System information

18
Special knowledge
When the C-46 is used without the Controller C-56 controlling
single or multiple zones it works as a full flow system in cooling
mode. The indoor influence is a supply temperature adjustment
that is depending on the difference of the indoor temperature
and the indoor set point. This means that the supply will be
increased if the indoor temperature is to low and it will be
decreased if the indoor temperature is too high. The size of the
adjustment is given by the indoor sensor influence parameter.
If the lower influence is set to 2 and the room temperature
is one degree below setpoint, the supply will be increased by
two degrees. If the upper influence is set to 2 and the room
temperature is one degree above setpoint, the supply will be
decreased by two degrees. The setting will not influence the
dew point control if the default setting is 4.
Using the Indoor sensor influence
Wireless Humidity Sensor H-56
The C-46 can handle up to 6 humidity sensors H-56. The
sensors should be placed in rooms where you expect the
highest humidity and cooling is activated.
The humidity in a zone, or room, is different depending on
several parameters. Especially sensitive are rooms where people
spend most of their time or rooms where there is a lot of
people.
The sensor should be placed in a representative spot in the
room / zone which is not affected by parameters such as direct
sunlight, electronic equipment or fireplaces.
Setting range: 0–8