The proPANEL® 90 unit offers a simple pumping station, used for radiant heating or as a high-temperature
loop. The proPANEL 90 is pre-wired to a control interface, meaning the pump relay is connected to the
control interface using a Cat5 cable. The panel is prepared to connect to the Climate Co˘ntrol Multifunction
hydronic controller and/or the Climate Co˘ntrol Network System. The panel features 1", stainless-steel
piping. The maximum recommended flow is 9 gpm.
Panel dimensions are 18" wide, 26" high and 7" deep; it weighs 26 lbs. The panel has a capacity of 90,000
BTUs at a 20 degree delta T.
Part No. Part Description Each Qty. List Price/Ea.
A3509000 proPANEL 90 1 $1,560.00
The proPANEL 90Z unit offers a pumping station with zoning capability (two zones). Featuring 1" valves
for zoning, the proPANEL 90Z is pre-wired to a control interface, meaning the pump relay is connected to
the control interface using a Cat5 cable. The two actuators controlling the valves are also
pre-wired into the interface. The panel is prepared to connect to the Climate Co˘ntrol Multifunction
Controller and/or the Climate Co˘ntrol Network System. The panel features 1", stainless-steel piping on the
primary side and ³⁄₄", stainless-steel piping on the secondary side. The maximum recommended flow is 4.5
gpm per outlet.
Panel dimensions are 18" wide, 26" high and 7" deep; it weighs 32 lbs. The panel has a capacity of 90,000
BTUs at a 20 degree delta T.
Part No. Part Description Each Qty. List Price/Ea.
A3509002 proPANEL 90Z 1 $2,244.00
The proPANEL 90M unit offers a one-temperature mixing and pumping station using a three-way
motorized mixing valve (0-10V). The proPANEL 90MZ is controlled by connecting it to a Climate Co˘ntrol
Multifunction Controller and/or the Climate Co˘ntrol Network System. The proPANEL 90M is pre-wired to
a control interface, meaning the pump relay and the mixing valves are connected to the control interface
using a Cat5 cable. Sensors are attached to the tubing to monitor the secondary supply temperature at the
selected level. They are also pre-wired to the control interface.
The panel features 1", stainless-steel piping. The maximum recommended flow is 9 gpm.
Panel dimensions are 18" wide, 26" high and 7" deep; it weighs 30 lbs. The panel has a capacity of 90,000
BTUs at a 20 degree delta T.
Part No. Part Description Each Qty. List Price/Ea.
A3509500 proPANEL 90M 1 $2,244.00
The proPANEL 90MZ unit offers a one-temperature mixing and pumping station with zoning capacity (two
zones). The proPANEL 90MZ uses 1" valves for zoning and a three-way motorized mixing valve (0-10V) for
mixing. To control the proPANEL 90MZ, it must connect to a Multifunction Controller and/or the Climate
Co˘ntrol Network System. The proPANEL 90MZ is pre-wired to a control interface, meaning the pump relay
and the mixing valves are connected to the control interface using a Cat5 cable. Sensors are attached to
the tubing to maintain the secondary supply temperature at the selected level; those are also pre-wired to
the control interface. The two actuators controlling the valves are also pre-wired into the control interface.
The panel features 1", stainless-steel piping on the primary side and ³⁄₄", stainless-steel piping on the
secondary side. The maximum recommended flow is 4.5 gpm per outlet.
Panel dimensions are 18" wide, 26" high and 7" deep; it weighs 37 lbs. The panel has a capacity of 90,000
BTUs at a 20 degree delta T.
Part No. Part Description Each Qty. List Price/Ea.
A3509502 proPANEL 90MZ 1 $2,830.00
proPANEL 90
Fully Assembled proPANEL® Units
proPANEL 90Z
proPANEL 90M
proPANEL 90MZ