User Manual
Table Of Contents
- QuikBridge Node repeater
- Product Summary
- Installation Overview
- Installation using a PC
- 1. Mount the repeater board in the enclosure.
- 2. Assemble the antenna shrouds and snap into place.
- 3. Connect the AC transformer leads and power the board.
- 4. Connect the USB cable from the PC to the repeater board.
- 5. Using the PC software, perform the initial configuration of the repeater.
- 6. Use the PC software to enter enrollment mode. Enroll the desired sensors into the repeater.
- 7. Mount the repeater in its final location.
- 8. Connect the AC transformer leads and power the board.
- 9. Connect the battery (if applicable).
- 10. Install the tamper switch.
- 11. Mount the enrolled sensors in their final locations.
- 12. Test the communication between the repeater and the base station receiver.
- 13. Test the communication between the enrolled sensors and the repeater.
- Installation Using the On-board DIP Switches
- 1. Mount the repeater board in the enclosure.
- 2. Assemble the antenna shrouds and snap into place.
- 3. Connect the AC transformer leads and power the board.
- 4. Connect the USB cable from the PC to the repeater board.
- 5. Using the PC software, perform the initial configuration of the repeater.
- 6. Mount the repeater in its final location.
- 7. Connect the AC transformer leads and power the board.
- 8. Connect the battery (if applicable).
- 9. Install the tamper switch.
- 10. Use the DIP switches to enter Enrollment Mode. Enroll the desired sensors into
- 11. the repeater.
- 12. Set the DIP switches back to Normal Mode.
- 13. Mount the enrolled sensors in their final locations.
- 14. Test the communication between the repeater and the base station receiver.
- 15. Test the communication between the enrolled sensors and the repeater.
- Mounting the Repeater
- Connecting the Antenna Shrouds to the Repeater
- Installing the Tamper Switch
- Powering the Repeater
- Initial Configuration
- Enrolling Sensors into the Repeater
- 1. Put the repeater in enrollment mode via the PC or the DIP switches.
- 2. Send an enrollment packet from the desired sensor. The method for sending the enroll ment packet varies depending on the type of sensor; see the installation instructions for each sensor for more information.
- 3. Verify that the enrollment packet was received by the repeater and that the sensor was enrolled, either through the PC interface or via the red LED.
- 4. Repeat until all sensors have been enrolled.
- Deleting Sensors from the Repeater
- PC Method
- DIP Switch Method
- 1. Put the repeater in individual delete mode via the DIP switches.
- 2. Send an enrollment packet from the desired sensor (the “enrollment” packet is used for both deletion as well as enrollment). The method for sending the enrollment packet varies depending on the type of sensor; see the installation instruct...
- 3. Verify that the packet was received by the repeater and that the sensor was deleted by watching for a long flash on the red LED.
- 4. Repeat for each sensor to be deleted.
- 1. Put the repeater in delete all mode via the DIP switches.
- 2. Verify that the red LED is blinking.
- 3. Press and release the tamper switch.
- 4. Verify one long flash on the red LED, signaling successful deletion of all sensors.
- Testing the Repeater Transmitter
- Testing the Repeater Receiver
- Enrolling Sensors into the Repeater
- Installation using a PC
- Specifications
- Notices
3
QuikBridge Node repeater Installation Instructions
Off
No Activity
00
Short Blink
On
Repeater received a packet from an enrolled sensor
01
Off
No Activity
01
Long Blink
On
Repeater received an enrollment-type packet from an
enrolled sensor and has deleted that sensor from
memory.
10
Off
No Activity
10
Long Blink
On
Repeater received an enrollment-type packet from an
unenrolled sensor and has enrolled that sensor into
memory.
11
Constant
Blinking
DIP switches are set to “delete all” mode, but repeater
is awaiting a press and release of the tamper switch
before it does the deletion.
11
Long Blink
On
Repeater has detected a press and release of the tamper
switch and deleted all sensors from memory
Installation
Overview
There are two basic installation methods, depending on whether the enrollment of sensors is
to be done using a personal computer (PC) or the DIP switches. Note that a PC is required for
initial configuration regardless of the method of sensor enrollment. The following are the
basic steps of each method. The steps are described more fully in later sections.
Installation using a PC
1. Mount the repeater board in the enclosure.