Installation and Operation Manual
Table Of Contents
- Uponor Smatrix Wave PULSE
- Table of contents
- 1 Copyright and disclaimer
- 2 Preface
- 3 Uponor Smatrix Wave PULSE system description
- 3.1 System overview
- 3.2 Example of a system
- 3.3 Uponor Smatrix Wave PULSE components
- 3.4 Accessories
- 3.5 Functions
- 4 Install Uponor Smatrix Wave PULSE
- 5 Install Uponor Smatrix Wave PULSE room controller
- 5.1 Placement of room controller
- 5.2 Connect optional slave module
- 5.3 Attach room controller to the wall
- 5.4 Install room controller antenna
- 5.5 Install communication module
- 5.6 Connect actuators to room controller
- 5.7 Connect electrical underfloor heating
- 5.8 Connect input to room controller GPI
- 5.9 Connect output to room controller relays
- 5.10 Connect room controller to AC power
- 5.11 Test actuators
- 6 Install Uponor Smatrix Wave room thermostat
- 6.1 Uponor Smatrix Wave T-161
- 6.2 Uponor Smatrix Wave T-163
- 6.6 Uponor Smatrix Wave T-169
- 9 Install Uponor Smatrix Wave relay module
- 9.1 Placement of relay module
- 9.2 Attach relay module to the wall
- 9.3 Connect output to relay module
- 9.4 Register relay module to room controller
- 9.5 Use relay module to connect fan coils
- 9.6 Use relay module for time delayed two stage additional cooling (requires communication module)
- 10 Install another Uponor Smatrix room controller in the system
- 11 Finishing installation
- 12 Operate Uponor Smatrix Wave PULSE room controller
- 12.1 Principle of operation
- 12.2 Normal operation without optional scheduling programs
- 12.3 Operation with scheduling programs
- 12.4 Run mode
- 12.5 Room controller LEDs
- 12.6 Reset the controller
- 12.7 Unregister room controller channels
- 13 Operate Uponor Smatrix PULSE communication module
- 14 Operate Uponor Smatrix Wave thermostats
- 16 Maintenance
- 17 Troubleshooting
- 17.1 General
- Fluctuating floor temperature
- The room is too cold (or too warm in cooling mode)
- Thermostat setpoint is too low
- The temperature displayed on the thermostat changes after the thermostat is moved
- Installation report and room controller/channel numbering on the thermostat label doesn't match
- Installation report and room controller/channel numbering on the thermostatic head label doesn't match
- White indicator cannot be seen in window of an actuator
- Setpoint temperature displayed in the room information menu is lower than the temperature set on the thermostat
- ECO mode
- The room is too warm (or too cold in cooling mode)
- The floor is cold
- All rooms are cold (or warm in cooling mode)
- Disturbing noise from the pump at the same time every week
- No communication
- Communication failure between the room controllers
- 17.2 Troubleshooting after installation
- 17.3 Digital thermostat alarms/problems
- 17.4 Analogue thermostat alarms/problems
- 17.5 Thermostatic head alarms/problems
- The text “bAt” is shown in the display
- The text “POS” is shown in the display
- The display is off
- Radio transmission icon is displayed but the signals are received only when the thermostatic head is close to the antenna
- No radio transmission icon is displayed on thermostatic head screen when buttons are pressed
- 17.6 Communication module alarms/problems
- Alarms shown in Uponor Smatrix PULSE app
- The communication module has lost communication with Uponor cloud services
- The communication module has re-established communication with Uponor cloud services
- Software update failed
- Thermostatic head valve position error
- Floor temperature limit reached
- Faulty temperature sensor
- Faulty external temperature sensor
- Faulty relative humidity sensor
- Faulty Comfort/ECO switch
- Relative humidity sensor limit
- Faulty outdoor temperature sensor
- Faulty heating/cooling supply sensor
- External heating/cooling switch lost
- General systems alarm
- High supply temperature
- Low supply temperature
- Thermostat tamper alarm
- Low average temperature
- Relay module lost
- The communication module does not start
- Bad Wi-Fi connection
- Alarms shown in Uponor Smatrix PULSE app
- 17.7 Room controller alarms/problems
- 17.8 Contact the installer
- 17.9 Installer instructions
- 17.1 General
- 18 Technical data
10 Operate Uponor Smatrix Wave PULSE
room controller
10.1 Principle of operation
The room controller operates the underfloor heating/cooling
installation according to customer needs. T
emperatures can be
adjusted with thermostats located in each room, or if installed with the
Uponor Smatrix PULSE app (requires communication module).
