Installation and Operation Manual
Table Of Contents
- Uponor Smatrix Wave PULSE
- Table of contents
- 1 Copyright and disclaimer
- 2 Preface
- 3 Uponor Smatrix Wave PULSE system description
- 3.1 System overview
- 3.2 Example of a system
- 3.3 Uponor Smatrix Wave PULSE components
- 3.4 Accessories
- 3.5 Functions
- 4 Install Uponor Smatrix Wave PULSE
- 5 Install Uponor Smatrix Wave PULSE room controller
- 5.1 Placement of room controller
- 5.2 Connect optional slave module
- 5.3 Attach room controller to the wall
- 5.4 Install room controller antenna
- 5.5 Install communication module
- 5.6 Connect actuators to room controller
- 5.7 Connect electrical underfloor heating
- 5.8 Connect input to room controller GPI
- 5.9 Connect output to room controller relays
- 5.10 Connect room controller to AC power
- 5.11 Test actuators
- 6 Install Uponor Smatrix Wave room thermostat
- 6.1 Uponor Smatrix Wave T-161
- 6.2 Uponor Smatrix Wave T-163
- 6.6 Uponor Smatrix Wave T-169
- 9 Install Uponor Smatrix Wave relay module
- 9.1 Placement of relay module
- 9.2 Attach relay module to the wall
- 9.3 Connect output to relay module
- 9.4 Register relay module to room controller
- 9.5 Use relay module to connect fan coils
- 9.6 Use relay module for time delayed two stage additional cooling (requires communication module)
- 10 Install another Uponor Smatrix room controller in the system
- 11 Finishing installation
- 12 Operate Uponor Smatrix Wave PULSE room controller
- 12.1 Principle of operation
- 12.2 Normal operation without optional scheduling programs
- 12.3 Operation with scheduling programs
- 12.4 Run mode
- 12.5 Room controller LEDs
- 12.6 Reset the controller
- 12.7 Unregister room controller channels
- 13 Operate Uponor Smatrix PULSE communication module
- 14 Operate Uponor Smatrix Wave thermostats
- 16 Maintenance
- 17 Troubleshooting
- 17.1 General
- Fluctuating floor temperature
- The room is too cold (or too warm in cooling mode)
- Thermostat setpoint is too low
- The temperature displayed on the thermostat changes after the thermostat is moved
- Installation report and room controller/channel numbering on the thermostat label doesn't match
- Installation report and room controller/channel numbering on the thermostatic head label doesn't match
- White indicator cannot be seen in window of an actuator
- Setpoint temperature displayed in the room information menu is lower than the temperature set on the thermostat
- ECO mode
- The room is too warm (or too cold in cooling mode)
- The floor is cold
- All rooms are cold (or warm in cooling mode)
- Disturbing noise from the pump at the same time every week
- No communication
- Communication failure between the room controllers
- 17.2 Troubleshooting after installation
- 17.3 Digital thermostat alarms/problems
- 17.4 Analogue thermostat alarms/problems
- 17.5 Thermostatic head alarms/problems
- The text “bAt” is shown in the display
- The text “POS” is shown in the display
- The display is off
- Radio transmission icon is displayed but the signals are received only when the thermostatic head is close to the antenna
- No radio transmission icon is displayed on thermostatic head screen when buttons are pressed
- 17.6 Communication module alarms/problems
- Alarms shown in Uponor Smatrix PULSE app
- The communication module has lost communication with Uponor cloud services
- The communication module has re-established communication with Uponor cloud services
- Software update failed
- Thermostatic head valve position error
- Floor temperature limit reached
- Faulty temperature sensor
- Faulty external temperature sensor
- Faulty relative humidity sensor
- Faulty Comfort/ECO switch
- Relative humidity sensor limit
- Faulty outdoor temperature sensor
- Faulty heating/cooling supply sensor
- External heating/cooling switch lost
- General systems alarm
- High supply temperature
- Low supply temperature
- Thermostat tamper alarm
- Low average temperature
- Relay module lost
- The communication module does not start
- Bad Wi-Fi connection
- Alarms shown in Uponor Smatrix PULSE app
- 17.7 Room controller alarms/problems
- 17.8 Contact the installer
- 17.9 Installer instructions
- 17.1 General
- 18 Technical data
The communication module has lost
communication with Uponor cloud services
This alarm will only be received as a push notification and/or SMS (if
activated) to the mobile phone number registered to the customer
account in Uponor cloud services.
