Simon XT
Installation Manual
50
No activity tm
a
Off Determines whether the panel sends a No Activity report to a central station when the
programmed time period elapses (on), or if the feature is disabled (off).
No activity means control panel, remote handheld, and key-chain touchpad buttons
have not been pressed and sensors have not been tripped within a specified period of
time (except sensors in group 25).
The timeout can be set from 02 to 24 hours.
Autophone test
b
Off Determines whether the panel automatically performs a periodic phone test (on) or not
(off). The test interval can be from 001 to 254 days. The time of day the panel performs
the test is determined by Supervisory Time, which must be turned on for this feature to
work.
Supervisory
time
12:00am Determines when the panel reports supervisory conditions (sensor failures) and
automatic phone tests to the central station.
The panel clock must be set to the correct time for this option and the automatic phone
test to work correctly.
Alarm cancel 006 Sets the time frame that determines whether the panel reports an alarm cancel
message to the central station. If the system is disarmed from an alarm state within the
programmed time, the panel sends an alarm cancel message to the central station. An
alarm cancel message is not reported if the system is disarmed after the programmed
time expires.
The time can be set from 006 to 255 minutes. When set to 255, the panel always reports
alarm cancel messages. Turning off this option disables alarm cancel reporting.
RF time-out 12 hours Determines the time period the panel must receive at least one supervisory signal from
learned sensors before identifying a sensor failure and sounding trouble beeps. Any
sensor failure is reported immediately and again at the supervisory time (Supervisory
Time). The timeout can be set from 02-36 hours. Entries must be two digits.
Fail-to-open
time
a
Off Determines whether the panel sends a Fail to open report to a central station if the
system has not been disarmed by the programmed time (on), or not (off).
System time must be set correctly for this feature to work.
Fail-to-close
time
a
Off Determines whether the panel sends a Fail to Close report to a central station if the
system has not been armed by the programmed time (on), or not (off).
System time must be set correctly for this feature to work.
Siren time-out 005 minutes Determines how long sirens sound alarms if no one is present to disarm the system. The
time can be set from 002 to 254 minutes. When this feature is turned off, sirens sound
alarms until the alarm is canceled (system is disarmed).
Arm LED
shutdown
Off Determines whether the panel LEDs (buttons) turn off 30 seconds after the last button
press (on) or remain on for the entire arming period (off).
Unvacated
premises
On Determines whether the system automatically arms down to level 2 (doors and
windows) if the user arms the system to level 4 (doors, windows, and motion sensors)
without leaving the premises (on), or remains at the armed level chosen by the user (off).
This feature does not work from a keyfob. Autobypass must be on for this feature to
work.
Table 20. Timers (continued)
Function Default Description