MID:COM 8000 Installation, Operation, and Maintenance Guide Reference for Installing, Operating, and Maintaining the MID:COM 8000 Computer, Printers, and Electronic Registers Including the MID:COM E:Count Electronic Register Midwest Computer Register, Corp. 1605 170th Street Hampton, IA 50441 Telephone: 641-456-4848 Fax: 641-456-4600 E-Mail: Sales@MidComCorp.com Web: www.MidComCorp.
TABLE OF CONTENTS TABLE OF CONTENTS.............................................. 2 TABLE OF FIGURES............................................... 6 Trademarks ................................................... 7 Copyright Notice ........................................... 7 Disclaimer ................................................. 7 Contact Information .......................................... 8 Email ...................................................... 8 Postal Address ............................
8000 Function 2 - Select Meter ............................ 8000 Function 3 – Load Truck .............................. 8000 Function 4 – Setup ................................... PRINT NAME AND .............................................. ODOMETER START .............................................. ODOMETER CALIBRATION ........................................ ODOMETER CALIBRATION ........................................ ODOMETER CALIBRATION ........................................
Special Note on E:Count Keyboard Entry .................... E:Count Register Display and Layout ......................... Figure 17. E:Count Wiring Diagram ........................ Section 5 – MID:COM E:Count Calibration....................... E:Count Overview and Theory of Operation .................. Meter Calibration and Temperature Compensation........... Meter Calibration (Un-compensated)....................... Temperature Compensation................................. Figure 18.
E:Count Controls the Valves ............................... 84 Ticket Ready............................................. 84 Delivery Menu Categories................................. 85 PRCODE – Product Code .................................. 85 DISVOL – Volumes ....................................... 85 SETUP – Enter Setup Mode ............................... 85 EXIT – Exit Delivery Menu ............................ 85 E:Count Register and 8000 Computer Delivery Procedure ....... 86 Figure 28.
TABLE OF FIGURES Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 8000 Back Panel Cable Connections.................. 14 8000 Back Panel Including Serial Ports.............
Trademarks MID:COM E:Count, MID:COM 8000 and their integrated software and hardware components are trademarks of Midwest Computer Register Corp. (MID:COM). Other brand and product names mentioned in this publication are trademarks or registered trademarks of their respective holders. Copyright Notice 8000 Users Guide v1.14.doc © 2008 Midwest Computer Register, Corp.
Contact Information You have several ways to interact with Midwest Computer Register, Corp. and its staff. If you have a suggestion you can email, write, or call us with the information below. Email Sales: Support: sales@midcomcorp.com http://www.midcomcorp.com/Contact.
Section 1 – MID:COM 8000 Installation Installation Overview These instructions describe the procedures to install a standard MID:COM 8000 computer register on a fuel delivery truck. Instructions for installing and using optional or additional accessories are included with those accessories. Attention to detail will insure long-term reliability. Mounting the Computer/Printer The MID:COM 8000 is supplied with an aluminum pedestal for mounting in the cab of the truck.
Power Hookup (continued) Make sure the negative terminal of the truck battery is grounded directly to the frame of the truck with a heavy conductor. The truck frame will be the connection point for all grounds. Locate the closest connection point to the positive terminal of the battery. Usually the heavy conductor attached to the battery post terminates to a junction block close by. This is where the 12-volt power will be picked up.
Power Hookup (continued) Terminate the shield and connect it to a nearby screw that is grounded. Use an Ohmmeter or test light to make sure the screw is grounded. A length of wire is supplied to create a ground cable from the underside of the pedestal top to the truck frame (use a 10GA single conductor cable and ring terminal and attach it to the underside of the pedestal top). Run the cable down to the top of the pedestal base and terminate again.
Truck Electrical System Checkout Procedure With the truck not running and all accessories off, measure the no-load voltage directly across the battery terminals. This voltage should be between 12.0 and 12.6 volts. A voltage reading less than 12.0 indicates a faulty battery. Replace the battery with a properly rated battery. This will insure proper operation under increasing load. With the truck running, the voltage should read between 13.5 and 14.0 volts.
