Technical information

Page 5
MINERVA is a comprehensive and reliable range
of networkable analogue addressable fire
controllers with over 60,000 installations
worldwide. MINERVA complies with BS5839 Pt 4
and can be installed to BS5839 Pt. 1.
The controllers and ancillaries are LPCB and
Marine approved with various other international
cross listings.
Features
8, 16 & 80 Zone networkable controllers
Seamless peer to peer networking
Full function repeaters
LPCB Approved
T890/891 Marine Approved variants
Mandarin option
Loop power sounder options
Wide range of addressable devices
Conventional system upgrade path
Continuous and pulsing sounders
Programmable mapping of signals for
controlled evacuation
On-site software configuration
Powerful cause and effect software
programming
Remote printer, mimic and VDU options
500 event memory
Pre-alarm capability
Threshold compensation for optimum detector
performance
Detector condition monitoring advises when
detector servicing is required
Weekly test reminder and walk test facility
Addressable intrinsically safe System 602
Surface and flush mount options
Technical Specification (Excludes Marine)
Dimensions: 320H x 440W x 140D mm
Approx. Weight: 7Kg
Colour: Dawn Grey BS4800 10-A-03
Installation: Surface or Semi-flush
Operating Temp: -10°C to + 55°C
Storage Temp: -20°C to + 65°C
Humidity: Up to 95% RH (Non-
condensing)
Housing Protection: IP43
Mains Supply: 110V-120V/220V-240V a.c.
± 10% at 50/60HZ ± 5%
Secondary Supply: 24V d.c. Nominal
NOTE: A self contained 2.7 amp switch mode
power supply together with 2 x 7 AH 12V or 4 x
10 AH 6V batteries may be fitted inside the main
housing of the MINERVA 8 or MINERVA 16E -
(See Note 1 for battery fixing kits). The MINERVA
80 requires a separate housing for its power
supply. Batteries up to 2 x 17 AH 12V may also be
fitted in this housing. See AC Power Module.
Datasheet - Product Code PB56 “Minerva 8, 16,
16E, 80 Panels”
Manual - Vol015A-02-D1 “Minerva Range of
Analogue Addressable Fire Controllers”
Technical Specification
LPCB Approved MINERVA 8 MINERVA 16E MINERVA 80
Marine Approved (Note4) - T891M T890M
Zones 8 16 80
Points 99 198 990
Zonal LED Display 8 16 80
LCD Display 80 Character 80 Character 80 Character
Sounder Circuits (2 off) 500mA each 500mA each 500mA each
Alarm Relay (1 off) 30Vd.c. @1.5A 30Vd.c. @1.5A 30Vd.c. @1.5A
Fault Relay (1 off) 30Vd.c. @1.5A 30Vd.c. @1.5A 30Vd.c. @1.5A
Product Codes
Control Panel Surface Mounting 557.180.564 557.180.550 557.180.556
Control Panel Flush Mounting 557.180.565 557.180.553 557.180.557
Marine Panel - 557.180.402 557.180.401
Repeater Panel Surface Mounting 557.180.566 557.180.554 557.180.558
Repeater Panel Flush Mounting - 557.180.555 557.180.559
Marine Repeaters (T290/291) - 557.180.404 557.180.403
Special Control Panel Variants -
Loop Powered Surface Mnt Panel Note 3 Note 3 557.180.569
Loop Powered Flush Mnt Panel Note 3 Note 3 557.180.570
Panel with Arabic overlay - 557.180.568 557.180.567
Panel with Dutch overlay 557.180.701 557.180.703 557.180.702
Panel with Mandarin graphics display - 557.180.575 557.180.576
MINERV A Analogue Addressable Fire Controllers
Additional Components
Note 1 : 557.180.055 MINERVA 8 and 16E battery fixing kit.
557.180.065 MINERVA 80 battery fixing kit
557.180.410 T890 battery fitting kit
Note 2 : 557.180.203 Loop Powered MINERVA 80 panels come complete with a special Loop
Powered ALXM (loop card) . An additional loop power ALXM card
(MINERVA-557.180.203) is required for each additional 2 loops.
557.180.014 ALXM (2 loop) expansion card for standard MINERVA 80
557.180.424 ALXM (2 loop) expansion card for T890
Note 3 : 557.180.092 MINERVA Loop powered insertion module converts MINERVA 8 and 16E
to Loop Powered panels.
Note 4: 557.180.454 T890/891 Bulkhead mounting kit