Installation and Operation Manual
Table Of Contents
- Uponor Smatrix Wave PULSE
- Table of contents
- 1 Copyright and disclaimer
- 2 Preface
- 3 Uponor Smatrix Wave PULSE system description
- 3.1 System overview
- 3.2 Example of a system
- 3.3 Uponor Smatrix Wave PULSE components
- 3.4 Accessories
- 3.5 Functions
- 4 Install Uponor Smatrix Wave PULSE
- 5 Install Uponor Smatrix Wave PULSE room controller
- 5.1 Placement of room controller
- 5.2 Connect optional slave module
- 5.3 Attach room controller to the wall
- 5.4 Install room controller antenna
- 5.5 Install communication module
- 5.6 Connect actuators to room controller
- 5.7 Connect electrical underfloor heating
- 5.8 Connect input to room controller GPI
- 5.9 Connect output to room controller relays
- 5.10 Connect room controller to AC power
- 5.11 Test actuators
- 6 Install Uponor Smatrix Wave room thermostat
- 6.1 Uponor Smatrix Wave T-161
- 6.2 Uponor Smatrix Wave T-163
- 6.6 Uponor Smatrix Wave T-169
- 9 Install Uponor Smatrix Wave relay module
- 9.1 Placement of relay module
- 9.2 Attach relay module to the wall
- 9.3 Connect output to relay module
- 9.4 Register relay module to room controller
- 9.5 Use relay module to connect fan coils
- 9.6 Use relay module for time delayed two stage additional cooling (requires communication module)
- 10 Install another Uponor Smatrix room controller in the system
- 11 Finishing installation
- 12 Operate Uponor Smatrix Wave PULSE room controller
- 12.1 Principle of operation
- 12.2 Normal operation without optional scheduling programs
- 12.3 Operation with scheduling programs
- 12.4 Run mode
- 12.5 Room controller LEDs
- 12.6 Reset the controller
- 12.7 Unregister room controller channels
- 13 Operate Uponor Smatrix PULSE communication module
- 14 Operate Uponor Smatrix Wave thermostats
- 16 Maintenance
- 17 Troubleshooting
- 17.1 General
- Fluctuating floor temperature
- The room is too cold (or too warm in cooling mode)
- Thermostat setpoint is too low
- The temperature displayed on the thermostat changes after the thermostat is moved
- Installation report and room controller/channel numbering on the thermostat label doesn't match
- Installation report and room controller/channel numbering on the thermostatic head label doesn't match
- White indicator cannot be seen in window of an actuator
- Setpoint temperature displayed in the room information menu is lower than the temperature set on the thermostat
- ECO mode
- The room is too warm (or too cold in cooling mode)
- The floor is cold
- All rooms are cold (or warm in cooling mode)
- Disturbing noise from the pump at the same time every week
- No communication
- Communication failure between the room controllers
- 17.2 Troubleshooting after installation
- 17.3 Digital thermostat alarms/problems
- 17.4 Analogue thermostat alarms/problems
- 17.5 Thermostatic head alarms/problems
- The text “bAt” is shown in the display
- The text “POS” is shown in the display
- The display is off
- Radio transmission icon is displayed but the signals are received only when the thermostatic head is close to the antenna
- No radio transmission icon is displayed on thermostatic head screen when buttons are pressed
- 17.6 Communication module alarms/problems
- Alarms shown in Uponor Smatrix PULSE app
- The communication module has lost communication with Uponor cloud services
- The communication module has re-established communication with Uponor cloud services
- Software update failed
- Thermostatic head valve position error
- Floor temperature limit reached
- Faulty temperature sensor
- Faulty external temperature sensor
- Faulty relative humidity sensor
- Faulty Comfort/ECO switch
- Relative humidity sensor limit
- Faulty outdoor temperature sensor
- Faulty heating/cooling supply sensor
- External heating/cooling switch lost
- General systems alarm
- High supply temperature
- Low supply temperature
- Thermostat tamper alarm
- Low average temperature
- Relay module lost
- The communication module does not start
- Bad Wi-Fi connection
- Alarms shown in Uponor Smatrix PULSE app
- 17.7 Room controller alarms/problems
- 17.8 Contact the installer
- 17.9 Installer instructions
- 17.1 General
- 18 Technical data
General System Alarm (requires
communication module)
GPI
WD0000002
Note
In systems with a communication module installed, the
function of the GPI is selected in Installer settings
during initial configuration, or in the System settings
menu.
1. Ensure that the power is disconnected from both the room
controller and the unit to receive an alarm signal from.
2.
Route the cable to/from the other unit via a cable entry
.
3.
Connect the cable to the room controller connector labelled GPI
.
5.9 Connect output to room
controller relays
Relay 1
(PUMP)
Relay 2
(BOILER)
CD0000008
Caution!
Changing status of the pump management and/or
cooling allowed (in the Uponor Smatrix app, requires
communication module) will set all relays to Not
configured. Which will have to be configured again.
Note
In systems with multiple room controllers (master/sub
configuration), all relays are initially set to Not
configured. Which will have to be configured during
installation.
Note
The room controller cannot supply power for the output.
Note
The room controller uses a dry contact connection on the
terminal block to control the output. When the relay
closes the function is activated.
Note
The electrical circuits of the output must be protected by
a circuit breaker with a maximum rating of 8 A.
The room controller has two relays which can be operated
independently
. A relay module can be used in installations where the
distance between the device and the room controller makes wiring
dif
ficult, or if more relays are needed.
The relays on the master room controller can be set to one of the
following combinations. A communication module is required to
change the relay configuration from default values.
Relay 1 (PUMP) Relay 2 (BOILER)
Circulation pump (default)
1)
Boiler (default)
Circulation pump
1)
H/C Switch
3)
Circulation pump
1)
Dehumidifier
5)
Chiller
1)3)
Boiler
Circulation pump
1)
Comfort/ECO
6)
Not configured Not configured
The relays on the sub room controller can be set to one of the
following combinations. A communication module is required for
configuration.
Relay 1 (PUMP) Relay 2 (BOILER)
Circulation pump
2)
H/C Switch
4)
Circulation pump
2)
Dehumidifier
5)
Not configured Not configured
1) Function only available when Pump management is set to Individual or
Common.
2) Function only available when Pump management is set to Individual,
otherwise "Not used" is shown in the Uponor Smatrix PULSE app.
3) Function only available when cooling is activated.
4) Function only available when cooling is activated, otherwise "Not used" is
shown in the Uponor Smatrix PULSE
app.
5) Function only available during relative humidity control (in cooling, no fan
coils).
6) This function is also used when connecting a ventilation unit.
28
|
Uponor Smatrix Wave PULSE
|
Installation and operation manual