Chapter 3
Installing the system
19
The following settings are in addition to UL 1023 and 985 and are required only if the system is set up for
central station reporting.
• Phone mod 1 set to zero or one.
• Automatic phone test set to 001.
• RF timeout set to four hours.
• AC power failure report set to on.
• CPU low battery report set to on.
• Fail to communicate set to on.
• Entry delay plus the dialer delay must not exceed 60 seconds.
SIA system requirements
SIA system requirements are the same as those described for a UL listed basic system on page 1, plus:
• If multiple annunciation is required, use hardwired siren part no.13-046.
Note: UL requirements take priority over SIA requirements. Entry delay must not exceed 60 seconds.
SIA setting requirements
Table 7 describes programming requirements to meet ANSI-SIA CP-01 (see System programming on page 39).
Note: Call waiting services should be disabled to prevent interrupting panel communication to the central monitoring station..
Table 7. SIA setting requirements
Function Programming page
reference
Default setting Required setting
Entry delay Table 20 on page 49 30 seconds 30 to 240 seconds
Exit delay Table 20 on page 49 60 seconds 45 to 240 seconds
Dialer delay Table 15 on page 43 30 seconds 15 to 45 seconds
Autoarm Table 13 on page 41 On On
Unvacated premises Table 20 on page 49 On On
Call waiting Table 15 on page 43 Off On if reporting to central station and
customer has call waiting service
Exit extension Table 13 on page 41 On On
Swinger shutdown Table 18 on page 47 On (one trip) On (one trip)
Fire alarm verify Table 18 on page 47 Off On
Duress/panic code Table 23 on page 52 Disabled Disabled
Cross zone Cross-zoning on
page 10
Disabled Disabled for zones with high probability of
false alarms.