purging the heating circuit:
Diverter valve in heating position, actuation of internal pump 
for 9 cycles: 30s on, 20 s off. Display: "Active heating circuit".
  Purging the hot water circuit:
After the above-mentioned cycles have run or the right selec-
tion button has been pressed again: Diverter valve in the hot 
water position, actuation of the internal pump as above. Display: 
"Active hot water circuit".
i
  If you do not press a button for more than 
15minutes. the test programs are stopped auto-
matically. The boiler switches to normal operat-
ing mode.
To terminate the test programs, you can press the left 
selection button ("Cancel") at any time.
P.00 Exhaust
Cancel
Heating circuit
1,0 bar
10.1  Boiler in error condition
i
  If the boiler is in error condition, you cannot 
start any test programs. You can detect an error 
condition by the fault symbol shown in the left 
bottom corner of the display. You must first 
reset.
10.5  Preparing the heating water
Pay attention to the specifications concerning heating 
water preparation in (¬section2.5.7).
10.6 Read off the filling pressure 
The boiler is equipped with an analogue pressure gauge 
(¬fig. 3.1 and 3.2) and also has a symbolic bar display for 
the filling pressure of the heating installation and a digital 
pressure and temperature display.
You can see the pressure gauge once you have removed 
the front casing of the boiler.
Press the right selection button twice to read off the digital 
filling pressure value.
10.7  Filling and purging the  heating installation 
b
 Caution.
Risk of damage caused by contaminated 
lines.
Foreign bodies such as welding remnants. 
sealing residue or dirt in the water lines can 
cause damage to the boiler.
 > Flush the heating installation thoroughly 
prior to commissioning.
 The system is filled via a customer-installed filling connec-
tion, which must be attached in a suitable position in the 
heating circuit. This connection must be removed again 
after the filling process is complete. If the local Water 
Authority regulations do not allow temporary connection a 
sealed system filler pump with break tank must be used. 
The heating system will not be filled automatically from the 
domestic hot water side. (Alternative methods of filling 
sealed systems are given in BS 5449). The ecoTEC plus 
combination boilers can be filled via the built in filling lopp 
under the boiler (¬fig. 10.3).
 To ensure the correct operation of the heating installation, 
the indicator on the pressure gauge must point to the 
upper half of the grey area or in the middle of the bar 
graph display (marked by the dashed limit value) when the 
heating installation is cold. This corresponds to a filling 
pressure of between 0.1MPa and 0.2MPa (1.0bar and 
2.0bar).
You can display the exact filling pressure (¬section10.6).










