Technical data
Fig. 3.5 Art.–No. 303 209
Fig. 3.6 Art.–No. 303 200
3.8 Flue termination
The following details refer to both flue systems.
a.The terminal must be positioned such that the produc-
ts of combustion can disperse freely at all times.
b.A plume of water vapour will sometimes be visible
from the flue terminal. Positions where this could be a
nuisance should be avoided.
c. If the terminal is fitted less than 2 m above a balcony,
above ground or above a flat roof to which people
have access then a suitable terminal guard must be
provided and fitted (made by Tower Flue Components,
Tonbridge, TN9 1TB).
Fig. 3.7 Flue termination
Note:
Vertical flues must not terminate within 600
mm of an openable window, air vent or any other
ventilation opening.
The flue assembly shall be so placed or sheilded as to
prevent ignition or damage to any pary of the building.
Terminal position mm
A Directly below an opening, above an opening or
horizontal to an opening, air brick, opening window, etc. 300
B Below gutters, soil pipes or drain pipes 75
C Below eaves 200
D Below balconies 200
E From vertical drain pipes and soil pipes 25
F From internal or external corners 300
G Above ground, roof or balcony 300
H From a surface facing a terminal 600
I From a terminal facing a terminal 1200
K Vertically from a terminal on the same wall 1500
L Horizontally from a terminal on the same wall 300
M Distance from adjacent for vertical Flue 500
Table 3.3 Terminal position for a fan assisted concentric flue
A
BCD
A
G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
A
A
1530
880
70
70
1103
70
15
13