Cable Routing Route the register cable from proximity of the register, down along the inside of the truck frame or along piping, and then into the cab. Keep away from other wiring as much as possible. Use the cable-ties supplied to secure the cable from movement and possible chaffing, and stay clear of moving parts. Where the cable must pass through a hole in sheet metal, use grommets to line the edge of the hole. The cable may run in a split loom or tubing to further protect it from weather and abrasion.
Figure 1. 8000 Back Panel Cable Connections Figure 2.
Computer Installation Checklist 1. Is the computer display clearly viewed from driver’s position? If not see “Contrast Adjustment” 2. Are cables routed away from moving parts? 3. Are computer and its cables free from rubbing on items in the cab? Check seat, dash, etc. 4. Is computer securely fastened to pedestal? 5. Is pedestal securely fastened to floor of cab? 6. Are grommets in place where cables pass through sheet metal? 7. Is register head sitting squarely on meter base? 8.
Installing the SRG00X-X Electronic Register and Accessories Spike Suppressor Installation All MID:COM 8000’s are shipped complete with one spike suppressor per register head, these are included in the installation kit. The spike suppressor must be installed across each hose reel solenoid – refer to the Solenoid Spike Suppressor Wiring Diagram on the next page.
Figure 3. Ferrite Cylinder Clamp Installation 8000 COMPUTER OR EPCM INSTALL ONE FERRITE CLAMP TO THE REGISTER CABLE AS CLOSE AS YOU CAN TO THE 9 PIN CPC CONNECTOR. REGISTER 8000 OR ECOUNT INSTALL ONE FERRITE CLAMP TO THE REGISTER CABLE AS CLOSE AS YOU CAN TO THE CPC CABLE ENTRY SEAL.
Figure 4.
SV104 Valve Wiring Instructions 3 Conductor Valve Cable Connections: Red = Connect to Both 1st and 2nd Stage Black = 1st Stage Shut Down White = 2nd Stage Shut Down The voltage present on an individual wire is dependent on the device connected to the valve: Red Wire Black Wire White Wire E:Count Register ---------------Constant Ground Switched +12 VDC Switched +12 VDC Valve Connections: 8000 Computer or SLS -------------------Constant +12 VDC Switched Solenoid Ground Switched Solenoid Ground Red to one
Figure 5. SV104 2 Stage Solenoid Valve Figure 6.
SV101 Solenoid Security/Preset Valve For Models 6501, 8000, SmartLink, and E:Count PART NUMBER DESCRIPTION Valve: 706-0006 Security valve for use with the 6501 register head, equipped with a short cable and a 2 pin nylon connector. 706-0004 Security valve for use with the 6501 computer’s ticket interlock feature, equipped with a long cable and ¼ inch “microphone” plug. 706-0015 Security/Preset valve for use with the 8000 computer, equipped with a long cable and 4 position circular plastic connector.
PART NUMBER DESCRIPTION Wiring: 706-0006 The valve comes pre-wired to the register head if it was ordered with the 6501 system or register head. For field installation, a ½ inch N.P.T. opening must be made in the register cover to accommodate the cable’s compression fitting. Route the cable through the register cover and plug the 2 pin connector onto the mating header on the right side of the headboard, just above the register cable plug. Install the compression fitting and replace the cover.
PART NUMBER DESCRIPTION Plumbing: MID:COM has supplied valves manufactured by two different companies: Asco and Parker-Skinner. Although they are functionally the same, they are constructed differently and their ports are numbered differently. Valves No Longer Available: ASCO P/N 832058 Green solenoid housing with three ports on main valve body. 1 Parker-Skinner P/N X54LB2XXX Gold solenoid housing with two ports on main valve body, and one port out the solenoid cover.
Security Valve Installation 1. Make sure the meter is blown down and safe to break pipe connections. 2. Remove the vapor line going to the differential valve. 3. Referring to the port designations below, connect the “common” port to the differential valve with a pipe nipple. NOTE: Fittings and hoses are user supplied. 4. Connect the vapor line to the “vapor” port. 5. Connect the “pressure” port to any source of liquid pressure upstream of the differential valve.
Mounting the Register Head The MID:COM 8000 mounts directly onto a Neptune 1-1/4” or larger meter with no adapters. All other meters use a Veeder-Root style mounting and therefore an adapter is necessary to convert from the Veeder-Root style to a Neptune configuration. MID:COM supplies three adapters for this purpose as listed below plus a fourth adapter for Neptune compensators. MODEL VR-1 This adapter is used in the majority of conversions.
