Technical information

Page 59
Approvals
Interface BASEEFA FM Product Codes
Conventional 4-20mA Addressable Relay Ex ‘ia’ Ex ‘d’ Ex ‘d’
S231i+ 516.037.004
S231f+ 516.037.003
S232f+ 516.037.015
S241i+ 516.038.004
S241f+ 516.038.003
S251i+ 516.039.004
S251f+ 516.039.003
S252f+ 516.039.015
S261f+ 516.040.002
S262f+ 516.040.012
S200 Plus Triple IR Solar Blind Flame Detector
The MINERVA S200 PLUS flame detectors are
the latest Infrared solar blind and multi-channel
infra-red flame detectors with low power
consumption and high false alarm immunity.
The MINERVA S200 PLUS range of advanced
flame detectors is the most comprehensive range
available.
Features
Triple waveband infrared solar blind flame
detection for optimum false alarm immunity
Unrivalled black body rejection over a wide
range of source temperatures
Range adjustable to 50 metres for a 0.1m
-2
petrol pan fire
Discrimination of optical faults (dirty windows)
from other faults by the built-in self test
Housing designed for easy installation of
cabling
Flexible mounting and angular adjustment
3 x 20mm field cable entries
IP66/67 housing designed for external use
Rugged stainless steel ANC4 LM25 alloy
housing and mounting bracket
Operating temperature range of -40 to + 80°C
Variable response times and sensitivity
settings
Remote self test and range setting
True window test in detection area (i.e. not in
the edge of the window)
Terminals provided for Remote LED
connection
BASEEFA (CENELEC) certified
Meets the requirements of EN54 Pt10
FM, DNV and LRS certified
Very low power consumption (0.35mA)
Models available with Conventional or
Analogue Addressable interface (requires 2
core cable only)
Models also available with relay or 4-20mA
outputs
Patented dual filter solar blindness for
complete solar blindness
100°field of view on IS versions
90° field of view on Flameproof versions
Unlike other flame detectors on the market the
MINERVA S200 PLUS is available in both
Intrinsically Safe (EEx ia) and Flameproof (EEx d)
models.
The intrinsically safe models are suffixed by the
letter " i " and meet the requirements of EN50020
part 7 and are BASEEFA certified EEx ia IIC T5.
As part of an intrinsically safe circuit, it is suitable
for zones 0,1 and 2 where group IIC gases or
lesser hazards can be continuously present in
explosive concentrations.
The flameproof models are suffixed by the letter
"f" and meet the requirements of EN50018 and
are BASEEFA certified EEx d IIC T6. The
detectors are suitable for zones 1 and 2 where
group IIC gases or lesser hazards can be
intermittently present in explosive concentrations.
Technical Specification
Detector Material: Stainless Steel 316L
Dimensions: 167H x 167W x 89D MM
Weight: 4.5Kg
Gland Entry: 3 x 20mm
Metal Parts: Bright Stainless Steel 316
(external & internal) to BS
1449 Pt 2
Tag Label: Stainless Steel 316
Range: 0.1m
2
petrol at 50m
0.4m
2
petrol at 60m
Response Time: Field Selectable 3,6 and 12s
Sensitivity: 3 range settings
Relative Humidity: 95% (100% intermittent)
Enclosure to: IP 66 and IP 67
For information on flame detector test equipment,
please refer to the detector test equipment
section.
Approvals
BASEEFA Approved models are suffixed ‘1’.
NSTC: Approved
LPCB: Approved
LRS: Approved
DNV: Approved
KFEIC: Approved
SSL: Approved
MCA: Approved
FM Approved models are suffixed ‘2’. .
Datasheet - Product Code PSF102 “Minerva S200
Plus Series”
Special Hazard Detectors
Product Codes
592.001.016
T210 Test source for use with (517.001.224 ) Solo
704 Adaptor Tube B and Solo 100/101 Poles
(517.001.230/226)
592.001.014
T210 Adaptor required for the T210 to be used
with S200 and S200 Plus Flame detectors
Datasheet - Product Code PSF60 “T110/T210 Test
Source”
Manual - Vol01A-01-G1 “Detectors Fire Manual”
S200 Series Test Equipment