Technical data
Flue gas installation
Installation and maintenance instructions ecoTEC plus 0020116700_06  27
7
Location
Minimum
dimensions
A
Directly below an opening, air brick, opening win-
dows, etc.
300mm
B Above an opening, air brick, opening window, etc. 300mm
C
Horizontally to an opening, air brick, opening win-
dow, etc.
300mm
D
Below temperature-sensitive building components 
e.g. plastic gutters, soil pipes or drain pipes
75mm
E Below eaves 200mm
F Below balconies or car port roof 200mm
G From a vertical drain pipe or soil pipe 150mm
H From an internal or external corner 200mm
I Above ground, roof or balcony level 300mm
J From a surface facing the terminal 600mm
K From a terminal facing the terminal 1200mm
L
From an opening in the car port (e.g. door, win-
dow) into the dwelling
1200mm
M Vertically from a terminal on the same wall 1500mm
N Horizontally from a terminal on the same wall 300mm
O From the wall on which the terminal is mounted 0 mm
P From a vertical structure on the roof N/A
Q Above intersection with roof 300mm
R
Horizontally to a window or opening on pitched or 
flat roofs
600 mm
S
Above a window or opening on pitched or flat 
roofs
600 mm
T
Below a window or opening on pitched or flat 
roofs
2000 mm
7.1 Position of the termination in a fan-assisted air/flue gas 
duct
BS5440–1 It is recommended that the fanned flue terminal 
should be positioned as follows:
a)  at least 2 m from an opening in the building directly 
opposite, and
b)  so that the products of combustion are not straightly 
directed to discharge across a boundary.
1)  Dimensions D, E, F and G:
These clearances may be reduced to 25mm without 
affecting the performance of the boiler. In order to 
ensure that the condensate plume does not affect 
adjacent surfaces the terminal should be extended as 
shown in ¬fig.7.6.
2) Dimension H:
This clearance may be reduced to 25mm without 
affecting the performance of the boiler. However, in 
order to ensure that the condensate plume does not 
affect adjacent surfaces a clearance of 300mm is pre-
ferred. For IE, recommendations are given in the cur-
rent edition of IS813.
For 1 and 2 above you can use the Variable Termination Kit 
to move the termination point away from the building fab-
ric.
Article numbers:
0020060584 - White
0020060585 - Black
7.6 Termination of air/flue gas duct under balcony or eaves