User's Manual
Table Of Contents
- Learn Mode Commercial Rate- of-Rise Heat Sensors
- Product Summary
- Installation
- Guidelines
- Programming
- 1. Separate the sensor from the base by twisting the sensor counter-clockwise and pulling it off the base. Set the base aside.
- 2. Place the panel in program mode.
- 3. Proceed to the LEARN SENSORS menu.
- 4. When the panel prompts you for a sensor group number, enter the fire group number (26).
- 5. Select the desired sensor number.
- 6. When the panel prompts you to trip the sensor, press and release the tamper switch on the sensor (Figure 1). Sys tem sirens beep indicating successful programming.
- 7. Exit program mode.
- Testing
- 1. Place the panel in the sensor test mode.
- 2. Rub your hands together vigorously, until they feel hot.
- 3. Place the palm of one hand on the round disc of the sensor, for about 7 to 10 seconds.
- 4. Listen for the appropriate number of beeps from interior sirens and speakers (refer to the specific panel installation instructions).
- 5. Exit sensor test.
- 1. Plug in a portable hair dryer.
- 2. Hold the hair dryer about 12 to 18 inches away from the sensor, aiming it at the side of the sensor.
- 3. Listen for the appropriate number of beeps from interior sirens and speakers (refer to the specific panel installation instructions).
- 4. Exit sensor test.
- Mounting the Sensor
- Replacing Batteries
- Specifications