User's Manual
Table Of Contents
UTC. All Rights Reserved. 5 P/N 0000000 – Rev. A – 06 Nov 12
11. Disabling Zones
The system can bypass a zone, so the zone is not monitored when the
system is armed. This is useful when a sensor is being repaired. You
can only change the Bypass state of a zone when the system is
disarmed.
The system continues to log the activity of bypassed zones in the Event
History (see “View Zone Event History,” above).
To bypass a zone:
A. With the system disarmed, tap the Security app on the Home
screen.
B. Tap the Turn Zone Off button for the smoke alarm. The Turn Zone
Off button changes to Turn Zone On.
C. When the system is disarmed, the Security Status header shows
that some zones have been bypassed.
12. Troubleshooting
Detector does not power up properly or reports low battery
o Be sure the battery is fully seated within the battery
compartment and the polarity is correct.
o Check the battery voltage (3.0 VDC nominal).
Control Panel does not respond
o Use the 60-401 RF Sniffer to confirm that the detector is sending
messages for activation.
o Move or rotate the detector position.
o Be sure the detector is enrolled into the control panel properly.
o Be sure you are using a compatible control panel (see “Error!
Reference source not found.”).
Tamper condition does not restore
o Be sure the detector’s top cover is installed properly.
o Be sure there are no trouble indications at the detector.
o Be sure you are using a compatible control panel (see “Error!
Reference source not found.”).
If a tamper alarm occurs
o Be sure you are using a compatible control panel (see “Error!
Reference source not found.”).
o Be sure the control panel is in sensor test mode during sensor
testing.
Alarm/open condition does not restore
o Be sure the motion condition has cleared at the detector.
o Be sure you are using a compatible control panel (see “Error!
Reference source not found.”).
13. Specifications
Compatible panels -
Power One CR123 battery
Battery type 3.0 VDC lithium
Standby Current
00
µ
A (typically)
Battery life 5 years (typically)
Sensor PIR thermal
Range 12 m / 40 ft @ 90
o
RF Wireless Frequency 2.4 GHz
Audible alarm Control Panel Indication
Weight w/battery 0.20 lbs / 0.09 kg
Dimensions
3.94 x 2.52 x 1.50 in.
(100 x 64 x 38 mm)
Storage temperature -4 to 140°F (-20 to 60°C)
Operating environment 40 to 100°F (4.4 to 37.8°C)
Relative Humidity 10 to 95% non-condensing
14. Maintenance Tips
To keep your detector in good working order:
o Perform a RF Communication Test once a week.
o Never use detergents or solvents to clean the detector.
Chemicals can permanently damage or temporarily
contaminate the Fresnel lens.
o Avoid spraying air fresheners, hair spray, paint, or other
aerosols near the detector.
o Do not paint the detector. Paint may interfere with proper
sensor operation.
15. Regulatory Information
Manufacturer: UTC Fire & Security
WEEE Directive
2002/96/EC (WEEE directive): Products marked with this symbol cannot
be disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this product to
your local supplier upon the purchase of equivalent new
equipment, or dispose of it at designated collection points.
For more information see: www.recyclethis.info.
RoHs Directive
2002/95/EC RoHS Compliant. Hereby, UTC Fire and Security declares
that this device does not contain lead, mercury, cadmium, hexavalent
chromium, polybrominated biphenyls (PBB) or polybrominated
depheny ethers (PBDE) in more than the percentage specified by EU
directive 2002/95/EC, except exemptions stated in EU directive
2002/95/EC annex.
UL Rating
ANSI/UL 639 Recognized
FCC Compliance
FCC ID: QPY-6540UPI-Z
IC: 8303B-6540UPI-Z