Install Manual
Table Of Contents
- Appendix B: Reference Tables
- About This Manual
- Special Installation Requirements
- Planning the Installation
- Installing the System
- The panel must be mounted at least 10 feet from any DTIM or between any two DTIMs.
- Mounting the Panel
- 1. Remove the panel from the back mounting plate by lifting the tab located on the top and pullin...
- 2. Remove the wiring knockout.
- 3. Feed all device wires through the knockout and place the back mounting plate in position again...
- 4. Level the back mounting plate and mark the top and bottom mounting holes.
- 5. Install anchors where studs are not present.
- 6. Partially insert a screw into the top mounting hole location then hang the back mounting plate...
- 7. Recheck for level, insert the lower screw, and tighten both mounting screws.
- 8. Install the antenna. There are three antenna options to choose from:
- 9. Place panel cabinet into back mounting plate and snap into place.
- Connecting Detection Devices to Panel Zone Inputs
- Connecting the AC Power Transformer (22-117)
- Connecting the Backup Battery Pack
- Figure 7. Connecting the Battery Pack
- 1. Remove the panel housing from the back mounting plate by lifting the tab located on the top of...
- 2. Slide the battery pack into the space provided on the back of the panel (Figure 8).
- 3. Plug the battery pack lead into the slot provided next to the wire terminals (Figure 7).
- 4. Replace the panel housing into back mounting plate and snap into place.
- Powering Up the Panel
- Programming the Panel
- Mounting the Panel
- Do not wait more than 1-2 seconds between steps 5 and 6 or steps 6 and 7 after releasing the tamp...
- Figure 10. DTIM Tamper Switch and LED Locations
- 1. Remove the DTIM cover.
- 2. Press twice and # once. The display shows phones; devices; add.
- 3. Press #. The display shows zone 01 - trip.
- 4. Press the DTIM’s tamper switch three times, holding the tamper switch down on the third press ...
- 5. Press the DTIM tamper switch twice, holding the tamper switch down on the second press and wai...
- 6. Press and hold the tamper switch down until the LED flashes once. The panel beeps once indicat...
- Account Menu (1st Tier)
- Phones Menu (1st Tier)
- Number 1 and 2 (Phones—Phone 1 and Phone 2)
- 3rd Tier
- FMT - CID (Phones—Phone 1 and Phone 2)
- 3rd Tier
- High Lvl (Phones—Phone 1 and Phone 2)
- 3rd Tier
- Low Lvl (Phones—Phone 1 and Phone 2)
- 3rd Tier
- Openings (Phones—Phone 1 and Phone 2)
- 3rd Tier
- Closings (Phones—Phone 1 and Phone 2)
- 3rd Tier
- Backup (Phones—Phone 2)
- 3rd Tier
- Dial Dly (Phones)
- 2nd Tier
- Pre-Dial String (Phones)
- 2nd Tier
- DTMF Dial (Phones)
- 2nd Tier
- Devices (1st Tier)
- Table 2: Sensor Group Assigned to Device
- Table 3: Device Programming
- Add (Devices)
- 2nd Tier
- Delete (Devices)
- 2nd Tier
- Review (Devices)
- 2nd Tier
- Text (Devices)
- 2nd Tier
- 1. To select the zone you want to add text to press , till you get to the correct zone then press...
- 2. Press # then to scroll thru the base words, press # to select the word you want.
- 3. Press to change to the prefix words. Press # then to scroll thru the prefix words. Press # to ...
- 4. Press to change to the suffix words. Press # then to scroll thru the suffix words. Press # to ...
- 5. Press * to review what has been selected, then press to go to the next zone to change.
- 6. Repeat steps 2 thru 4 to change all zones.
- Table 4: Sensor Text
- Downloader (1st Tier)
- Codes (1st Tier)
- Timers (1st Tier)
- Fire related trouble beeps are not affected by Sleepy Time.
- Sleep Hour (Timers)
- 2nd Tier
- Options (1st Tier)
- KTP Arm (Options)
- 2nd Tier
- Police Panic (Options)
- 2nd Tier
- Emergency Panic (Options)
- 2nd Tier
- Fire Panic (Options)
- 2nd Tier
- Rcvr Trouble (Options)
- 2nd Tier
- Panel Tamper (Options)
- 2nd Tier
- Exit Ext (Options)
- 2nd Tier
- Swinger Shutdown (Options)
- 2nd Tier
- Quick Arm (Options)
- 2nd Tier
- Quick Exit (Options)
- 2nd Tier
- Auto Stay Arm (Options)
- 2nd Tier
- Supv Time (Options)
- 2nd Tier
- Alarm Verify (Options)
- 2nd Tier
- Demo Kit (Options)
- 2nd Tier
- Reports (1st Tier)
- Siren (1st Tier)
- Exit - DL (1st Tier)
- User Programing Menu Items
- Downloader Programming
- ToolBox Downloader Programming
- 1. Contact your downloader station and ask the operator to prepare to download to the panel.
