Installation Manual
18
UL listed installations
Some installations may require configurations dictated by city/state codes, insurance, or Underwriter’s
Laboratories (UL). This section describes the various component and configuration listings.
Basic system:
• Control panel: backup battery 6 V 1.2 Ah (34-025) (Portalac model # PE6V1.2)
• Standard class 2, 9 VAC, 3.34 A power transformer (GE model # 22-153).
• Hardwired siren (13-374)
Household burglary alarm system unit (UL 1023), basic system plus the following:
• Hardwired magnetic contact (13-068 or 13-071) or wireless learn mode door/window sensor (60-670)
• Panel piezo beeps set to on
• Entry delay set to 45 seconds or less
• Exit delay set to 60 seconds or less
• RF time-out set to 24 hours
• Control panel alarms turned on
• Autoarm set to on
• Siren timeout set to five minutes or more
• Trouble beeps set to on
• RF jam detect set to on
• Hardwired siren supervision set to on
• Exit extension set to off
• Quick exit set to off
Household fire warning system (UL 985), basic system plus the following:
• Wireless smoke sensor 60-848-95 learned into sensor group 26
• Panel piezo beeps turned on
• Control panel alarms set to on
• Siren timeout set to four minutes or more
• Trouble beeps set to on
• RF jam detect set to on
• Hardwired siren supervision set to on
• Smoke supervision must be set to on
UL 1023 & 985 24-hour backup:
• For 24-hour backup, the total current draw for all connected devices is limited to 250 mA (during
normal standby conditions) using a 1.2 AH battery.
UL 1635 digital alarm communicator system:
• Same as UL 1023 & 985, plus: