Installation and Operation Manual
Table Of Contents
- Uponor Smatrix Wave PULSE
- Table of contents
- 1 Copyright and disclaimer
- 2 Preface
- 3 Uponor Smatrix Wave PULSE system description
- 3.1 System overview
- 3.2 Example of a system
- 3.3 Uponor Smatrix Wave PULSE components
- 3.4 Accessories
- 3.5 Functions
- 4 Install Uponor Smatrix Wave PULSE
- 5 Install Uponor Smatrix Wave PULSE room controller
- 5.1 Placement of room controller
- 5.2 Connect optional slave module
- 5.3 Attach room controller to the wall
- 5.4 Install room controller antenna
- 5.5 Install communication module
- 5.6 Connect actuators to room controller
- 5.7 Connect electrical underfloor heating
- 5.8 Connect input to room controller GPI
- 5.9 Connect output to room controller relays
- 5.10 Connect room controller to AC power
- 5.11 Test actuators
- 6 Install Uponor Smatrix Wave room thermostat
- 6.1 Uponor Smatrix Wave T-161
- 6.2 Uponor Smatrix Wave T-163
- 6.6 Uponor Smatrix Wave T-169
- 9 Install Uponor Smatrix Wave relay module
- 9.1 Placement of relay module
- 9.2 Attach relay module to the wall
- 9.3 Connect output to relay module
- 9.4 Register relay module to room controller
- 9.5 Use relay module to connect fan coils
- 9.6 Use relay module for time delayed two stage additional cooling (requires communication module)
- 10 Install another Uponor Smatrix room controller in the system
- 11 Finishing installation
- 12 Operate Uponor Smatrix Wave PULSE room controller
- 12.1 Principle of operation
- 12.2 Normal operation without optional scheduling programs
- 12.3 Operation with scheduling programs
- 12.4 Run mode
- 12.5 Room controller LEDs
- 12.6 Reset the controller
- 12.7 Unregister room controller channels
- 13 Operate Uponor Smatrix PULSE communication module
- 14 Operate Uponor Smatrix Wave thermostats
- 16 Maintenance
- 17 Troubleshooting
- 17.1 General
- Fluctuating floor temperature
- The room is too cold (or too warm in cooling mode)
- Thermostat setpoint is too low
- The temperature displayed on the thermostat changes after the thermostat is moved
- Installation report and room controller/channel numbering on the thermostat label doesn't match
- Installation report and room controller/channel numbering on the thermostatic head label doesn't match
- White indicator cannot be seen in window of an actuator
- Setpoint temperature displayed in the room information menu is lower than the temperature set on the thermostat
- ECO mode
- The room is too warm (or too cold in cooling mode)
- The floor is cold
- All rooms are cold (or warm in cooling mode)
- Disturbing noise from the pump at the same time every week
- No communication
- Communication failure between the room controllers
- 17.2 Troubleshooting after installation
- 17.3 Digital thermostat alarms/problems
- 17.4 Analogue thermostat alarms/problems
- 17.5 Thermostatic head alarms/problems
- The text “bAt” is shown in the display
- The text “POS” is shown in the display
- The display is off
- Radio transmission icon is displayed but the signals are received only when the thermostatic head is close to the antenna
- No radio transmission icon is displayed on thermostatic head screen when buttons are pressed
- 17.6 Communication module alarms/problems
- Alarms shown in Uponor Smatrix PULSE app
- The communication module has lost communication with Uponor cloud services
- The communication module has re-established communication with Uponor cloud services
- Software update failed
- Thermostatic head valve position error
- Floor temperature limit reached
- Faulty temperature sensor
- Faulty external temperature sensor
- Faulty relative humidity sensor
- Faulty Comfort/ECO switch
- Relative humidity sensor limit
- Faulty outdoor temperature sensor
- Faulty heating/cooling supply sensor
- External heating/cooling switch lost
- General systems alarm
- High supply temperature
- Low supply temperature
- Thermostat tamper alarm
- Low average temperature
- Relay module lost
- The communication module does not start
- Bad Wi-Fi connection
- Alarms shown in Uponor Smatrix PULSE app
- 17.7 Room controller alarms/problems
- 17.8 Contact the installer
- 17.9 Installer instructions
- 17.1 General
- 18 Technical data
All rooms are cold (or warm in cooling mode)
ECO mode symbol shown
• System in ECO mode
-
Change ECO profile or assign another profile to the room
-
Reduce the ECO setback value for the thermostat
-
Reduce the General ECO setback value in the Uponor
Smatrix PULSE app (requires communication module)
-
Cancel temporary ECO
Check the chiller information and operation mode
in the Uponor Smatrix PULSE app (requires
communication module)
• The system is in cooling mode
-
Correct signal from external device needed
Check the boiler information and operation mode in
the Uponor Smatrix PULSE app (requires
communication module)
• The system is in heating mode
-
Correct signal from external device needed
Disturbing noise from the pump at the same
time every week
• Change time for pump exercise in the Uponor Smatrix PULSE
app (requires communication module)
No communication
Communication error
• Registration lost
-
Contact the installer
-
Check the registration status of the room controller
• Software versions incompatible
-
Check software versions of the Uponor components in the
Uponor Smatrix PULSE app (or thermostat displays during
startup)
-
Contact the installer
• The antenna is installed inside a metal cabinet, or too close to
other shielding objects
-
Change the antenna location. If the problem persists,
contact the installer
• The communication module is installed inside a metal cabinet, or
too close to other shielding objects
-
Change the communication module location. If the
problem persists, contact the installer
• The thermostat, thermostatic head, or relay module is placed too
far from the communication module/antenna
-
Change the location of the communication module/
antenna, thermostat, thermostatic head, and/or relay
module. If the problem persists, contact the installer
Communication failure between the room
controllers
Communication error
• Registration to room controller is lost
-
Contact the installer
-
Check the registration status of the room controller
-
Check the room controller configuration
• The antenna is installed inside a metal cabinet, or too close to
other shielding objects
-
Change the antenna location. If the problem persists,
contact the installer
• The communication module is installed inside a metal cabinet, or
too close to other shielding objects
-
Change the communication module antenna location. If
the problem persists, contact the installer
14.2 Troubleshooting after
installation
The system does not start
The power indicator in the room controller is off
• There is no AC power to the room controller
1. Check that the room controller is connected to AC power
2. Check the wiring in the 24V compartment
3. Check that there is 115V AC power in the wall socket
There is 115V AC power in the wall socket
• Blown room controller fuse or faulty power cable
-
Replace the fuse and/or power cable and plug
Poor radio reception
Repeated radio alarms
• The antenna is installed inside a metal cabinet, or too close to
other shielding objects
-
Change the antenna location. If the problem persists,
contact the installer
• The communication module is installed inside a metal cabinet, or
too close to other shielding objects
-
Change the communication module antenna location. If
the problem persists, contact the installer
• Building structure unfavourable for radio transmission
-
Change the antenna location. If the problem persists,
contact the installer
69
|
Uponor Smatrix Wave PULSE
|
Installation and operation manual