- 2. Make sure the system is disarmed.
- 3. Go into installer program mode.
- 4. Press * to go to the exit - dl display.
- 5. Enter the installer or dealer code.
- 6. When the downloader session completes, a panel programmed status message will be displayed.
- 1. Call the panel location.
- 2. Let the phone ring once, then hang up.
- 3. Wait at least 10 seconds but not more than 40, then call the panel location again. The panel s...
- ToolBox Downloader Programming
- Testing the System
- Allegro
- Appendix A: Troubleshooting
- 1. Check that panel transformer is plugged into an unswitched outlet.
- 2. Check the AC circuit breaker to be sure the circuit is live.
- 3. Check that the backup battery is installed correctly and the AC power transformer is plugged in.
- 4. Check for proper panel and transformer wiring.
- 5. Measure the incoming AC voltage at panel terminals 1 and 2. It should read about 8 VAC.
- 1. Unplug the AC power transformer and disconnect the wires from the transformer and the panel.
- 2. Check transformer to panel wire for short or open circuits.
- 3. Plug in the transformer and check for 8.0 VAC at the transformer unconnected terminals. If zer...
- 1. Perform a battery test by entering and exiting sensor test.
- 2. Check that the backup battery is installed correctly and the AC power transformer is plugged in.
- 3. Measure the incoming AC voltage at the panel terminals 1 and 2. It should read about 8 VAC.
- 4. Remove the backup battery power by disconnecting the battery and replace the battery.
- 1. Check the AC circuit breaker to be sure the circuit is live.
- 2. Check for proper panel and transformer wiring.
- 3. Check that the transformer is supplying AC to the panel.
- 4. Check that the transformer is plugged into a nonswitched outlet and secured with the provided ...
- 1. Check your records to see if you have the customer’s access code(s) on file.
- 2. Verify the access code(s) using the Downloader.
- 3. Clear memory and reprogram the panel locally.
- 4. Use Apartment Manager code to enter program mode and view the primary and user codes.
- 1. Check your records to see if you have the install code on file.
- 2. Verify the install code using the Downloader.
- 3. Use the Dealer Code to enter program mode and view the installer code.
- 4. Call Technical Support for assistance.
- 1. Press STATUS for an indication of the problem.
- 2. Make sure all monitored perimeter doors and windows are closed.
- 3. Make sure all perimeter and interior sensors are closed.
- 1. Attempting to bypass a 24-hour sensor (a sensor that is active in all levels) that cannot be b...
- 2. Sensor is not active in the current arming level.
- 3. Sensor is not learned in.
- 1. Check that the premises phone line is working.
- 2. Perform a phone test.
- 3. Check for correct phone line wiring between the DTIM and RJ-31X Jack (see DTIM Installation In...
- 4. Verify that central station phone number is programmed into the panel. If necessary, reprogram...
- 5. Verify that the correct phone format (SIA or CID) is being used.
- 1. Sensor is not active in current arming level. Verify sensor group and retest.
- 2. Zone is not learned into panel memory. Enter installer program mode. Go to Devices, then Add a...
- 3. Verify wiring.
- 1. Check that the wireless sensor battery is installed.
- 2. Check the sensor battery for low voltage. Replace batteries, if necessary.
- 3. Use an RF Sniffer (60-401) to verify that sensor is transmitting.
- 4. Constant beeps from the RF Sniffer indicate a runaway (faulty) sensor. Remove the sensor’s bat...
- 5. Sensor is not learned into panel memory. Enter installer program mode—Devices, Add, and learn ...
- 6. Sensor may be out of range. Move sensor to another location.
- 1. Sensor tamper switch is tripped—sensor cover is off, not latched securely, or sensor is not mo...
- 2. Check the sensor battery for low voltage. Replace batteries, if necessary.
- 1. Use an RF Sniffer (60-401) to verify that sensor is transmitting. If sensor is not transmittin...
- 2. Change mounting position of sensor (from horizontal to vertical or vice versa) and test sensor...
- 3. Sensor signal is not reaching panel/receiver because sensor is too far away or there is too mu...
- 1. Perform a sensor test.
- 2. Call technical support for assistance.