VR-1 Adapter The gear plate from the Veeder Root register must be used with this VR-1 Adapter. Modify the gear plate by removing and discarding the bevel tooth gear. Also remove the 25-tooth brass gear and replace with the 39-tooth gear that is attached to the adapter. Secure gear screws. Figure 7.
Figure 8.
Figure 9.
Section 2 – MID:COM 8000 Operating Instructions 8000 General Rules and Operating Procedure The MID:COM 8000 uses a 22 key keyboard and 4 line alphanumeric display for operator control. Although the system is basically menu driven, prompting the operator for input, certain operations are particular to the 8000 and must be thoroughly understood for ease of operation. The operator is prompted through the various modes of operation by a series of “screens” on the display screen.
At times, the operator will have to input new prices, taxes, preset volumes, etc. The method of entry the 8000 uses is called S.E.A., which is an abbreviation for “select-enteraccept”. This is unique to the 8000 and must be understood completely. For example, to enter a new price, the operator presses the line key pointing to the price on the display. A blinking cursor will then appear over the first or leftmost digit of the price.
8000 Startup The following example illustrates the first three (3) screens that the operator encounters after starting the truck: [SCREEN 1] MID:COM 8000 SOFTWARE VER XXXX SELF TEST STAND BY [SCREEN 2] NO DATACARD INSERTED [SCREEN 3] MID:COM 8000 SOFTWARE VER XXXX SELF TEST OK [MAIN MENU]
8000 Function 1 - Printing Shift Totals When “Print Shift Totals” is selected, the operator will be prompted to insert a blank ticket. Once the ticket is inserted to its full depth, the 8000 will begin printing the current shift total information which includes the following: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Time and date of previous shift printout. Current time and date. Totalizer Truck number. Driver number. Plant number. Total gallons delivered since last print out.
8000 Function 3 – Load Truck When the “Load Truck” function is selected, the following screen will appear:
8000 Function 4 – Setup Selecting “Setup” places the operator in a set of screens used to configure the 8000 for how it will be used, set the clock, enable discounts, etc. Setup is required when the machine is installed and periodically when such things as daylight savings time may require the clock to be reset. The screens in “Setup” are shown and explained below. The operator may arrow-down through the screens, change what is necessary, and then press start/stop to return to the main menu.
ELAPSED TIME PRINT
Miles (or kilometers) shows the current mileage on the truck. A new number may be entered here to correspond with the actual mileage on the truck. The mileage figure is updated as the truck is driven. Because the sensor does not distinguish between forward and reverse, there is an inherent forward “creep” for this reading when compared to the actual odometer. “Abort” will leave this screen and return to the main menu or press start/stop.
Subtract the beginning odometer reading from the last and enter the difference in “miles (or kilometers) driven”. Be careful to note the position of the decimal point. When accepted, press “calibrate complete” to exit and return to the main screen. At this point, all setup has been complete. 8000 Function 5 – Loading the Tax Code Information Besides entering and using single tax rates explained in the following sections, the 8000 can accept and use multiple tax codes.
8000 Function 6 – Making a Delivery without a Datacard From the main menu, press the down-arrow key. If using the E:Count, the Product Code of the previous delivery must be valid or else “Invalid Product Code” displays. All four lines of the screen will show the values from the previous delivery. Therefore, if the information does not have to be changed, the operator simply presses the down-arrow key and he will be prompted to insert the delivery ticket and begin the delivery.
Short-cut Delivery Delivery with a Datacard 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Insert the customer Datacard in the slot marked DATACARD before starting the truck or while in main menu. Select ▼ from the main menu. Select either SCAN ACCOUNTS or ENTER ACCOUNT NUMBER with corresponding Line Key button. If SCAN ACCOUNTS, use ▼ to find the account on the card. If ENTER ACCOUNT NUMBER was selected, enter the account number using the number keys.
