Technical information
Page 22
The RMS series of manual pull stations are of high
quality non-toxic die-cast construction.
Low profile and smooth edges offer an attractive
yet functional design. All components are pre-
painted or have plated surfaces to inhibit
corrosion.
The RMS series of manual pullstations have a 10
amp snap action switch. They can be used with or
without a break glass rod for positive indication
that the unit has been operated.
Hazardous Locations
The RMS series of pull stations are constructed of
high strength metal die cast alloy.
The UL rating of Class I Group B (Hydrogen) C &
D, Class II Groups E, F, G, Class III and outdoor
rating of type 4X, allows these stations to offer
unmatched placement flexibility. The terminal
block connections, D.P.D.T contacts @ 10 amps
meet most electrical requirements.
Having a ‘conventional’ pull station design the
RMS series stations offer easy identification.
Features
. Die cast metal construction
. Low profile functional design
. Dual action option
. Institutional (Key operated) option
. Explosion proof option
. Break glass option
. Weatherproof option
. Hex screw or key lock reset options
. UL Listed
Technical Specification
Dimensions: 118H x 83W x 37D mm
(RMS-1T)
Weight: 560g (RMS-1T)
Contact: Single pole, single throw
(double pole, single throw
optional)
Contact Rating: 10 Amps @ 125/250Va.c.
Wire AWG: 12 to 22 AWG
Wiring: Terminal block connections
(6-32 w/sem plate)
Switch: 10 Amp @ 120Va.c.
Key Switch: (pre-signal) 0.5 Amp 30Vd.c.
Product Code
960673
TFX RMS-1T Single action non addressable pull
station
Pullstations & Ancillaries
The AUTOCALL IXA-RMS series of manual
pullstations are of high quality, non toxic, diecast
construction and connect directly to the
AUTOCALL TFX system. Using one of 126
available addresses on the loop, each station
responds to regular polls from the control panel
and reports its type and status.
Low profile and smooth edges offer an attractive
yet functional design. All components are pre
painted or have plated surfaces to inhibit
corrosion.
The RMS series of manual pull stations have a
10A snap action switch. All stations can be used
with or without a breakglass rod (included) for
positive indication that the unit has been
operated.
Programming with CONSYS allows an
addressable manual station to be automatically
programmed for “fast response” that invokes a
special polling interrupt routine. This results in a
one second alarm response. Systems which rely
on simple polling techniques to detect an alarm
can take longer to report manual alarms.
Features
. Die cast metal construction
. Low profile functional design
. Terminals for field wiring
. Powered directly by signalling circuit (no
additional power required)
. Programmable for normal or fast alarm
reporting
. Optional dual action
. Optional break glass
. Optional hex screw or key lock reset
Listings & Approvals
. UL Listed; File No. S165
. CSFM No. 7150-1493-156
Technical Specification
Dimensions: 118.75H x 80W x 22D mm
Wire AWG: 12 to 22 AWG
Wiring: Terminal block connections
Product Codes
976277
TFX IXA-RMS Addressable indoor pullstation for
use on TFX panels
960687
TFX Surface mount backbox for use with RMS
pullstations
960684
TFX Spare glass rod for use with RMS pullstations
Addressable Manual Stations
These alarm bells are ideal warning devices for
schools, stores, public buildings and any other
location with low to moderate ambient noise
levels. These alarm bells are completely enclosed
in an aluminium die cast housing with red
enamelled steel gongs. These alarm bells can be
mounted in standard outlet boxes or 4” x 4”
junction boxes. All are specifically designed for
use with fire alarm systems and are UL listed.
UL Spherical dB Measurement
Sound level measurements are made in
accordance with UL Test Standard 464. The
audible device is wall mounted in a reverberant
room and sound power output is measured at
various points along a 10’ radium from the wall
(i.e. the spherical dB measurement represents an
average of several readings taken along a 180
arc, 10 feet from the bell).
Indoor Measurement
Sound level in the indoor installation may vary
depending upon room size and acoustical
loading.
Product Code
508722
K-MP-6P 6” UL Bell 30mA 85dB
Notification Appliances - Motor Types
Technical Specification
Product Code Vibrating Type Rated Size (Inches) Rated Current Starting Voltage UL Spherical dB Indoor Measurement
Voltage Polarised Measurement
508722 24Vd.c. 6 0.03A 12V 84 86-89
508722