User Manual

Table Of Contents
Simon XT
Installation Manual
20
Table 8 describes nonprogrammable (hard-coded) system operation, as required to meet ANSI-SIA CP-01, and
is provided only for your reference.
Central station reporting
The panel has been tested with the following central station receivers using SIA and Contact ID reporting
formats:
Note: Before beginning installation, installers must verify compatibility with the following central station receivers.
Radionics D6600 central station receiver
Sur-Gard central station receiver with models SG-DRL2A and SG-CPM2
CS5000 digital alarm communicator receiver
UL Canada listed installations
This section describes the requirements for CUL (UL Canada) listed installations.
Canadian standards CSA certified accessories
Standard Class 2, 9 VAC, 3.34 A power transformer (GE Security model 22-153-CN).
Residential burglary alarm system unit (ORD-C1023-1974)
Basic system as described for UL 1023 listed installations plus:
Hardwired magnetic contact (13-068 or 13-071) or wireless learn mode door/window sensor (60-670)
Siren timeout set to six minutes or more
Table 8. Nonprogrammable (hard coded) system operation
Function Operation
Silent exit All annunciators enabled
Remote arming exit time and
progress annunciation
All annunciators enabled
Abort annunciation Enabled
Cancel report annunciation Enabled
Recent closing Enabled (2 minute window)
Exit error Enabled
Restoration of power Panel resumes operation in same arming state and disregards alarm signals from sensors
for the first 60 seconds after power restoration
Cancel alarm Enter code only.