Technical data
5.13  Complete Interface I-75/76 installation
The illustration below shows how to complete the Uponor 
Interface I-75/76 installation.
To complete the Interface I-75/76 installation:
1  Check the entire installation.
  •  Check that Interface I-75/76 and thermostats have 
power.
  •  Check Interface I-75/76 for alarms.
2  Close the controller cover.
3  Fill in the installation report included in this manual and 
give all information about the system to the end user.
5.14  Optional: room by-pass (Interface I-76 only)
It is possible to use one room per controller as a by-pass. This 
means that the loops are opened for this room when all other 
loops on the controller are closed. This is needed by some heat 
pumps that need a minimum fl ow and load to operate correctly. 
If more than one controller is used it is possible to choose one 
for each controller. To reach the by-pass settings Interface I-76 
must be set to Installer level access.
1  On the Uponor screen, select Main Menu > Settings > 
Rooms > By Pass. 
2 Select Controller from the list and 
confi rm by pressing OK. 
3  Choose the relevant room for the 
by-pass function. 
5.15  Optional: auto-balance (Interface I-76 only)
The auto-balance function removes the need for manual 
balancing of the manifold at installation. The principle for 
automatic balancing is that the energy required by each loop 
is distributed in pulses. The length of the pulses in each loop is 
calculated from the actual heat demand of the room. The auto-
balance function requires an Interface I-76 set to Installer level 
access. To activate the auto-balance function of Interface I-76:
1  On the Uponor screen, select Main Menu > Settings > 
System Parameters > Auto Balance. 
2 In the Auto Balance screen, select 
Active and press OK. The auto-balance 
function is now activated. 
  When Auto-balancing is used all balancing valves on the 
manifold must be fully open.
5.16  Room check (Interface I-76 only)
The room check function checks that the loops and thermostats 
are correctly mapped. It works best at night to minimize 
interference from sunlight, kitchen appliances, and so on. It 
works only if there is a heat demand and the heating is running. 
You can choose which rooms to include in the test. To start the 
room check Interface I-76 must be set to Installer level access:
1  On the Uponor screen, select Main Menu > Settings > 
System Parameters > Room Check. 
2 On the Room Check screen, select 
Room Check Start/Stop and press 
OK. 
3  On the new Room Check screen the Room check function 
can be either started or stopped. Confi rm selection by 
pressing OK. 