Technical information

Page 56
516.018.103 (571.104)
VRT-300 Remote VESDAnet socket
A display module monitors the VESDA LaserPLUS
detector. It reports a visual representation of
smoke levels, and all alarm and fault conditions.
The internal sounder warns personnel in the local
area that an alarm threshold has been reached,
or a fault has occurred.
It has a 20 segment vertical bar graph, a 2-digit
numerical display, an audible sounder and clear
alarm and fault indicators. It also has 4 push
buttons to control the detector and the mode of
the display.
Displays can be located at a convenient location -
either within the detector module, or remotely on
the VESDAnet. For monitoring convenience,
multiple displays can be associated with a single
detector.
Features
Four alarm levels (Alert/Action, Fire 1 & Fire 2)
20 segment vertical bar graph
Alarm threshold indicators
(Alert, Action & Fire 1)
Audio and visual indication
Alarm indicators
Informative fault indicators
Multi-mode numeric display(defaults to smoke
obscuration)
Acknowledged push-button presses
Multiple language supported
Addressable to any detector
Technical Specification
Supply Voltage: 18-30Vd.c. (when used in
detector unit, Remote unit or
19” rack)
Current Consumption: 60mAquiescent plus 20mA
alarm @24Vd.c. - (module
only)/90mA quiescent plus
20mA alarm @24Vd.c. (in
remote mounting box)
Dimensions: 150H x 140W x 90D mm
Operating Temp.: 0°C to +39°C
Humidity: 10-95% RH, non condensing
Optional Remote Displays
516.018.101 (571.084)
VRT-100 Remote programmer
516.018.102
VRT-200 Remote display including 7 relays
516.018.106 (571.082)
VRT-600 Remote detector display- no relays
516.018.119
VRT-J00 Compact Display c/w 7 relays
516.018.120
VRT-K00 Compact Display no relays
516.018.104
VRT-400 Remote scan display including 7 relays
516.018.107 (571.083)
VRT-700 Remote scanner display - no relays
516.018.108
VRT-800 Remote scanner display with 12 relays
VESDA LaserPLUS is also available in a Scanner
configuration, which allows the system to
distinguish and identify the pipe carrying smoke,
while sampling multiple sectors.
The VESDA LaserPLUS will continue to sample
from all sectors to monitor the fire growth and
maintain full protection.
Features
Individual pipe annunciation
Adaptive scan threshold
Wide sensitivity range (0.005 to 20% obs/m)
Laser based light source
Configurable alarm levels
Purpose built Aspirator
4 In-Line inlet pipes
Flow sensor for each pipe inlet
Low-cost maintenance
Dual stage filter
Easy access to filter cartridge
Recessed mounting
Technical Specification
Supply Voltage: 18 to 30Vd.c.
Current consumption:(No display or programmer)
240mA quiescent plus 70mA
alarm (24Vd.c. & 3000 rpm)
Dimensions: 225H x 350W x 125D mm
Weight: 4.0Kg including display and
programmer modules
Operating Temp.: 0
°
C to + 39
°
C
Humidity: 10-95% RH, non condensing
Relay Outputs: 7 or 12
LaserPLUS Scanners - 7 & 12 Relay Output Variants
516.018.004 (561.044)
VLS-214 FD7 Scanner, programmer and display
with 7 relays.
516.018.007 (561.039)
VLS-314 FD12 Scanner, programmer and display
with 12 relays
516.018.005 (561.045)
VLS-204 FD7 Scanner and display with 7 relays.
516.018.008 (561.040)
VLS-304 FD12 Scanner and display with 12 relays
516.018.006
VLS-200 FD7 Scanner
516.018.016 (561.046)
VLS-600 FD7 Scanner with Fire OK LED
516.018.009
VLS-300 FD12 Scanner
516.018.019 (561.041)
VLS-700 FD12 Scanner with Fire OK LED
Scanner Displays
Detector Displays