Specifications
8
8
Start-Up Instructions
1. Plug the valve into an approved power source.
2. When power is supplied to the control, the screen will display “INITIALIZING WAIT
PLEASE” while it finds the service position.
3. If screen is locked, press MENU for 3 seconds to unlock. Press SET/REGEN and hold for 3
seconds to initiate a manual regeneration. An option for delayed or immediate regenera-
tion will appear. Press the SET / REGEN button again and “Delayed” will begin flashing,
press the down arrow button to have “Immediate” flash. Press the SET / REGEN button
and then press the MENU button and the valve will immediately start moving to the
BACKWASH position.
4. Open the inlet on the bypass valve slowly and allow water to enter the unit. Allow all air
to escape from the unit before turning the water on fully then allow water to run to drain
for 3-4 minutes or until all media fines are washed out of the softener indicated by clear
water in the drain hose.
5. Press any button to advance to the BRINE position. Check the water level in the brine
tank to insure the valve is drawing brine properly.
6. Press any button to advance to the RINSE position. Check the drain line flow. Allow the
water to run for 3-4 minutes or until the water is clear.
7. Press any button to advance to the REFILL position. Check that the valve is filling water
into the brine tank. Allow the valve to refill for the full amount of time as displayed on the
screen to insure a proper brine solution for the next regeneration.
8. The valve will automatically advance to the SERVICE position. Open the outlet valve on
the bypass, then open the nearest treated water faucet and allow the water to run until
clear, close the tap and replace the faucet screen.
9. Add salt into the cabinet tank.
10. Program time, date, hardness and people into controller using Programming Instructions
Programming Instructions
Key Pad Configuration
MENU BUTTON “ ”: The function of this key is to enter the level one programming
mode where the valve settings can be adjusted.
SET / REGEN BUTTON “•”: This button has two functions. The first is to initiate a manual
regeneration by holding the button for 3 or more seconds. The
second function is while in programming mode, pressing this key
allows the user to change the value of each setting.
UP / DOWN “ ”: These buttons are used to increase or decrease the value of the
settings while in the programming mode.