User Manual
Table Of Contents
- Preface
- Chapter 1 Introduction
- Chapter 2 Planning
- Chapter 3 Installing the system
- UL listed installations
- SIA system requirements
- Central station reporting
- UL Canada listed installations
- California state fire marshall listed installations
- Opening panel cover and chassis
- Mounting the panel
- Connecting hardwired devices
- Wiring a phone line to the panel
- Wiring the power transformer
- Installing X10 modules
- Chapter 4 Programming
- Programming overview
- Menu navigation
- System programming
- Resetting memory to the factory defaults
- Chapter 5 Testing
- Chapter 6 Troubleshooting and support
- Appendix A Specifications and tables
- Index
Simon XT
Installation Manual
10
Cross-zoning
Cross-zoning (two-trip) refers to two different group 18 sensors that must be tripped within two minutes of
each other to report an alarm to the central station. Figure 2 shows the path of a person walking from the
kitchen to the living room. When the person is detected walking through the kitchen, the motion sensor in the
kitchen is tripped, sounding a local alarm. If motion is detected by the living room motion sensor within two
minutes, an alarm report will be sent to the central station.
Figure 2. Cross-zone diagram
Note: We do not recommend cross-zoning for exit/entry zones. Each zone can individually protect the intended area.
31
32
33
34
35
36
37
38
39
40
Table 5. Sensor assignments/locations (continued)
Sensor # Device Sensor
group
Sensor name/location Notes
Motion sensor
Motion sensorPath of
person walking