Technical information
Page 70
The LPBD521 module is used to drive the FireRay
2000 beam detector units directly from the
MINERVA loop. A single LPBD521 can be used to
power the analyser unit, the beam receiver unit
and the transmitter unit. Alternatively, two
separate LPBD521's can be used with one to
power the analyser unit and receiver units and the
second to drive the transmitter separately, either
from the same loop or a different loop. Up to 12
LPBD521's can be used per loop.
The module is addressable and will therefore take
one address on the loop.
Technical Specification
Powered: Loop
Temperature Range: -20
o
C to+70
o
C
Operating Humidity: up to 95% RH non-
condensing
Dimensions (PCB): 60H x 84W x 14D mm
Product Code
557.180.217
LPBD521 loop powered beam detector interface
module for use with FireRay 2000
Datasheet - Product Code PSF85 “Fireray 2000
Optical Beam Smoke Detectors”
Manual - Vol08A-02-D26 “Ancillaries Manual”
LPBD521 - Loop Powered Beam Detector Module
The LD40 linear heat detection system is used to
monitor fire (or overheat) conditions in confined
or polluted areas or where there are adverse or
unusually variable environmental conditions. The
sensor cable is unaffected by dust, moisture or
vibration and requires little maintenance.
Features
• Easy and cost effective installation
• Good sensitivity with adjustable alarm
threshold
• Open and short circuit monitoring
• Suited for outdoor and indoor applications
• Can be used in hazardous areas
• Mechanical protection is provided for cables in
areas where damage may occur
• Chemical resistance sheathing is available for
areas where petro-chemical corrosion may
occur.
Technical Specification
Dimensions: 170H x 105W x 111D mm
Weight: 0.55Kg
Operating Temp: -25
o
C to +70
o
C
Relative humidity: Up to 98% RH non-
condensing
Rating: IP55
Operating Voltage: +8 to +30Vd.c.
Quiescent Current: 60-80µA
Product Codes
516.016.005
LD40 High resistance sensor cable blue - 200M
reel
516.016.006
LD40 High resistance sensor cable black - 200M
reel (Nylon sheath suitable for petrochemical
exposure)
516.016.010
LD40 EOL Termination kit
516.016.011
LD40 In-line Jointing kit
516.016.012
LD40 Analyser module with conventional
detection zone interface. Requires a DM520 or
similar zone module interface to MINERVA/TFX
addressable loops
Datasheet - Product Code PSF42 “LD40 Linear
Heat Detection System”
Linear Heat Detection