Technical data

7 Gas supply adjustments (Commissioning Part II)
Instructions for Installation and Servicing turboMAX plus and thermoCOMPACT R132
Gas Rate thermoCOMPACT 615/2 E Output[kW]
Gas type 6.5 8.0 10.0 12.0 14.0 15.0
Natural gas 2H Gas Rate
1)
[m
3
/h]
Main burner jet mark
2)
for G20
0.8 1.0 1.3 1.4 1.7 1.7
7 / 120
Gas Rate thermoCOMPACT 620/2 E Output[kW]
Gas type 7.7 8.0 10.0 12.0 14.0 16.0 18.0 20.0
Natural gas 2H Gas Rate
1)
[m
3
/h]
Main burner jet mark
2)
per G20
0.9 1.0 1.2 1.4 1.7 1.9 2.1 2.3
7 / 120
Gas Rate thermoCOMPACT 624/2 E, turboMAX plus 824/2 E Output[kW]
Gas type 8.9 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
Natural gas 2H Gas Rate
1)
[m
3
/h]
Main burner jet mark
2)
for G20
1.1 1.2 1.4 1.7 1.9 2.1 2.4 2.6 2.8
7 / 120
Gas Rate thermoCOMPACT 628/2 E, turboMAX plus 828/2 E Output[kW]
Gas types 10.4 12.0 14.0 16.0 18.0 20.0 22.0 24.0 26.0 28.0
Natural gas 2H Gas Rate
1)
[m
3
/h]
Main burner jet mark
2)
per G20
1.3 1.5 1.7 1.9 2.1 2.4 2.6 2.8 3.1 3.3
7 / 120
Gas Rate thermoCOMPACT 637E, turboMAX plus 837 E Output[kW]
Gas type 10.5 12.0 16.0 18.0 20.0 24.0 28.0 30.0 33.0 36.9
Natural gas 2H Gas Rate
1)
[m
3
/h]
Main burner jet mark
2)
per G20
1.3 1.5 1.9 2.2 2.4 2.8 3.3 3.5 3.9 4.3
7 / 120
Burner Pressure thermoCOMPACT 637, turboMAX plus 837 E Output[kW]
Gas type Ignition rate 10.5 12.0 16.0 18.0 20.0 24.0 28.0 30.0 33.0 36.9
Natural gas 2H Burner pressure
1)
[mbar]
Main burner jet mark
2)
for G20
1.2 1.2 1.5 2.5 3.1 3.8 5.3 7.1 8.1 9.7 12.0
7 / 120
Setting-up program: P.11 mid. setting point pressure: 5.3 mbar
LPG 3 B/P
Burner pressure
1)
[mbar]
Main burner jet mark
2)
for G30 2.8 2.8 3.5 5.9 7.3 8.9 12.6 16.8 19.1 22.9 28.2
7 / 072 for G31 3.5 3.5 4.4 7.3 9.1 11.1 15.6 20.8 23.7 28.3 34.9
Setting-up program: P.13 mid. setting point pressure: 15.3 mbar
Table 7.1: Burner pressure
Table 7.2: Gas flow rate 1) 15 °C, 1013mbar, dry
2) The nozzles are stamped with the mark shown in this table.
The marking corresponds to the nozzle hole diameter multiplied by 100