Installation manual
Uponor Control System - Installation Manual 7
3.3 Connections
3.3.1 Controller description
6
-channel controller
12-channel controller
3.3.2 Connect the actuators to the controller
Example of an installation:
All actuators of a group are controlled by the thermostat
connected to the first actuator.
Do not "U-Link" with wire. The linking is automatic. The first
thermostat controls all following AC output (actuators) if no
thermostat is added there. One thermostat can control the
whole controller (14 outputs).
In this example, thermostat #01 controls the actuators on
terminals 1 to 4.
Thermostat #05 controls the actuator on channel 05 and also
controls channels 06 to 11 when no additional thermostat is
linked to 06 to 11.
In the following example, thermostat #03 is added, it
controls the actuator on channel 03 and also control
channel 04.
Thermostat #01 controls actuators on channels 01a and 01b
and channels 02a and 02b.
99
See controller picture in fold-out.
Mark
Description
Quick connector for 8 actuators
Power LED
230VAC 50Hz compartment
Quick connector for 6 thermostats
Mark
Description
Quick connector for heating / cooling relay
Quick connector for timer
Quick connector for Condense sensor
Quick connector for 14 actuators
Bi-color power LED (red for Heating mode and
green for Heating / Cooling mode)
Push-button for Heating or Heating / Cooling mode
230VAC 50Hz compartment
Quick connector for 12 thermostats
1
2
3
4
1
2
3
4
5
6
7
8
99
See wiring diagram in the fold-out.
There are two non-polarized wires to connect the
thermostat.
INSTALLATION_MANUAL_R3-04A.mif Page 7 Mercredi, 14. mars 2007 11:34 11