As soon as the temperature measured at a thermostat is lower
(heating mode) or higher (cooling mode) than the setpoint
temperature, a demand to change the room temperature is created
and sent to the room controller. The room controller will open the
actuators according to current operating mode and other settings.
Once the set temperature is reached, this information is sent and the
actuators are closed.
The system supports different types of cooling methods and is setup
in the Uponor Smatrix PULSE app.
Available cooling methods in the Uponor Smatrix PULSE app.
• Underfloor cooling (UC)
Cooling in the system is achieved using underfloor loops.
• Fancoil (FC)
Cooling in the system is achieved using fancoils (connected to a
relay module registered to a room thermostat).
Note! Autobalancing (Installer settings) should be disabled in the
system.
In rooms where underfloor cooling is allowed and a fancoil is
installed, underfloor cooling is started when the room
temperature is a couple of degrees above setpoint (1st stage),
and the fancoil is started at setpoint (2nd stage cooling).
• Ceiling cooling (CC)
Cooling in the system is achieved using ceiling cooling (2-pipe or
4-pipe system).
Select if the system utilizes a 2-pipe or 4-pipe delivery solution
for heating/cooling.
-
2-pipe means one supply temperature to the system at a
time (heating or cooling).
Autoblancing disabled:In rooms where underfloor heating/
cooling is allowed. Underfloor cooling and ceiling cooling is
both started when the room termperature is about 1
degree above setpoint.
Autobalancing enabled: Ceiling cooling and underfloor
cooling will follow the current cooling demand.
-
4-pipe means separate independent heating/cooling
sources.
In heating mode:
The underfloor loops are used when there is a heating
demand. Ceiling cooling is used when there is a cooling
demand.
In cooling mode:
Underfloor loops and ceiling cooling are used at the same
time when there is a cooling demand.
See Uponor Smatrix PULSE app for more information about the
individual functions.
10.2 Normal operation without
optional scheduling -
programs
When the system is running in normal mode:
• In Heating mode, the actuators are open when room
temperatures are lower than the temperatures set on the
thermostats.
• In Cooling mode, the actuators are open when room
temperatures are higher than the temperatures set on the
thermostats.
See Uponor Smatrix PULSE app for more information about
different cooling configurations.
For more information see, Operate Uponor Smatrix Wave
thermostats, Page 81.
For more information see, Operate Uponor Smatrix Wave
thermostatic head, Page 97.
10.3 Operation with scheduling -
programs
Scheduling programs provide an option to switch selected rooms
between Comfort and ECO mode using a 7-day program. This
optimises the installation and conserves energy.
The use of scheduling programs requires at least one of:
• Uponor Smatrix Wave T-168 (programmable thermostat)
• Uponor Smatrix PULSE R-208 (required for mobile app access)
For more information see, Operate Uponor Smatrix Wave
thermostats, Page 81.
For more information see, Operate Uponor Smatrix PULSE
communication module, Page 80.
10.4 Run mode
During normal operation the room controller is in run mode.
Exit to run mode
3 s
SI0000176
If the room controller is in registration or forced mode, exit to run
mode by pressing the OK button until the LEDs turn off (about 3
seconds).
Uponor Smatrix Wave PULSE
|
Installation and operation manual
|