Installation and Operation Manual
Table Of Contents
- Uponor Smatrix Wave PULSE
- Table of contents
- 1 Copyright and disclaimer
- 2 Preface
- 3 Uponor Smatrix Wave PULSE system description
- 3.1 System overview
- 3.2 Example of a system
- 3.3 Uponor Smatrix Wave PULSE components
- 3.4 Accessories
- 3.5 Functions
- 4 Install Uponor Smatrix Wave PULSE
- 5 Install Uponor Smatrix Wave PULSE room controller
- 5.1 Placement of room controller
- 5.2 Connect optional slave module
- 5.3 Attach room controller to the wall
- 5.4 Install room controller antenna
- 5.5 Install communication module
- 5.6 Connect actuators to room controller
- 5.7 Connect electrical underfloor heating
- 5.8 Connect input to room controller GPI
- 5.9 Connect output to room controller relays
- 5.10 Connect room controller to AC power
- 5.11 Test actuators
- 6 Install Uponor Smatrix Wave room thermostat
- 6.1 Uponor Smatrix Wave T-161
- 6.2 Uponor Smatrix Wave T-163
- 6.6 Uponor Smatrix Wave T-169
- 9 Install Uponor Smatrix Wave relay module
- 9.1 Placement of relay module
- 9.2 Attach relay module to the wall
- 9.3 Connect output to relay module
- 9.4 Register relay module to room controller
- 9.5 Use relay module to connect fan coils
- 9.6 Use relay module for time delayed two stage additional cooling (requires communication module)
- 10 Install another Uponor Smatrix room controller in the system
- 11 Finishing installation
- 12 Operate Uponor Smatrix Wave PULSE room controller
- 12.1 Principle of operation
- 12.2 Normal operation without optional scheduling programs
- 12.3 Operation with scheduling programs
- 12.4 Run mode
- 12.5 Room controller LEDs
- 12.6 Reset the controller
- 12.7 Unregister room controller channels
- 13 Operate Uponor Smatrix PULSE communication module
- 14 Operate Uponor Smatrix Wave thermostats
- 16 Maintenance
- 17 Troubleshooting
- 17.1 General
- Fluctuating floor temperature
- The room is too cold (or too warm in cooling mode)
- Thermostat setpoint is too low
- The temperature displayed on the thermostat changes after the thermostat is moved
- Installation report and room controller/channel numbering on the thermostat label doesn't match
- Installation report and room controller/channel numbering on the thermostatic head label doesn't match
- White indicator cannot be seen in window of an actuator
- Setpoint temperature displayed in the room information menu is lower than the temperature set on the thermostat
- ECO mode
- The room is too warm (or too cold in cooling mode)
- The floor is cold
- All rooms are cold (or warm in cooling mode)
- Disturbing noise from the pump at the same time every week
- No communication
- Communication failure between the room controllers
- 17.2 Troubleshooting after installation
- 17.3 Digital thermostat alarms/problems
- 17.4 Analogue thermostat alarms/problems
- 17.5 Thermostatic head alarms/problems
- The text “bAt” is shown in the display
- The text “POS” is shown in the display
- The display is off
- Radio transmission icon is displayed but the signals are received only when the thermostatic head is close to the antenna
- No radio transmission icon is displayed on thermostatic head screen when buttons are pressed
- 17.6 Communication module alarms/problems
- Alarms shown in Uponor Smatrix PULSE app
- The communication module has lost communication with Uponor cloud services
- The communication module has re-established communication with Uponor cloud services
- Software update failed
- Thermostatic head valve position error
- Floor temperature limit reached
- Faulty temperature sensor
- Faulty external temperature sensor
- Faulty relative humidity sensor
- Faulty Comfort/ECO switch
- Relative humidity sensor limit
- Faulty outdoor temperature sensor
- Faulty heating/cooling supply sensor
- External heating/cooling switch lost
- General systems alarm
- High supply temperature
- Low supply temperature
- Thermostat tamper alarm
- Low average temperature
- Relay module lost
- The communication module does not start
- Bad Wi-Fi connection
- Alarms shown in Uponor Smatrix PULSE app
- 17.7 Room controller alarms/problems
- 17.8 Contact the installer
- 17.9 Installer instructions
- 17.1 General
- 18 Technical data
• Transmitter working with reduced signal intensity
-
Force the thermostat to transmit by changing the
temperature setpoint
-
Replace thermostat
• The room controller antenna is installed inside a metal cabinet,
or too close to other shielding objects
-
Change the antenna location. If the problem persists,
contact the installer
• The communication module is installed inside a metal cabinet, or
too close to other shielding objects
-
Change the communication module antenna location. If
the problem persists, contact the installer
• New installations in building shield radio signals (for example,
metal door safe)
-
Try to find a new position for the thermostat and/or the
antenna, or, if possible, move the shielding object
Relative humidity icon is displayed in the alarm list
Note
RH control is activated in the Uponor Smatrix PULSE
app (requires communication module).
• The relative humidity limit is reached
-
Lower the humidity level by increasing the ventilation or
activating a dehumidifier
Floor temperature sensor icon is displayed in the
alarm list
• Faulty temperature sensor
-
Check the connection of the floor sensor
-
Disconnect the temperature sensor and check it with an
ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram, see External temperature
sensor resistance diagram, Page 105
• Incorrect thermostat control mode, or temperature sensor not
connected
-
Select correct thermostat control mode (settings menu 4)
Outdoor temperature sensor icon is displayed in
the alarm list
• Faulty temperature sensor
-
Check the connection of the outdoor sensor
-
Disconnect the temperature sensor and check it with an
ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram, see External temperature
sensor resistance diagram, Page 105
•
Incorrect thermostat control mode, or temperature sensor not
connected
-
Select correct thermostat control mode (settings menu 4)
Indoor temperature sensor icon is displayed in the
alarm list
• Faulty temperature sensor
-
Contact the installer or replace the thermostat
Remote temperature sensor icon is displayed in the
alarm list
• Faulty temperature sensor
-
Check the connection of the remote sensor
-
Disconnect the remote temperature sensor and check it
with an ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram, see External temperature
sensor resistance diagram, Page
105
• Incorrect thermostat control mode, or temperature sensor not
connected
-
Select correct thermostat control mode (settings menu 4)
External temperature sensor resistance
diagram
kΩ
°C
0
10
20
30
40
50
60
70
80
90
100
-20 -10 0 10 20 30 40 50 60 70 80
DI0000014
Temperature (°C) Resistance (kΩ)
-20 94
-10 54
0 32
10 20
20 12.5
30 8
40 5.3
50 3.6
60 2.5
70 1.8
80 1.3
14.4 Analogue thermostat alarms/
problems
An alarm is sent when more than 1 hours have elapsed since the
room controller communicated with the thermostat.
Uponor Smatrix Wave T-161
The LED on the thermostat flashes every two
hours, or low battery alarm displayed in the Uponor
Smatrix PULSE app (requires communication
module)
• Thermostat battery power is running low
-
Replace the battery
Uponor Smatrix Wave PULSE
|