8000 Computer Register Ticket Specifications Model MCR-80 DOT Matrix Printer General Type: Snap set or continuous form, with or without an envelope Copies: Maximum of 5 copies or a total thickness of 0.017” Paper Type: Top copy – Carbonless self-contained Remaining copies – carbonless or carbon interleave Width: 4.0 to 5.0 inches - Printer side stops are field adjustable and factory set at 4.25 inches Length: Minimum 4.
Cautions: It is very important to have no discontinuities in form thickness in the print area. All parts of the form need to bound at the insertion edge. If the ticket uses an envelope, the edge of the envelope or a strip for the envelope cannot be present in the print area. Perforations on any parts of the form are also prohibited in the print area. Failure to observe these cautions may cause ticket tearing and printer problems, and void warranties.
Printer Model MCR-80 Adjustments The MCR-80 Printer is adjustable for ticket width, ticket depth, and vertical line spacing. Unless otherwise specified, the factory settings are for a 4-1/4 inch wide ticket, depth as described below, and line spacing of 6 lines per inches. To readjust the printer, refer to the instructions below and illustrations accompanying this document. Printer Ticket Width Adjustment is made by moving the right and left ticket guides in or out.
get hung up upon inserting a ticket. Also if the spacers are removed you must attach the switch to the switch plate with different screws (4-40 X ½ BDSLMS). If the switch tang is to be positioned near the shaft or the back of the tray, make sure the ticket will fully depress the tang until it bottoms on the switch housing. After tightening the screws, insure again the switch tang travels freely, does not bind on the edge of the slot in the ticket tray and it is fully depressed when the ticket is inserted.
Figure 10. Part Diagram for the 8000 Computer Figure 11.
Figure 12.
Figure 13.
Section 3 – MID:COM SRGXXX-X Register Calibration Calibration of the MID:COM SRGXXX-X register is done in the register head using numerically encoded switches. See the accompanying section describing the register module and calibration procedures. The register leaves the factory with a calibrator setting of 1.000, which equates to a 1:1 ratio. When replacing an existing Veeder-Root register be sure to transfer any necessary gear plate from the register.
Figure 14. Mechanical Register Calibration Comparison Mechanical Register Calibration Factor Settings CHANGE GEARS MID:COM CAL. SETTINGS CHANGE GEARS REG. SPIN S.B. SPIN S1,2,3,4 (Gallons) REG. S6,1,2,3,4 (Liters) SPIN 29 30 24 25 26 17 28 29 30 32 23 24 25 26 27 28 29 30 31 32 33 34 27 28 29 27 31 32 33 35 25 26 27 28 29 30 31 32 33 34 1.1379 1.1333 1.1250 1.1200 1.1154 1.1111 1.1071 1.1035 1.1000 1.0938 1.0870 1.0833 1.0800 1.0769 1.0741 1.0714 1.0690 1.0667 1.0645 1.
8000 Register Module Figure 15.
Switch Description and Calibration Instructions Used For Register Models SRG OXX-X Switches 1-4 (S1-S4) Meter Calibration Factor Range: 0.000 – 1.999 (000.0 to 199.9% of un-calibrated reading) SWITCH # Amount of change for each switch position S4 = 00.1 Units per hundred S3 = 01.0 Units per hundred S2 = 10.0 Units per hundred S1 = Calibrate above or below a 1:1 ratio, set to 0 or 1. *** To register more on the register, adjust switches to higher number.
Switch Description and Calibration Instructions Used For Register Models SRL 001-X Switches 1-4 (S1-S4) Meter Calibration Factor Range: 0.000 – 1.999 (000.0 to 199.9% of un-calibrated reading) SWITCH # Amount of change for each switch position S4 = 00.01 Units per hundred S3 = 00.10 Units per hundred S2 = 01.00 Units per hundred S1 = 10.00 Units per hundred S6 = Calibrate above or below a 1:1 ratio, set to 0 or 1. *** To register more on the register, adjust switches to higher number.