- 1. Replace the battery and perform a sensor test.
- 2. Call technical support.
- 1. Perform a phone test.
- 2. Check to make sure manual phone test option is on.
- 3. Verify that high and/or low level reporting option is on.
- 4. Perform a sensor test to verify communication between the DTIM and panel. See Phone Test (Repo...
- 5. Check DTIM wiring (see DTIM installation instructions).
- 1. Verify Downloader Phone Number matches ToolBox setting.
- 2. Verify Downloader CODE matches ToolBox setting.
- 3. Verify Dealer CODE matches ToolBox setting.
- 4. Verify panel Account Number matches ToolBox setting.
- 1. Verify Downloader Phone Number matches ToolBox setting.
- 2. Verify Downloader CODE matches ToolBox setting.
- 3. Verify Dealer CODE matches ToolBox setting.
- FCC Notices
- Specifications
- Appendix A: Troubleshooting
12
Allegro
Preliminary 2/5/02
Emergency Panic (Options)
2nd Tier
(Default = off) This setting determines whether panel keypad
emergency panic buttons are enabled (on) or disabled (off). If
enabled, an immediate alarm will occur after the emergency
panic buttons are pressed for two seconds and the panel
displays the alarm as an emergency panic. If the DTIM is
installed with the system;
❑ An alarm report will be issued.
❑ If the dialer delay option is on, the report will be delayed
or can be aborted.
To turn the emergency panic on or off:
Press # to turn on or off.
Fire Panic (Options)
2nd Tier
(Default = on) This setting determines whether panel keypad
fire panic buttons are enabled (on) or disabled (off). If enabled,
an immediate Fire alarm will occur after the fire panic buttons
are pressed for two seconds and the panel displays the alarm as
a fire panic. If the DTIM is installed with the system, an
immediate alarm report will be issued.
Note
The alarm report cannot be aborted or cancelled.
To turn the fire panic on or off:
Press # to turn on or off.
Rcvr Trouble (Options)
2nd Tier
(Default = off) When Receiver Trouble is on, the panel reports
a receiver failure under the following conditions:
❑ A wireless sensor signal has not been received for two
hours or
❑ The receiver is being jammed with a constant signal.
Note
For UL Listed installations using wireless devices, Receiver
Trouble must be set to on.
To turn receiver trouble reports on or off:
Press # to turn on or off.
Panel Tamper (Options)
2nd Tier
(Default = on) Panel Tamper determines how the panel handles
possible tamper situations. When this feature is on, the panel
reports a panel tamper if the panel back cover or DTIM cover
is opened while the panel is armed. A police alarm will sound
and
PANEL TAMPER will be displayed. If this feature is off, the
panel will display a status message only.
To turn the panel tamper on or off:
Press # to turn on or off.
Exit Ext (Options)
2nd Tier
(Default = on) When Exit Extension is on, the panel restarts
the exit delay timer if the user re-enters the premises through a
standard delay door before the standard exit delay time
expires.
This helps prevent exit faults and false alarms by allowing
users to re-enter the premises for a forgotten item.
When this feature is off, the exit delay timer does not restart if
the user re-enters the premises, forcing the user to disarm the
system to avoid setting off an accidental alarm.
Note
For UL Listed Installations the Exit Extension option must
be set to off.
To turn exit extension on or off:
Press # to turn on or off.
Swinger Shutdown (Options)
2nd Tier
(Default = 1, Parameters = 1-2) This setting determines the
maximum number of times a sensor or zone can go into alarm
(during a single arming period) before the panel automatically
bypasses that sensor or zone. This feature only applies to
sensors or zones in groups 0, 1, 4, 6, 8-10, and 13-23.
When set to 1, the panel automatically bypasses a sensor or
zone after it causes an alarm. When set to 2, the panel waits
until a sensor or zone has caused a second alarm (during the
same arming period) before bypassing it. At any setting, the
automatic bypass is logged into the event buffer and can only
be viewed thru ToolBox.
The bypassed sensor or zone will be cleared (automatically
unbypassed) if the system receives no further activations from
that sensor or zone over the next 48–50 hours.
Changing the arming level also clears all bypassed sensors and
zones and resets the Swinger Limit count on all sensors and
zones.
To set the swinger shutdown:
Press #, enter desired number and then press #.
Quick Arm (Options)
2nd Tier
(Default = off) Quick Arm allows system arming without
using an access code. When Quick Arm is on, the system
arming level can be increased without entering an access code.
A valid access code is still required to disarm the system.
To turn quick arm on or off:
Press # to turn on or off.