Technical information
Page 29
The range of NTR gas release panels are state-of-
the-art intelligent panels, which enable a wide
variety of gas release applications to be
implemented. The panel is provided with default
settings to suit most INERGEN
®
, FM200™ and
CO
2
applications and can be programmed to suit
most other gas releasing applications. For
compatibility with latest standards the panel
complies with all relevant parts of EN54 part 2
and 4. The NTR panel is designed to comply with
BS7273 and can be installed to fully comply with
BS5839 Pt 1 and BS6266.
System Operation (Default UK Operation)
Stage 1 - The panel stays in Stage1 Fire Alarm
until the fire or false alarm source is removed and
the panel is reset or Stage 2 ensues.
Stage 2 - The panel stays in Stage 2 for 30
seconds (adjustable) to provide a Pre-release
Warning during which time the HOLD or ABORT
sequences can be initiated.
Stage 3 - The panel remains in Stage 3 Gas
Release for the solenoid firing time or until the
release confirmation is received from the High
Pressure Switch.
Stage 4 - The panel remains in the Fire Alarm
condition and indicates the gas released
message until the system is silenced and reset.
Failure to receive a release confirmation will
initiate a fault.
The user interface is provided through a
combination of LEDs and a 2 x 40 character LCD
display. The LCD display provides a full customer
definable text display of the alarm or fault
condition whilst also displaying zones in alarm,
fault or isolate status. The display also indicates
the outputs that have been activated.
Features
• ANPI (BOSEC) Approved
• Customer friendly, multi language information
on LCD display
• Comprehensive fault diagnostics
• Manual release zone - direct to stage 2
• Can be used with a wide range of approved
detectors
• Detector removal monitoring
• 2 monitored Sounder outputs up to 4A
• 2 monitored Solenoid circuits
• 4 monitored Relay outputs
• 3 programmable auxiliary inputs
• 3 levels of alarm discriminations per zone
• One common fault relay
• Internal batteries (up to 12Ah)
• Programmable cause and effect
• Programmable user access levels
• Can interface to intrinsically safe System 601
• High and Low pressure monitoring
• Initial/Reserve changeover facility
• Optional Door Interlock
• Optional remote hold and abort
• Optional Auto/Manual key switches
• Optional I/O expansion board
• 16 digital outputs or 16 relay output options
Technical Specification
Dimensions 320H x 430W x 150D mm
Weight 6.3kg
Power Supply 198 -264Va.c.
Quiescent Current 50mA @ 24Vd.c.
Alarm Current 1Amp @ 24Vd.c.
Operating Temp 0 to +40°C
Operating Humidity 0-90% RH non-condensing
Note: The NTR is compatible with the T500 range
of ancillaries.
Datasheet - Product Code PSF106 “NTR Intelligent
Release Panels”
NTR100 Conventional Extinguishing Controllers
Product Codes
The following product codes include all the
optional extras which can be included as part of
your customer's requirements. Additional spare
parts are also included.
509.022.001
NT100 Series Spare Commissioning Kit Included
With All Panels
509.022.007
PRN-01 Optional Integral Printer For Use With All
NT Controller Variants
509.022.008
PRN-02 Spare Printer Paper For PRN-01 supplied
one per pack.
509.022.011
NT100 Spare PSU For NT,NTR & NTF Variants
509.022.013
NT Flush Mount Bezel
509.022.033
NT/NTR/NTF Display PCB Spare
Product Codes
NTR-08 NTR-16
Single Area Dual Area
UK 508.022.003 -
Belgian 508.022.004 -
Dutch - 508.022.021
Danish 508.022.006 508.022.02 5
Finnish 508.022.001 508.022.02 2
Norwegian - 508.022.023
Swedish 508.022.002 -
509.022.007
PRN-01 Optional Integral Printer for use with NT &
NTF Controller Variants
509.022.003
NTX-01 4 Way Expansion Board - Supplied Fitted
to the NTF And NTR Controllers. Also Supports
NTX-02,03,04 Expansion Boards
509.022.004
NTX-02 16 Way Relay Output Board
(24Vd.c.@1A) Requires NTX-01 Expansion Board
509.022.005
NTX-03 16 Way Digital Output Driver Board -
Requires NTX-01 Expansion Board
509.022.006
NTX-04 16 Way Digital Input Board for use on
Special NT Controller Variants only