Technical information

Page 74
CP Series Callpoints
A comprehensive range of callpoints for use with
both conventional and addressable systems. All
the callpoints are designed to enable an alarm
signal to be given by breaking a glass element,
this operates a switch and is indicated by an LED
indicator. If required, an optional transparent
hinged cover may be installed to guard against
accidental operation.
Features
Integral LED indicator for easy identification of
operation
Surface or flush mounting
Extensive range of conventional and analogue
addressable callpoints
Test key facility, speeds maintenance visits
Optional transparent hinged cover
Hazardous areas models available (See
Special Hazards Section)
IP66 Waterproof models for external
applications
Technical Specification - (Indoor & Outdoor)
Housing: Modified Polyphenylene
Oxide[Noryl SE100]
Operating Temp.: -20
o
C to +70
o
C
Relative Humidity: up to 95% RH (non-
condensing)
Datasheet - Product Code PSF36 “CP200 Series
Break Glass Detectors”
Manual - Vol08A-02-D9/D10/D27 “Ancillaries
Manual
Typically the conventional callpoint devices draw
no current in the ‘off’ state, but when activated, will
present an alarm load to the fire detection control
panel. The alarm load is defined by the internal
resistance arrangement for the device.
Addressable callpoints contain an address unit
enabling connection to the MINERVA
Addressable range of fire controllers. The address
unit includes a custom chip and a 7-way DIL
Switch which is used to define the address of the
callpoint.
R2
R1
R2
R1
-
IN OUT
Typical Conventional Wiring
Callpoint
Loop
Black
IN
Red
OUT
-
Flying Leads
+
Typical Addressable Wiring
+ -
87mm
Red
51.5mm
15mmAlthough the callpoint can
be fitted on a 16mm deep
box this leaves little room
for the conductors: A
25mm deep box is
recommended.
Note: Contacts rated at 32Vdc @ 100mA
Indoor Callpoint
Weight: 200g
124mm
87mm
39mm
59mm
Outdoor Callpoint (IP66)
Weight: 400g
Outdoor Callpoint (IP55)
Callpoint Dimensions
Conventional Callpoints
Addressable Callpoints
79mm
123mm
110mm
123mm
110mm
Model Colour Type IP Range R1/R2 Ohms
CP200 Red Conventional Alert 44 120/470
CP210 Red Conventional Evacuate 44 49/39
CP230 Red Conventional Alert 66 120/470
CP270 Yellow Conventional Evacuate 44 47/39
CP920 Red Addressable 44 Not Applicable
CP930 Red Addressable 66 Not Applicable
CP937 Red Addressable 55 Not Applicable
Keyswitch White Conventional 44 Not Applicable
Commonly Used Callpoints