Section 4 – MID:COM E:Count Specifications Electrical Requirements Operating Voltage: 10-30 VDC unregulated Operating Current: Standby 275 mA Up to 2 solenoids activated: 1 A additional each Operating Environment Outdoors exposed to elements Temperature Range: -40ºC to +60ºC (-40ºF to 140ºF) Humidity: 100% Condensing Enclosure Aluminum permanent mold casting with epoxy powder coat Rating: IP-66 and NEMA-4 Silicone gasket for keyboard and cover seals Calibration and Program Screws seal with BUNA ‘O’ Ring Env
Inputs/Outputs Pulse Input Internal: 100 pulse-per-revolution quadrature encoder for rotational displacement meters External: Single or dual channel electrical output, 3 to 30 V signal (ppr) input input dual from from channel positive meters with Pulse Output Calibrated pulse output for remote counting or monitoring devices. Raw encoder pulse output for connection to small volume piston provers. Powered Control Outputs Three (3) High-side 12 V drivers for use with solenoid valves and other devices.
E:Count Register Display and Layout Figure 16. E:Count LCD and Keyboard Layout GALLONSLITRES ‘GALLONS’ or ‘LITRES’ indicates the current Volume Mode (US or Metric). VOLUME CORRECTED TO 60F15C Displayed whenever the Temperature Compensation is active. ‘60F’ in Gallons Mode, 15C’ in Liters mode. DELIVER Indicates Delivery Mode is active and will display until the Fuel Delivery Ticket prints. PRESET Indicates the being changed. PRODUCT Indicates the Product Code is being changed.
Special Note on E:Count Keyboard Entry The E:Count uses special technique called PRESS & HOLD for keyboard entry. This technique eases keyboard operation, especially when wearing gloves, in the absence of any audible or tactile feedback. Simply press a button and wait for the desired action. Examples: • For menus press & hold the mode key until the selection appears. o PRESS & HOLD to enter that selection. o PRESS & HOLD to exit the selection.
E:Count Register Display and Layout Figure 17.
Section 5 – MID:COM E:Count Calibration E:Count Overview and Theory of Operation Meter Calibration and Temperature Compensation The MID:COM E:Count model MCR-05 is a general purpose electronic meter register for use with mechanical positive displacement meter with rotational output as well as other types of meters with electronic pulse outputs. In the case of a rotational output, the E:Count has an internal 100 pulse per revolution (ppr) quadrature encoder which converts the meter rotation to a pulse train.
E:Count Overview (continued) The second step in calibration, and only step after initial installation, is to determine the calibration factor with a prover or master meter. For initial installation a factor of 1.0000 should be used as a point of reference. Subsequently use the present factor. With a factor near unity, the meter error as expressed by PROVER VOLUME/REGISTER VOLUME results in a percentage in which the error can be added or subtracted to the current calibration factor as needed.
E:Count Overview (continued) Temperature Compensation Temperature compensation is done by table lookup only. The E:Count is loaded with the appropriate API or ASTM table for the following products: Comp Table # -----------00 01 02 03 04 05 06 07 08 09 Description ----------UNCOMPENSATED PROPANE DIESEL/HEATING OIL GASOLINE LUBE OIL METHANOL ANHYDROUS AMMONIA JET-A FUEL JET-B FUEL ETHANOL The tables are interpolated and extrapolated as necessary to have 1024 entries ranging from -40 to +62.
E:Count Overview (continued) However, if the difference is large the following needs to be considered: 1. The displayed temperature will always correspond to the correct table value. 2. The resulting calculations using that value will also always be correct. 3. The table in the E:Count may not be the same as the one being used for the test. 4. The product being tested is not exactly the same as what the table is intended for.
Figure 18. Serial Preset Wiring Diagram SERIAL PORT FROM REGISTER Figure 19. FROM REGISTER SERIAL PORT FROM 8000 REGISTER PORT VALVE PORT Serial Preset Connector Box Diagram FROM 8000 FROM REGISTER THE INSIDE SERIAL PORT OF THE COMPUTER CONNECTS TO THE OUTSIDE 9 PIN CIRCULAR CONNECTOR OF THE REGISTER IN A DUAL APPLICATION, THE INSIDE SERIAL PORT OF THE COMPUTER CONNECTS TO THE MIDDLE CONNECTOR OF THE DUAL ADAPTER BOX.
E:Count 8000 Serial Preset – Continued SOFTWARE VERSIONS 8000 computer needs to have software version P8??X? for Gallons 8000 computer needs to have software version P15??X? for Litres Ecount register head needs to have software version E832G or higher and the EM8 or higher chip installed DIFFERENCES WITH SERIAL COMMUNICATION There must be a serial cable connecting the inside serial port of the 8000 to the outside 9 pin connector of the E:Count.
