User's Manual
Table Of Contents
- About this Document
- Product Summary
- Installation
- General Sensor Installation Guidelines
- Install on a Wall
- 1. Determine a suitable location for the UFT.
- 2. Mark where the magnet will be installed.
- 3. Drill a 3/4” diameter hole 3/4” deep into the wall.
- 4. Push the magnet into the hole, magnet side first.
- 5. Remove the UFT cover by squeezing the cover ends firmly to release the tab on the cover from t...
- 6. Remove the circuit board from the UFT base by pulling back the plastic tab and lifting the bat...
- 7. Mark where the UFT will be installed over the magnet. See Figure 1 for acceptable magnet locat...
- 8. Verify the UFT reed switch is properly aligned with the installed magnet.
- 9. Mount the UFT base with screws or brads. Use spacers to compensate for metal surfaces or heigh...
- 10. Reattach the circuit board to the UFT base
- 11. Attach the External Switch (See “Connecting External Switch” in this manual)
- 12. Reattach the UFT cover to the UFT base.
- Install in an Electrical Box
- Mounting the box on a wall
- 1. Determine a suitable location for the UFT.
- 2. Mark where the magnet will be installed.
- 3. Drill a 3/4” diameter hole 3/4” deep into the stud or wall.
- 4. Mark where the box will be installed over the magnet.
- 5. Mark the box at the location where the magnet will enter the box.
- 6. Drill a 13/16” hole in the box at the magnet location.
- 7. Mark where the UFT will be installed on the box.
- 8. Verify the UFT reed switch is properly aligned with the magnet hole.
- 9. Mount the box using screws or brads making sure to align the hole in the box with the hole in ...
- 10. Push the magnet, magnet side first, through the hole in the box and into the hole in the stud...
- 11. Mount the UFT in the box using velcro strips.
- 12. Remove the UFT cover by squeezing the cover ends firmly to release the tab on the cover from ...
- 13. Attach the External Switch (See “Connecting External Switch” in this manual)
- 14. Reattach the UFT cover to the UFT base.
- Mounting the box in a wall
- 1. Determine a suitable location for the UFT.
- 2. Mark the box at the location where the magnet will be installed.
- 3. Drill a 3/4” hole in the box at the magnet location.
- 4. Insert the magnet into the hole.
- 5. Mark where the UFT will be installed on the box
- 6. Verify the UFT reed switch is properly aligned with the magnet.
- 7. Mount the box in the wall using screws or brads.
- 8. Mount the UFT in the box using velcro strips.
- 9. Remove the UFT cover by squeezing the cover ends firmly to release the tab on the cover from t...
- 10. Attach the External Switch (See “Connecting External Switch” in this manual)
- 11. Reattach the UFT cover to the UFT base.
- Mounting the box on a wall
- Connecting External Switch
- Programming
- 1. Set the panel to program mode.
- 2. Proceed to the LEARN SENSORS menu.
- 3. Select the appropriate zone type and zone number assignments.
- 4. Set the external switch in the alarm condition (open for a normally closed circuit, closed for...
- 5. Trip the sensors tamper switch by removing the sensor cover.
- 6. Exit program mode.
- 7. Place the cover back on the sensor.
- Testing
- Specifications
- FCC Notice
3
Preliminary 1/22/02
instructions or reference manual for complete programming
details.
1. Set the panel to program mode.
2. Proceed to the LEARN SENSORS menu.
3. Select the appropriate zone type and zone number
assignments.
4. Set the external switch in the alarm condition (open for
a normally closed circuit, closed for a normally open
circuit).
5. Trip the sensors tamper switch by removing the sensor
cover.
6. Exit program mode.
7. Place the cover back on the sensor.
Testing
The following steps describe the general guidelines for test-
ing the sensor. Refer to the specific panel installation
instructions or reference manual and the instructions for the
external switch for complete testing details.
1. Set the panel to the installer zone test mode.
2. Trip the sensor.
3. The signal strength from the UFT will be displayed on
all keypads. It should be 15 or higher for proper opera-
tion.
Specifications
Operating Temperature
Range: ...........................10° to 120° F
Compatibility: ...............Advent Commercial Fire 250 Zone
(60-562-03)
Advent Commercial Fire 132 Zone
(60-562-06)
Advent Commercial Burg 250
Zone (60-562-01)
Advent Commercial Burg 132
Zone (60-562-04)
Power Source: ...............1 AA 3.6-volt lithium battery (not
replaceable)
Transmit Range:............At least 500 feet, open air