UL listed installations
Some installations may require configurations dictated by city/state codes, insurance, or Underwriter’s
Laboratories (UL). This section describes the various component and configuration listings.
Basic system:
Control panel: backup battery 6 V 1.2 Ah (34-025) (Portalac model # PE6V1.2)
Standard class 2, 9 VAC, 3.34 A power transformer (GE model # 22-153).
Hardwired siren (13-374)
Household burglary alarm system unit (UL 1023), basic system plus the following:
Hardwired magnetic contact (13-068 or 13-071) or wireless learn mode door/window sensor (60-670)
Panel piezo beeps set to on
Entry delay set to 45 seconds or less
Exit delay set to 60 seconds or less
RF time-out set to 24 hours
Control panel alarms turned on
Autoarm set to on
Siren timeout set to five minutes or more
Trouble beeps set to on
RF jam detect set to on
Hardwired siren supervision set to on
Exit extension set to off
Quick exit set to off
Household fire warning system (UL 985), basic system plus the following:
Wireless smoke sensor 60-848-95 learned into sensor group 26
Panel piezo beeps turned on
Control panel alarms set to on
Siren timeout set to four minutes or more
Trouble beeps set to on
RF jam detect set to on
Hardwired siren supervision set to on
Smoke supervision must be set to on
UL 1023 & 985 24-hour backup:
For 24-hour backup, the total current draw for all connected devices is limited to 250 mA (during
normal standby conditions) using a 1.2 AH battery.
UL 1635 digital alarm communicator system:
Same as UL 1023 & 985, plus: