Technical information
Page 31
Introduction
The self-contained MXCE panels provide all the
required monitoring and control functions to
install a complete fire detection, alarm and
extinguishing system. The MXCE T540 and T550
controllers support 2 and 4 detection zones
respectively. Coincidence operation is available
as standard on zones 1 and 2. Additionally on
the T550, zones 3 and 4 can be used for
extinguishing (coincidence) or as independent fire
alarm zones.
The exceptionally priced T540 and T550
controllers are designed as feature enhanced,
aesthetically modern replacement for the current,
more expensive and heavily dated T530 and T520
Extinguishing panels. Additionally, the
introduction of 2-wire sounder capability
(detectors and sounders on the same 2-wire
circuit) to the extinguishing systems market will
achieve significant cost and installation savings.
Installation Features
The MXCE offers flexible mounting arrangements,
with easily removable door, multiple conduit
entries and large terminations, designed
specifically for simplified installation.
• Reversible back-box for top or bottom conduit
and cable entry
• Surface or semi-flush mount
• Terminations that suit up to 2.5mm
2
CSA cable
Power Supply
The power supply is designed to comply with the
latest standard (EN54 pt4). The internal mains
PSU provides all power plus charging and
monitoring of the 2 x 12V lead acid batteries (up
to 7 Ah).
• 1.8A PSU/Charger
• Panel battery capacity - 2 x 7Ah batteries
internally
Panel Functions
• Coincidence operation zones 1 and 2
• Optional coincidence operation on zones 3
and 4(T550)
• Auto/Manual select
• 2-wire sounders (on the detection zones)
Inputs and Outputs
• 2 or 4 zones
• First stage sounders (sounder circuit 1 and 2-
wire sounders)
• Second stage sounders (sounder circuit 2)
• Mode-select Auto/Manual input
• Extinguishing Disable input
• Hold button input
• Abort button input
• High and low pressure extinguishant monitor
inputs
• Manual electrical release input
• Signalling fault monitor
The following additional Inputs/Outputs are
available on the T550
• Fire and fault relays
• Mode select/status indication
• Mimic inputs (silence/reset/evacuate)
• Door interlocks
MXC-DIGI
A uniquely designed plug-in digital dialler which
fits inside the panel and provides fire, fire test and
fault signalling.
Sounders
Each MXCE zone can support up to sixteen Tyco
2-wire sounders, which can be any combination
of Tyco 602SBD sounder base units or wall
mounted Symphoni Sounders.
Panel Features
• Available in 2 and 4 zone variants
• Operates with Tyco 600 Series Conventional
Detectors
• All zones supports Tyco 2-wire sounders
• 4 zones variant offers extinguishing coinci-
dence functionality on zones 3 & 4
• T550 supports up to 3 x T56x Series of remote
Status Indicators
• Uniquely supports plug-in Central Station com-
municator within the panel unit
• Designed to comply with BS7273 and EN54
pts 2 &4
• Can be installed to meet the requirements of
BS5839 pt1
• MXCE LED display replaces T530 filaments -
reduces associated maintenance and time
costs
• Aesthetically pleasing design - 332W x 240H x
100D (mm).
Product Codes
508.030.501
MXCE T540 2 zone conventional extinguishing
controller
508.030.502
MXCE T550 4 zone conventional extinguishing
controller
509.030.005
MXC-DIGI Plug-in Scantronic Minicom
Communicator and mounting kit.
509.030.016
MXCE Zone End of Line Unit (Pk 8)
509.030.015
MXCE Spare Key (2 off)
MXCE Conventional Fire Detection & Extinguishing Controller