E:Count 8000 Serial Preset – Continued CHANGES IN THE 8000 On the load truck screen each product code from 01-99 stores it’s own quantity. Any product code with a quantity other than zero will print the quantity on board on the shift ticket. If you are using a datacard, after you select the customer, it gets the product code from the card and shows it on the display. With no datacard it will bring up the last entered product code.
E:Count Calibration Mode To enter Calibration Mode back out the – the E:Count will display CALBRT MODE and enter Calibration Mode. If the Compensator is turned ON, the VOLUME CORRECTED TO legend will display and the Net Volume will be displayed. If the Compensator is turned OFF, the VOLUME CORRECTED TO legend will NOT display and the Gross Volume will be displayed.
E:Count Calibration Mode (continued) Figure 20.
E:Count Calibration Mode (continued) Calibration PRCODE – DISVOL – CALFAC – TEMP F – TEMP C TABLE – MRATIO – CMPTBL SERIAL – AIRSEN – REGNUM – UNITS – EXIT – Menu Categories: Display or Change the Current Product Code Display Gross and Net Volumes Display or Change the Calibration Factor Display or Change the Product Temp in Degrees F Display or Change the Product Temp in Degrees C Display the current Compensation Table Value Display or Change the Meter Ratio Display or Change the Compensation Table Number
E:Count Calibration Menu Figure 21.
E:Count Calibration Menu (continued) E:Count Calibration Menu Categories PRCODE – Product Code • Press to set the current Product Code. • The Product Code is a 2-digit number from 00 to 99. • Use the keys to change the Product Code. • Press to save the Product Code and return to the Calibration Menu. Note: Changing the Product Code affects all calibration data.
E:Count Calibration Menu (continued) TEMP C – Temperature in Degrees Celsius • Press to display the Current Temperature. • The current Temperature in Degrees Celsius will be displayed (if the temperature probe is installed). • Use the and Arrow keys to change the Temperature set point for the probe. • Press to return to the Calibration Menu.
E:Count Calibration Menu (continued) CMPTBL – Temperature Compensation Table • Press to display Temp. Comp. Table. • Use the buttons to set the Temp. Comp. Table. • Press to save the Temp. Comp. Table and return to the Calibration Menu.
E:Count Calibration Menu (continued) AIRSEN – Optical Air Sensor • Press to display the Air Sensor setting. • Press the to ON to enable the Air Sensor. • Press the to OFF to disable the Air Sensor. • Press to save the Air Sensor setting and return to the Calibration Menu. NOTE: The AIRSEN requires an Electronic Air Sensor (or Electronic Air Eliminator) hardware to be installed. Contact your distributor for more information.
E:Count Register Valve Control Options When the MID:COM E:Count Electronic Register is connected to a MID:COM 8000 Electronic Computer, the E:Count is in control of the security valves. The Calibration must be performed on the MID:COM E:Count. E:Count Delivery - E:Count controls the valves 1. 2. 3. 4. 5. The driver manually enters the Preset Quantity on the E:Count. The E:Count will automatically shut the valves when the Preset Quantity has been reached.
Figure 23. E:Count Menu Reference when Used with 8000 MID:COM E:Count Commands Used with MID:COM 8000 Version: E833G April 10, 2008 PRESS MODE BUTTON TO DISPLAY FLOW RATE DURING DELIVERY Deliver Mode - Delivery Active MODE FRXXXX Rate = xxxx units/minute Press & Hold keys until the desired item is shown or until the desired action is taken.
E:Count Calibration Instructions A. E:Count Valve Control with Non-Compensated Register 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. BACK OUT CALIBRATION SCREW - WILL DISPLAY CALIBRATE PRESS MODE UNTIL PRCODE IS DISPLAYED, PRESS S/S CHANGE THE PRODUCT CODE TO WHAT YOU WANT TO CALIBRATE, PRESS S/S PRESS MODE UNTIL YOU SEE CALFAC, PRESS S/S VERIFY THERE IS A CAL FACTOR, ENTER A FACTOR OF 1.
