F. Blow out or use a soft-bristled brush to remove dust and dirt
from the smoke chamber base.
G. Line up the new smoke chamber with the optical base by
aligning the arrows on the smoke chamber to the latches on the
optical base and snap down into place.
H. Replace the alarm cap by lining up the cap with the smoke
alarm. Then insert the cap into the smoke alarm and turn
clockwise approximately 15 degrees. The cap snaps firmly into
place when secure.
I. Insert the batteries into the smoke alarm using the proper
polarity, and replace the battery compartment cover.
J. Reattach the smoke alarm to its mounting base (see “Mounting
the Sensor).
K. Test the smoke alarm sensitivity and contact the Central
Monitoring Station to place the system back online (remove from
Test mode).
L. Verify all auxiliary functions for a complete test of the system.
Low Battery
Replace the batteries per Section 5 - Installing / Replacing Battery.
9. Troubleshooting
Detector does not power up properly or reports low battery
Be sure the battery is fully seated within the battery compartment and
the polarity is correct.
Check the battery voltage (3.0 VDC nominal).
Control Panel does not respond
Use a wireless RF Sniffer to confirm that the product is sending
messages for activation.
Be sure the detector is enrolled into the control panel properly.
Be sure you are using a compatible control panel.
Tamper condition does not restore
Be sure the product is installed properly onto the mounting plate and
the mounting plate has a magnet.
Be sure there are no trouble indications at the detector.
Be sure you are using a compatible control panel.
If a tamper alarm occurs
Be sure you are using a compatible control panel.
Be sure the control panel is in sensor test mode during sensor testing.
Alarm/open condition does not restore
Be sure the smoke or heat has cleared at the product.
Be sure you are using a compatible control panel.
10. Specifications
Compatible panels DLC-100
RF Wireless Frequency 915 MHz (NA)
RF Distance LOS
See Section 6.
Power Two CR123 batteries
Battery type
3.0 VDC lithium
Panasonic
®
CR123A, Duracell DL123A
Standby Current
35 µA (typically)
Battery life 5 years (typically)
Sensor Photoelectric
Sensitivity 2.2% +/- 1.3% / ft.
Drift Compensation Adj. 0.5% / ft. max.
Heat Detection - Fixed 135°F ± 5°F (57.2°C ± 2.8°C)
Heat Rate-of-Rise
15°F/min>105°F (8.3°C/min>
40.6°C)
Audible alarm 85 dBA @ 10’ (3M) temporal 3
Low Battery Beep 1 every 45 seconds.
Weight w/batteries 0.20 lbs / 0.09 kg
Dimensions 5.6" x 2.4" (14.2cm x 6.1cm)
Storage temperature -4 to 140°F (-20 to 60°C)
Operating environment 32 to 100°F (0 to 38°C)
Relative Humidity 0 to 95% non-condensing
11. Regulatory Information pending agency approvals.
Manufacturer: Edwards, A Division of Walter Kidde Portable Equipment,
Inc. (Edwards)
RoHs Directive
2011/65/EC RoHS Compliant. Hereby, Edwards declares that this
product does not contain lead, mercury, cadmium, hexavalent
chromium, polybrominated biphenyls (PBB) or polybrominated diphenyl
ethers (PBDE) in more than the percentage specified by EU directive
2011/65/EC, except exemptions stated in EU directive 2011/65/EC
annex.
Agency Rating
ANSI/UL 268, CSFM
FCC Compliance
FCC ID: QPY-SA915FFH
IC: 8303B-SA915FFH
The device complies with part 15 of the FCC Rules as well as Industry
Canada Rules and Regulations license-exempt RSS standard(s).
Operation is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired
operation.
Conformité Réglementaire
Ce dispositif est conforme à la réglementation de la IC et (Partie 15) de
la FCC. Son fonctionnement est soumis à deux conditions : (1) ce
dispositif ne doit pas causer d’interférences nuisibles, et (2) ce dispositif
doit accepter toute interférence reçue, y compris les interférences
pouvant entraîner des conditions de fonctionnement indésirables.
Optical
base
Smoke
chamber
Detector
cap
Smoke
chamber
latch
Alignment
arrows