• There is an communication error between the communication
module and Uponor cloud services. The communication module
LED is fixed red, or flashing orange.
-
Make sure the communication module is connected to an
internet connected router, via either Wi-Fi or ethernet.
-
Make sure the communication module is connected to the
room controller.
-
Restart the router if needed.
-
Restart the controller and communication module if
needed (unplug and plug in the controller from the wall
socket).
The communication module has re-established
communication with Uponor cloud services
This alarm will only be received as a push notification and/or SMS (if
activated) to the mobile phone number registered to the customer
account in Uponor cloud services
.
•
The communication between communication module and
Uponor cloud services is re-established, and the communication
module LED is fixed green.
Software update failed
• The room controller software update has failed.
1. Make sure all sub room controllers are within radio range,
and not shielded by any object.
2. Restart the room controller (power of
f and on again).
Contact the installer if the problem persists.
Floor temperature limit reached
• The floor temperature is either too high or too low. This may be
due to:
-
The floor is heated by the sun, or another heat source.
Wait until the floor temperature is lowered.
-
The floor is cooled by a cool draft, or similar. W
ait until the
floor temperature is higher.
-
Too high supply temperature to the room. Review the heat
source settings, if applicable.
-
Too low supply temperature to the room. Review the heat
source settings, if applicable.
-
Too high setpoint for the room. Reduce the setpoint.
-
T
oo low setpoint for the room. Increase the setpoint.
-
Floor temperature limit to low. Increase the limit.
Faulty temperature sensor
• An error has been detected with the internal temperature sensor
in the thermostat.
Replace the thermostat.
Faulty external temperature sensor
• An error has been detected with the external sensor connected
to the thermostat.
-
Make sure the correct thermostat control mode (settings
menu 4) is set in the digital thermostat
-
Check the connection of the external sensor.
-
Disconnect the external sensor and check it with an
ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram.
If the error persists, replace the external sensor.
Faulty relative humidity sensor
Note
RH control is activated in the Uponor Smatrix PULSE
app (requires communication module).
• An error has been detected with the internal relative humidity
sensor in the thermostat.
Replace the thermostat.
Faulty Comfort/ECO switch
• The room controller is having problem communicating with the
system device configured as an external switch.
Force the thermostat to transmit by opening/closing the external
switch.
If the problem persists:
-
The system device thermostat is out of range. T
ry to find a
new position for the system device thermostat and/or the
antenna, or, if possible, move any shielding objects
-
New installations in building shield radio signals (for
example, metal door safe). Try to find a new position for
the system device thermostat and/or the antenna, or, if
possible, move the shielding object
-
Low radio signal detected (sporadic communication with
the connected unit). The transmitter is working with
reduced signal intensity
-
The transmitter in the system device thermostat is faulty.
Replace the thermostat
Relative humidity sensor limit
Note
RH control is activated in the Uponor Smatrix PULSE
app (requires communication module).
• The relative humidity limit is reached.
Lower the humidity level by starting a dehumidifier or increasing
the supply temperature setpoint.
Faulty outdoor temperature sensor
• An error has been detected with the outdoor temperature sensor
connected to the public thermostat.
-
Check the connection of the outdoor temperature sensor.
-
Disconnect the external sensor and check it with an
ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram.
If the error persists, replace the external sensor.
73
|
Uponor Smatrix Wave PULSE
|
Installation and operation manual