E:Count Calibration Instructions (continued) B. E:Count Valve Control with Compensated Register 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34.
Electronic Versus Mechanical Temperature Compensation Although difficult to quantify, our experience in the meter calibration business has shown that as much as a 1 percent gain in delivery product can be gained by the use of electronic compensation. In some cases more. There are a number of reasons: 1. Mechanical compensators use expanding bellows, which can only approximate the actual characteristics of the product. In the case of propane, it is a very poor match.
Figure 24.
Figure 25.
Figure 26.
Section 6 – MID:COM E:Count Setup Mode Setup Categories NEWCOD – Display or Change the Security Code STAGE1 - Display or Change the Stage 1 Shutoff Value STAGE2 - Display or Change the Stage 2 Dwell Value EXIT - Return to Delivery Mode When entering Setup Mode the E:Count will require the operator to enter the Security Code to continue. After a valid Security Code is entered the E:Count will display the first Setup Category. To display the next Setup Category press .
E:Count Setup Mode (continued) Figure 27.
E:Count Setup Mode (continued) E:Count Setup Mode Category Details NEWCOD – Set Security Code • Press to set the Security Code. • The Security Code is 6 digits from 000000 to 999999. • Use the keys to change the Security Code. • Press to save the Security Code and return to Setup Mode. STAGE1 – Stage 1 (Fast Flow) Shutoff Volume • Press to set the Stage 1 Shutoff Volume. • The Stage 1 Shutoff Volume is a whole number from 00 to 99.
Section 7 – MID:COM E:Count Delivery Mode E:Count Delivery Menu E:Count Controls the Valves Ticket Ready Delivery PRCODE DISVOL SETUP EXIT Menu Categories – Display or Change the Active Product Code – Display the Gross and Net Delivery Volumes – Enter the Setup Menu - Return to Delivery Mode To display the next Delivery Menu Category press . To view or modify the Delivery Menu Category press .
E:Count Delivery Menu (continued) Delivery Menu Categories PRCODE – Product Code Press to set the current Product Code. The Product Code is a 2-digit number from 00 to 99. Use the keys to change the Product Code. Press to save the Product Code and return to Delivery Mode. Note on Product Code: Changing the Product Code affects all calibration data.
E:Count Register and 8000 Computer Delivery Procedure 1) Press on the 8000 computer until INSERT TICKET is shown. 2) Insert the ticket to print the ticket header. 3) If desired, press on the E:Count Register to access the E:Count Delivery Menu. a. This will allow you to select a Product Code, view Net and Gross volumes for the previous delivery, and access the Setup Menu. b.
Section 8 – MID:COM E:Count Program Mode To enter Program Mode in Delivery Mode back out the – the E:Count display will not change however the E:Count will be in Program Mode. Proceed as directed by MID:COM personnel to complete E:Count programming. To exit Program Mode (after programming is complete) tighten the - the E:Count will reset and will be in Delivery Mode. Figure 29. E:Count Program Mode E:Count Power-Up On Power-up the E:Count will: 1.
Section 9 – MID:COM 8000 Maintenance and Troubleshooting 8000 Maintenance Checklist 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. Cable connectors free of excess strain. Cables connected and locked in place. Battery connectors free of corrosion. Ignition line secured. Pedestal mounting assembly properly grounded. Ground lugs tight and free of corrosion. Cables free of nicks and cuts Register cover and calibration plate screws tight. Register mounting bolts tight.
MID:COM 8000 Operational Tests After the MID:COM has been installed, per the installation instructions supplied with the system, initial power up should be performed to test that the MID:COM has been installed correctly and that it is operating properly. The following is a brief run through simulating a basic delivery from start to finish covering correct responses VS incorrect responses with possible fixes.
4. If first screen appears like this: a. Replace CPU module. xxxxxxxxxxxxxxx xxxxxxxxxxxxxxx 5. If unit powers up to main menu then goes into power failure and then powers back up and then repeats itself over and over: a. The circuit breaker or fuse may have popped. Reset and check cable for shorts. b. Also power module may have a broken trace on the 12 volt or ground line, which may have been caused by a shorted register cable. Replace power module and register cable. 6.
