35 USG Exterior Ceiling Applications
USG Drywall Suspension System
Test Record UL526A, B
Class 15 Uplift
System Components
Main runners DGL26 or DGLW26
Cross Tees DGL424 or DGLW424, or DGCL4 hat shaped cross channels (record UL526B)
Perimeter Molding DGWM24 angle mold or DGCM27 channel mold.
When angle mold is used, main runners and cross tees attached to molding with 1/2” type S screws.
Gypsum Panels – 1/2 in. thick, 4 ft wide, installed with long dimension perpendicular to cross tees. End joints centered along
cross tees, side joints to be centered along main runners.
– Gypsum board fastened to each cross tee with No. 8 by 1 in. long bugle head screws with one screw located
at midspan of cross tee and with additional screws located 12 in. o.c. beginning from center screw and with
screws located 1-1/2 in. from each gypsum board side joint.
– At gypsum board butt ends, a total of seven screws used, with one screw located at midspan of cross tee
and additional screws spaced 8 in. o.c. with one screw located 1-1/2 in. from wall board side joint. All screws
located max 1/2 in. from edge.
– End joints of adjacent sheets staggered min. 4 ft.
– Sheets fastened to lower leg of wall channel with screws spaced max 12 in. o.c.
Type Max Unbraced Length (in)
Compression Posts
3/49 x 1/29 x 0.0599 channel
31
3/49 x 1/29 x 0.0599 channel (Back-to-back)
46
1-1/29 x 7/329 x 0.0599 channel
31
1-1/29 x 7/329 x 0.0599 channel (Back-to-back)
41
3/49 EMT conduit, 0.049” wall thickness
59
1-5/89 25 gauge steel studs, 0.01799 min
97
1-5/89 25 gauge steel studs, 0.01799 min (Back-to-back)
128
– Back to back types shall be connected with stitch welds at 129 OC or with 1/49 dia bolts at 129 OC,
rst connection within 69 of each end.
– Compression posts to be located within 69 of expansion joints if applicable.
– All compression post notched at ends to t over bulb of main runner.
– Compression post fastened to main runners with type S coated steel screw or equivalent
– 33 ksi min steel.