Owner manual

44 USG Exterior Ceiling Applications
Seismic Perimeter Applications
Celebration
Perimeter Conditions
1
Fixed
Floating
Note: 3/49 gap shown for typical seismic design categories D-F.
3/89 gap is typical for seismic design category C.
¹Other seismic detailing may be required. Please visit www.USG.com or www.seismicceilings.com for more information.
12 ga. hanger wire
Celebration
perimeter
panel
DXFEV F
INELINE
main or cross tee
compression post
8" max.
M7Z molding
ACM7 clip
fasten one through either
top hole and one through
the wing into the wall
arrowhead spacer for
cut perimeter panels
into first reveal row
arrowhead spacer for
cut perimeter panels
into first reveal row
12 ga. hanger wire
Celebration
perimeter
panel
DXFEV F
INELINE
main or cross tee
compression post
8" max.
3
/4"
M7Z molding
fasten one through center
of slot and one through
the wing into the wall
ACM7 clip