Technical information
Page 66
514.001.009
CP220Ex Red Callpoint intrinsically safe for use
with BASEEFA certified conventional system 601.
Simple apparatus marking
514.001.017
IF500Ex Intrinsically safe addressable interface
module. May be used to interface simple
apparatus switch callpoint to MINERVA analogue
addressable system. For use on BASEEFA
certified System 602
514.001.023
CP540Ex Red callpoint intrinsically safe for use
with IF500Ex. Simple apparatus marking
514.001.052
CP950Ex MEDC weatherproof intrinsically safe
callpoint with integral analogue addressable
module
514.001.053
IF520Ex EExia MEDC SM87PB Stainless steel
heavy duty intrinsically safe callpoint push button
with integral IF500Ex analogue addressable
module
Intrinsically Safe Callpoints
A variety of Ex ‘ia’ Intrinsically safe callpoints are
available as standard using KAC and MEDC
callpoint housings.
The CP220Ex is a conventional callpoint for use
on BASEEFA Certified System 601. System 601 is
compatible with MINERVA 1 to 4, System 1700,
NT & MINERVA Addressable DM modules.
The IF500Ex is an Intrinsically safe addressable
interface module.
It can be used to interface simple apparatus to
MINERVA analogue addressable systems,
designed to BASEEFA Certified System 602.
The IF500Ex can interface to devices such as ‘H’
Series detectors & T54B heat probes. In addition
the CP540Ex is specifically designed for use with
the IF500Ex. The IF500Ex is fitted inside the
CP950Ex and the IF520Ex and BASEEFA Certified
as integrated units.
CP220Ex CP540Ex CP950Ex IF520Ex IF500Ex
Dimensions(H x W x D mm) 87 x 87 x 51.5 87 x 87 x 51.5 126 x 120 x 118 122 x 122 x 118 122 x 120 x 90
Weight 200g 200g 1.2Kg 4.1Kg 900g
Material Polycarbonate Polycarbonate Polyester Stainless Steel Polyester
Conventional Yes No No No No
Addressable No Requires IF500Ex Yes Yes Yes
Colour Red Red Red Red Grey
BASEEFA Cert. Simple Apparatus Simple Apparatus 89C2202 89C2202 89C2202
IP Rating IP67 IP67 IP66 & 67 IP66 & 67 IP67
Note: Variants are available on request
Product Codes
515.001.041
Spare key for IF520Ex callpoint and other
SM87PB models
517.001.120
System 601 EOL Unit (PK10)
Datasheet - Product Code PSF24 “System 601/602 for Hazardous Areas”
Manual - Vol08A-02-D11/D31/D32 “Ancillaries Manual”