Operation: Display Main Menu: Correct response: (No Datacard Inserted) Down arrow twice (3 times if using E:Count Register) to insert ticket screen. Incorrect Response: 1. If keyboard is inactive (no beep when button is depressed): a. Replace keyboard. 2. If keyboard is active (beep is heard) but screen does not advance: a. Replace CPU module.
Operation: Insert Ticket Correct Response: Upon insertion of a ticket, the ticket will depress a microswitch that activates the ticket clamp solenoid and drops the printer platen down allowing the ticket to travel to the stop switch. When the stop switch is activated the printer platen clamps down on the ticket and the printer will start to print information about this delivery. After information is printed, the register will reset to 0.
Operation: Begin Delivery with SRGXXX-X Register Correct Response: Delivery should displays. begin with gallons being registered on both Incorrect Response: 1. If no product flows: a. Check security or preset valve to be sure they are operational. Lights on top of power module will indicate if the proper signal has been sent to the valve. 2. Product flows but no registration on rear display: a. Check switch settings and connections to register module. b. The problem may be a faulty encoder.
Operation: Begin Delivery with E:Count Register Correct Response: Delivery should displays. begin with gallons being registered on both Incorrect Response: 1. If no product flows: a. Check security or preset valve to be sure they are operational. 2. If product flows but no registration on rear display: a. If DELIVER is visible on the display: i. Verify the correct Product Code (PRCODE) is selected for the current product type ii.
Operation: Computer Displays of Gallons Registered Correct Response: Computers display will show the gallons registered. Incorrect Response when using SRG-XXX-X Register: 1. No registration on computer display: a. Switch register cable to meter 2, b. Switch valve cable to valve 2, c. Select meter 2 on main menu, d. Try again. e. If OK: i. Replace power module when convenient. f. If still no registration: i. Replace register cable 1st, ii. Then replace CPU if problem continues.
Operation: Delivery Ticket Printing Correct Response: 1. Delivery ticket is printed and ticket is advanced out. 2. Once ticket has finished printing, remove ticket will appear on computers display. 3. Once ticket is removed, display will go back to the main menu. 4. Printer will have printed each line clearly with proper line spacing. Incorrect Response: 1. Print button is inactive and computer is locked up: a. Replace CPU module. 2. If print out is ghosting itself: a. Replace printer. 3.
Figure 30.
Figure 31.
Figure 32.
Figure 33. 8000 RF Noise Elimination Jumper Notes: • • • Connector J7 is shipped from the Manufacturer connected (set on both pins) Disconnect the jumper shorting block to both pins of J7 to eliminate RF Noise.
8000 Program Updates and Sipstick Replacement The MID:COM “sipstick” is the central processing unit(s) for the 8000 computer. These sipsticks contain the microprocessor and program/data memory that controls the unit. If a program change or update has been made, it’s necessary to replace the sipstick(s) as described below. The sipsticks are installed in both vertically and right-angle sockets as shown in the diagram in the “SIP Stick Installation” diagram on the next page.
Figure 34. 8000 Sipstick Installation Sipstick Caution The sipsticks are susceptible to damage by static electricity. It is very important to leave them in the anti-static package they came in until the moment before installation. Return the original to the package as soon as possible.
Figure 35.
INDEX 12-volt ........................................... 10, 11, 16 1st Stage Shut Down .................................. 19 2nd Stage Shut Down ................................. 19 6501 ................................................... 21, 22 access code ........................................ 34 account number ........................... 36, 40 actual odometer............................... 37 Air Sensor........................................... 72 air-ride seat....................................
gear-plates ........................................ 25 gross................................................. 51, 52 Gross................... 51, 52, 65, 67, 69, 84, 85 ground cable .............................................. 11 heat shrink ................................................. 13 hose reel .................................. 15, 16, 88, 95 Humidity ............................................... 53 ignition ...................................... 9, 10, 11, 89 Inputs/Outputs .................
Select Meter .............................................. 32 Serial Number ..................................... 71, 72 serial numbers ................................. 88 Setup Mode ....................... 81, 82, 83, 84, 85 shift totals ...................................... 32 Shock....................................................... 53 sipstick .................................................... 101 Skinner .................................................. 23 SLS .................................
VERSION HISTORY Version 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.