Installation and Operation Manual

Ventilation (requires communication module)
RELAY 2 (BOILER)
WD0000006
Note
This connection requires a dry contact sensing input in
the ventilation unit.
Note
This relay function requires a communication module,
and must be set in Installer settings during initial
configuration, or in the System settings menu.
Note
In systems with a communication module, make sure that
room controller
, relay 2 (Boiler), is set to Comfort/ECO in
Installer settings.
1. Ensure that the power is disconnected from both the room
controller and the ventilation unit.
2. Remove the screw and open the cover for the optional
connections compartment.
3. Route the cable from/to the ventilation unit via a cable entry.
4. Connect the ventilation unit to the connection labelled Relay 2
(BOILER).
5. Secure the cable to/from the ventilation unit with a cable clamp
in the enclosure.
6. Close and secure the lid to the optional connections
compartment.
Relay function
The relay is closed when the Uponor Smatrix system is set to ECO.
The ventilation must be setup to lower its speed when the input is
closed (ECO), and to switch back when the input is opened again
(Comfort).
This function requires a communication module, and to change the
setting of the relay output (Installer settings) to Comfort/ECO.
5.10 Connect room controller to
AC power
1. Check wiring
SI0000037
Check that all wiring is complete and correct:
Actuators
GPI connection (Heating/cooling switch)
Relay connections (Circulation pump)
2. Close 115 V AC compartment
SI0000038
Ensure that the 115 V AC compartment of the room controller is
closed and the fixing screw is tightened.
3. Power up the room controller
SI0000039
Connect the power cable and plug to a 115 V AC wall socket.
32
|
Uponor Smatrix Wave PULSE
|
Installation and operation manual
115 V
60 Hz