Instruction Manual

25 (75*)
75 (225*)
7
9
100 (300*)
150 (450*)
14
21
200 (600*) 28
to protect
Seconds
of emission
to protect
to protect
Seconds
of emission
Seconds
of emission
SHOOTING TABLE MODULAR 2 PLUS (max 28 sec.)
50 (150*)
75 (225*)
100 (300*)
7
9
14
150 (450*)
200 (600*)
250 (750*)
21
28
35
300 (900*) 40
to protect
Seconds
of emission
to protect
to protect
Seconds
of emission
Seconds
of emission
SHOOTING TABLE MODULAR 3 PLUS (max 40 sec.)
50 (150*)
75 (225*)
100 (300*)
6
9
12
150 (450*)
200 (600*)
250 (750*)
21
23
35
300 (900*)
400 (1200*)
40
46
to protect
Seconds
of emission
to protect
to protect
Seconds
of emission
Seconds
of emission
SHOOTING TABLE MODULAR 4 PLUS (max 46 sec.)
50 (150*)
75 (225*)
100 (300*)
6
9
12
150 (450*)
200 (600*)
250 (750*)
16
21
24
300 (900*)
400 (1200*)
500 (1500*)
27
37
48
to protect
Seconds
of emission
to protect
to protect
Seconds
of emission
Seconds
of emission
SHOOTING TABLE MODULAR 5 PLUS (max 48 sec.)
50 (150*)
75 (225*)
100 (300*)
150 (450*)
4
6
8
12
200 (600*)
250 (750*)
300 (900*)
400 (1200*)
16
20
24
32
500 (1500*)
600 (1800*)
700 (2100*)
800 (2400*)
40
48
56
64
to protect
Seconds
of emission
to protect
to protect
Seconds
of emission
Seconds
of emission
SHOOTING TABLE MODULAR 8 PLUS (max 64 sec.)
*Industrial standard as from other manufacturers
The value in the first column indicates the volume of the room to be protected, with respective seconds of emission reported in the second
column. The value in m³ varies depending on the density to be obtained. With the suggested value it is possible to get the maximum
density recommended to ensure the absence of any residual. In places where a little residual causes no problems, it is possible to increase
the shooting time. Please note that the more fog released, the more the time required to recover visibility. High levels of fog, over
recommended limits, can leave residual. Any residue usually goes away by itself within 24/48 hours, otherwise, being soluble in water, it is
enough to use a wet cloth for cleaning. If you desire to obtain an average of 1 meter visibility after 60 seconds, as specified by the
standard EN 50131-8 : 2019, as used as reference by all manufacturers of Fog generators, the number of shooting seconds it is to be
reduced in half.
Do not obstruct the nozzle when the generator is armed and bag is in.