User's Manual
Table Of Contents
UTC. All Rights Reserved. 6 P/N 0000000 – Rev. A – 06 Nov 12
13. Troubleshooting
Detector does not power up properly or reports low battery
Be sure the battery is fully seated within the battery compartment and
the polarity is correct.
Check the battery voltage (3.0 VDC nominal).
Control Panel does not respond
Use a wireless RF Sniffer to confirm that the product is sending
messages for activation.
Be sure the detector is enrolled into the control panel properly.
Be sure you are using a compatible control panel.
Tamper condition does not restore
Be sure the product is installed properly onto the mounting plate and
the mounting plate has a magnet.
Be sure there are no trouble indications at the detector.
Be sure you are using a compatible control panel.
If a tamper alarm occurs
Be sure you are using a compatible control panel.
Be sure the control panel is in sensor test mode during sensor testing.
Alarm/open condition does not restore
Be sure the smoke or heat has cleared at the product.
Be sure you are using a compatible control panel.
14. Specifications
Compatible panels -
Power two CR123 battery
Battery type
3.0 VDC lithium
Panasonic
®
CR123A, Sanyo
®
123A
Standby Current
35
µ
A (typically)
Battery life 5 years (typically)
Sensor Photoelectric
Sensitivity 2.2% +/- 1.3% / ft.
Drift Compensation Adj. 0.5% / ft. max.
Heat Detection - Fixed 135°F ± 5°F (57.2°C ± 2.8°C)
Heat Rate-of-Rise
15°F/min>105°F (8.3°C/min>
40.6°C)
Audible alarm 85 dBa @ 10’ (3M) temporal 3
Low Battery Beep 1 every 45 seconds.
RF Wireless Frequency 2.4 GHz
Weight w/battery 0.20 lbs / 0.09 kg
Dimensions 5.6" x 2.4" (14.2cm x 6.1cm)
Storage temperature -4 to 140°F (-20 to 60°C)
Operating environment 40 to 100°F (4.4 to 37.8°C)
Relative Humidity 0 to 95% non-condensing
15. Regulatory Information
Manufacturer: UTC Fire & Security
WEEE Directive
2002/96/EC (WEEE directive): Products marked with this symbol cannot
be disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this product to
your local supplier upon the purchase of equivalent new
equipment, or dispose of it at designated collection points.
For more information see: www.recyclethis.info.
RoHs Directive
2002/95/EC RoHS Compliant. Hereby, UTC Fire & Security declares that
this product does not contain lead, mercury, cadmium, hexavalent
chromium, polybrominated biphenyls (PBB) or polybrominated
depheny ethers (PBDE) in more than the percentage specified by EU
directive 2002/95/EC, except exemptions stated in EU directive
2002/95/EC annex.
UL Rating
ANSI/UL 217 Recognized, ANSI/UL 268 Recognized, C-UL-US, CSFM
Means of Conformity
We declare under our sole responsibility that this product is in
conformity with Directive 93/68/EEC (Marking) and Directive
89/336/EEC (EMC) based on test results using (non)-harmonized
standards in accordance with the Directives mentioned.
FCC Compliance
FCC ID: QPY-5XXNTT-Z
IC: 8303B-5XXNTT-Z
The device complies with part 15 of the FCC Rules as well as Industry
Canada Rules and Regulations license-exempt RSS standard(s).
Operation is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired
operation.
Conformité Réglementaire
Ce dispositif est conforme à la réglementation de la IC et (Partie 15) de
la FCC. Son fonctionnement est soumis à deux conditions : (1) ce
dispositif ne doit pas causer d’interférences nuisibles, et (2) ce dispositif
doit accepter toute interférence reçue, y compris les interférences
pouvant entraîner des conditions de fonctionnement indésirables.
WARNING: Changes to Section 15 – Regulatory Information is
strictly prohibited. Any changes or modification made to the product
without the permission of the manufacturer could void the user’s
authority to use this product.
16. Product Information
Fire Prevention and Escape
The purpose of an early warning smoke alarm is to detect the presence
of fire in its early stages and sound an alarm giving the occupant(s)
time to exit the premises safely.
Avoid Fire Hazards
No detection device can protect life in all situations. Therefore,
safeguards should be taken to avoid potentially dangerous situations
as
follows:
o Do not smoke in bed.
o Do not leave children home alone.
o Never clean with flammable liquids such as gasoline.
o Properly store materials. Use general good housekeeping
techniques to keep your home neat and tidy. A cluttered
basement, attic, or other storage area is an open invitation to
fire.