User Guide
Plumbing Design Assistance Manual l Chapter 6 – Installation methods l 65
Supporting Uponor PEX pipe
Suspended runs of Uponor PEX pipe can be supported by the same conventional means as metallic pipe, using copper tube size
(CTS) hangers and supports. However, support spacing will vary depending on local code requirements.
Note: Uponor recommends using hangers and supports designed for use with plastic piping.
Nominal
pipe size
Spacing for bare PEX (Dimension A) Spacing with PEX-a Pipe Support (Dimension B)
International
codes
(IPC, IMC)
Uniform codes
(UPC, UMC)
National
Plumbing Code
of Canada
(NPCC)
International
codes
(IPC, IMC)
Uniform codes
(UPC, UMC)
National
Plumbing Code
of Canada
(NPCC)
½"
32" 32" 32" 6'-0" 6'-0" 6'-0"
¾"
32" 32" 32" 6'-0" 6'-0" 6'-0"
1"
32" 32" 32" 8'-0" 8'-0" 8'-0"
1¼"
32" 48" 32" 8'-0" 8'-0" 8'-0"
1½"
32" 48" 32" 8'-0" 8'-0" 8'-0"
2"
32" 48" 32" 8'-0" 8'-0" 8'-0"
2½"
32" 48" 32" 8'-0" 8'-0" 8'-0"
3"
32" 48" 32" 8'-0" 8'-0" 8'-0"
Table 6-2: Horizontal support spacing requirements for Uponor PEX pipe
Figure 6-4: Maximum allowable support spacing for bare-PEX pipe
Figure 6-5: Maximum allowable support spacing for PEX pipe with PEX-a Pipe Support
Uponor PEX pipe
Uponor PEX-a Pipe Support
Stainless-steel strapping
B
Uponor PEX pipe
AA