Technical data

Instructions for Use, Installation and Servicing ecoMAX pro 17
10 Gas, Water and Condensate connections 
10.1 Gas Connection
Before connection check the supply of local gas.
The gas supply can be connected from below, or through 
the wall at the rear of the boiler.
Ensure the supply pipe is fully engaged in the 
compression fitting on the gas service valve inlet. See 
Fig. 10.1. and refer to section 4.3.
10.2 Water Connections
Provision is made for the water connections to be made 
from above the boiler, see Fig. 10.2 (using the two 22mm 
compression couplers supplied). The position is shown 
on the wall template.
Flush out the domestic hot water and the heating 
systems before connecting to the boiler.
10.3 Condensate Drain Connection
The condensate drain connection is at the rear of the 
boiler, see Fig. 10.1. A 21.5 mm plastic overflow pipe 
should be connected to the spigot on the condense trap 
(using the coupler). The drain pipe should have a fall of 
a least 2.5° away from the boiler. Condensate should, 
if possible be discharged into the household internal 
drainage system. If this is not practicable, discharge 
can be allowed into the external household drains or a 
purpose designed soak away. 
 It is recommended that any external condensate drain 
pipe is insulated and also preferably of 32mm diameter, 
to prevent freezing in adverse weather conditions.
The condensate is discharged periodically in ‘slugs’ by 
siphonic action.
It is not necessary to provide air breaks or extra traps 
in the discharge pipe, as there is already a 75mm high 
trap inside the boiler. Fitting an extra trap may cause 
the boiler siphon to work incorrectly. Refer to BS 6798 
and BS 5546 for advice on the disposal of the boiler 
condensate.
Fig 10.2
12692
Fig 10.1
12691










